Timers - Multifunction G2ZMF11 24-240V GAMMA series 16 functions 16 time ranges Connection of remote potentiometer possible Zoom voltage 24 to 240V AC/DC 2 change-over contacts Width 22.5mm Industrial design Technical data 1. Functions 1 delayed contact (terminals 15-16-18) and 1 instantaneous contact (terminals 25-26-28) E11 ON delay R11 OFF delay with control contact Es11 ON delay with control contact Wu11 Single shot leading edge voltage controlled Ws11 Single shot leading edge with control contact Wa11 Single shot trailing edge with control contact Bi11 Flasher pulse first Bp11 Flasher pause first 5. Input circuit Supply voltage: 24 to 240V AC/DC Tolerance: 24 to 240V DC 24 to 240V AC Rated frequency: 24 to 240V AC 48 to 240V AC Rated consumption: Duration of operation: Reset time: Wave form for AC: Residual ripple for DC: Drop-out voltage: Overvoltage category: Rated surge voltage: 2 delayed contacts E20 ON delay R20 OFF delay with control contact Es20 ON delay with control contact Wu20 Single shot leading edge voltage controlled Ws20 Single shot leading edge with control contact Wa20 Single shot trailing edge with control contact Bi20 Flasher pulse first Bp20 Flasher pause first -20% to +25% -15% to +10% 48 to 400Hz 16 to 48Hz 4.5VA (1W) 100% 500ms Sinus 10% >15% of the supply voltage III (in accordance with IEC 60661-1) 4kV 6. Output circuit 2 potential free change-over contacts Rated voltage: 250V AC Switching capacity: 750VA (3A / 250V AC) If the distance between the devices is less than 5mm! 2. Time ranges Time range Adjustment range 1s 50ms 1s 3s 150ms 3s 10s 500ms 10s 30s 1500ms 30s 1min 3s 1min 3min 9s 3min 10min 30s 10min 30min 90s 30min 1h 3min 1h 3h 9min 3h 10h 30min 10h 30h 90min 30h 1d 72min 1d 3d 216min 3d 10d 12h 10d 30d 36h 30d 3. Indicators Green LED ON: Green LED flashes: Yellow LED ON/OFF: terminals A1-A2 (galvanically separated) Switching capacity: 1250VA (5A / 250V AC) If the distance between the devices is greater than 5mm! indication of supply voltage indication of time period indication of relay output 4. Mechanical design Self-extinguishing plastic housing, IP rating IP40 Mounted on DIN-Rail TS 35 according to EN 60715 Mounting position: any Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 Tightening torque: max. 1Nm Terminal capacity: 1 x 0.5 to 2.5mm with/without multicore cable end 1 x 4mm without multicore cable end 2 x 0.5 to 1.5mm with/without multicore cable end 2 x 2.5mm flexible without multicore cable end Fusing: Mechanical life: Electrical Life: Switching frequency: Overvoltage category: Rated surge voltage: 5A fast acting 20 x 106 operations 2 x 105 operations at 1000VA resistive load max. 60/min at 100VA resistive load max. 6/min at 1000VA resistive load (in accordance with IEC 60947-5-1) III (in accordance with IEC 60664-1) 4kV 7. Control contact Activation: Potential free: Loadable: Control voltage: Short circuit current: Line length: Control pulse length: bridge Y1-Y2 yes, basic isolation against input and output circuit no max. 5V max. 1mA max. 10m min. 50ms 8. Remote potentiometer (not included) The internal potentiometer is de-activated when a remote potentio-meter is connected !!! Connections: 1M potentiometer (type RONDO R2), terminals Z1-Y2 Line type: twisted pair Control voltage: max. 5V Short circuit current: max. 5A Line length: max. 5m www.tele-online.com G2ZMF11 24-240V Technical data 9. Accuracy Base accuracy: Frequency response: Adjustment accuracy: Repetition accuracy: Voltage influence: Temperature influence: ON delay with control contact (Es11) The supply voltage U must be constantly applied to the device (green LED illuminated). When the control contact Y1-Y2 is closed, the instantaneous contact switches into on-position and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the delayed contact switches into on-position (yellow LED illuminated). This status remains until the control contact is opened again. If the control contact is opened before the interval t has expired, the interval already expired is erased and is restarted with the next cycle. 1% (of maximum scale value) using 1M remote potentiometer 5% (of maximum scale value) using 1M remote potentiometer <0.5% or 5ms 0.01% / C 10. Ambient conditions Ambient temperature: -25 to +55C (in accordance with IEC 60068-1) -25 to +40C (in accordance with UL 508) Storage temperature: -25 to +70C Transport temperature: -25 to +70C Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) Pollution degree: 3 (in accordance with IEC 60664-1) Vibration resistance: 10 to 55Hz 0.35mm (in accordance with IEC 60068-2-6) Shock resistance: 15g 11ms (in accordance with IEC 60068-2-27) Functions The internal potentiometer is de-activated when a remote-potentio-meter is connected ! The function has to be set before connecting the relay to the supply voltage. ON delay (E11) When the supply voltage U is applied, the instantaneous contact switches into on-position and the set interval t begins (green LED flashes). After the interval t has expired (green LED illuminated) the delayed contact switches into on-position (yellow LED illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the expiry of the interval t, the interval already expired is erased and is restarted when the supply voltage is next applied. U LED U R15-16-18 R25-26-28 t