Technical Data 1007 Effective August 2018
Supersedes February 2016
Low-Peak™ LPJ Class J 600Vac/300Vdc,
70-600A, dual element, time-delay fuses
Catalog symbols:
• LPJ-(amp)SP (non-indicating)
• LPJ-(amp)SPI (indicating)
Description:
Bussmann® series Ultimate protection LPJ Class
J dual element, current-limiting, time-delay fuses
available with optional open fuse indication. Time-
delay – 10 seconds (minimum) at 500% of rated
current.
Specifications:
Ratings
• Volts
• 600Vac
• 300Vdc*
• Amps 70-600A
• IR
• 300kA Vac RMS Sym.
• 100kA Vdc
* Indicating versions not Vdc rated.
Agency information
• UL® Listed, Guide JDDZ, File E4273
• CSA® Certified, Class 1422-02, File 53787,
Class J per CSA C22.2 No. 248.8
• CE
• RoHS compliant
Available with
easy
ID™
open fuse indication
Catalog numbers (amps) - non-indicating fuses*
LPJ-70SP LPJ-125SP LPJ-250SP LPJ-500SP
LPJ-80SP LPJ-150SP LPJ-300SP LPJ-600SP
LPJ-90SP LPJ-175SP LPJ-350SP
LPJ-100SP LPJ-200SP LPJ-400SP
LPJ-110SP LPJ-225SP LPJ-450SP
* Open fuse indication available on all part numbers by
inserting the suffix “I,” e.g., LPJ-90SPI. Requires 75Vac
minimum voltage. Indicating fuses are not Vdc rated.
Carton Quantity:
Amp rating Carton qty.
70–200 5
225–600 1
Dimensions - in:
Features:
• Industry’s only UL Listed and CSA Certified fuse
with a 300kA interrupting rating that allows for
simple, worry-free installation in virtually any
application.
• Fast short-circuit protection and dual-element,
time-delay performance provide ultimate
protection.
• Reduces existing fuse inventory by up to 33%
when upgrading to Low-Peak fuses.
• Consistent 2:1 ampacity ratios for all Low-Peak
fuses make selective coordination easy.
• Long time-delay minimizes needless fuse openings
due to temporary overloads and transient surges.
• Current-limitation protects downstream
components against damaging thermal and
magnetic effects of short-circuit currents.
• Dual-element fuses have lower resistance than
ordinary fuses so they run cooler.
• Can often be sized for back-up protection against
motor burnout from overload or single-phasing if
other overload protective devices fail.
• Proper sizing can provide “no damage” Type 2
coordinated protection for NEMA® and IEC® motor
controllers.
• Space-saving package for equipment downsizing.
6.0"
8.0"
3.75"
0.69" 2.13" 0.38"
0.53"
2" 2.5"
7.13"
5.25"
3.38"
0.53"
1.63"
1.88"
0.41"
*2"
0.25"
5.75"
4.38"
3.0"
0.38" 1.38"
1.13"
0.28"
0.19"
1.5"
4.63"
3.63"
2.63"
65 to 100A
0.28"
0.75" 1.13"
0.13"
1"
0.38"
110 to 200A
225 to 400A
450 to 600A