G2ZMF11 24-240V
www.tele-online.com
Timers - Multifunction
GAMMA series
16 functions
16 time ranges
Connection of remote potentiometer possible
Zoom voltage 24 to 240V AC/DC
2 change-over contacts
Width 22.5mm
Industrial design
Technical data
1. Functions
1 delayed contact (terminals 15-16-18) and
1 instantaneous contact (terminals 25-26-28)
E11 ON delay
R11 OFF delay with control contact
Es11 ON delay with control contact
Wu11 Single shot leading edge voltage controlled
Ws11 Single shot leading edge with control contact
Wa11 Single shot trailing edge with control contact
Bi11 Flasher pulse first
Bp11 Flasher pause first
2 delayed contacts
E20 ON delay
R20 OFF delay with control contact
Es20 ON delay with control contact
Wu20 Single shot leading edge voltage controlled
Ws20 Single shot leading edge with control contact
Wa20 Single shot trailing edge with control contact
Bi20 Flasher pulse first
Bp20 Flasher pause first
2. Time ranges
Time range Adjustment range
1s 50ms 1s
3s 150ms 3s
10s 500ms 10s
30s 1500ms 30s
1min 3s 1min
3min 9s 3min
10min 30s 10min
30min 90s 30min
1h 3min 1h
3h 9min 3h
10h 30min 10h
30h 90min 30h
1d 72min 1d
3d 216min 3d
10d 12h 10d
30d 36h 30d
3. Indicators
Green LED ON: indication of supply voltage
Green LED flashes: indication of time period
Yellow LED ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 60715
Mounting position: any Shockproof terminal connection according to
VBG 4 (PZ1 required), IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage:
24 to 240V AC/DC terminals A1-A2 (galvanically separated)
Tolerance:
24 to 240V DC -20% to +25%
24 to 240V AC -15% to +10%
Rated frequency:
24 to 240V AC 48 to 400Hz
48 to 240V AC 16 to 48Hz
Rated consumption: 4.5VA (1W)
Duration of operation: 100%
Reset time: 500ms
Wave form for AC: Sinus
Residual ripple for DC: 10%
Drop-out voltage: >15% of the supply voltage
Overvoltage category: III (in accordance with IEC 60661-1)
Rated surge voltage: 4kV
6. Output circuit
2 potential free change-over contacts
Rated voltage: 250V AC
Switching capacity: 750VA (3A / 250V AC)
If the distance between the devices is less than 5mm!
Switching capacity: 1250VA (5A / 250V AC)
If the distance between the devices is greater than 5mm!
Fusing: 5A fast acting
Mechanical life: 20 x 106 operations
Electrical Life: 2 x 105 operations at 1000VA resistive load
Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 4kV
7. Control contact
Activation: bridge Y1-Y2
Potential free: yes, basic isolation against input
and output circuit
Loadable: no
Control voltage: max. 5V
Short circuit current: max. 1mA
Line length: max. 10m
Control pulse length: min. 50ms
8. Remote potentiometer (not included)
The internal potentiometer is de-activated when a remote potentio-meter
is connected !!!
Connections: 1MΩpotentiometer(typeRONDOR2),
terminals Z1-Y2
Line type: twisted pair
Control voltage: max. 5V
Shortcircuitcurrent: max.5μA
Line length: max. 5m
G2ZMF11 24-240V
www.tele-online.com
ON delay with control contact (Es11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the
instantaneous contact switches into on-position and the set interval t
begins (green LED flashes). After the interval t has expired (green LED
illuminated) the delayed contact switches into on-position (yellow LED
illuminated). This status remains until the control contact is opened
again.
If the control contact is opened before the interval t has expired, the
interval already expired is erased and is restarted with the next cycle.
U
LED U
R15-16-18
R25-26-28
t
Y1-Y2
<t
Single shot leading edge voltage controlled (Wu11)
When the supply voltage U is applied, both contacts switch into
on-position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated) the
delayed contact switches into off-position (yellow LED not illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the interval t has expired, the both contacts
switch into off-position. The interval already expired is erased and is
restarted when the supply voltage is next applied.
U
LED U
R15-16-18
R25-26-28
t<t
Single shot leading edge with control contact (Ws11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, both
contacts switch into on-position (yellow LED illuminated) and the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the delayed contact switches into off-position
(yellow LED not illuminated). The instantaneous contact remains in
on-position, until the control contact is opened again. During the interval,
the control contact (and the instantaneous contact) can be operated any
number of times. A further cycle can only be started when the cycle run
has been completed.
U
LED U
R15-16-18
R25-26-28
tt
Y1-Y2
Technical data
9. Accuracy
Base accuracy: ±1% (of maximum scale value)
using1MΩremotepotentiometer
Frequency response: -
Adjustmentaccuracy: ≤5%(ofmaximumscalevalue)
using1MΩremotepotentiometer
Repetition accuracy: <0.5% or ±5ms
Voltageinuence: -
Temperatureinuence: ≤0.01%/°C
10. Ambient conditions
Ambienttemperature: -25to+55°C
(in accordance with IEC 60068-1)
-25to+40°C(inaccordancewithUL508)
Storagetemperature: -25to+70°C
Transporttemperature: -25to+70°C
Relative humidity: 15% to 85%
(in accordance with IEC 60721-3-3 class 3K3)
Pollution degree: 3 (in accordance with IEC 60664-1)
Vibration resistance: 10 to 55Hz 0.35mm
(in accordance with IEC 60068-2-6)
Shock resistance:
15g 11ms (in accordance with IEC 60068-2-27)
Functions
The internal potentiometer is de-activated when a remote-potentio-meter
is connected ! The function has to be set before connecting the relay to
the supply voltage.
ON delay (E11)
When the supply voltage U is applied, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired (green LED illuminated) the
delayed contact switches into on-position (yellow LED illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the expiry of the interval t, the interval
already expired is erased and is restarted when the supply voltage is
next applied.
U
LED U
R15-16-18
R25-26-28
t<t
OFF delay with control contact (R11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, both
contacts switch into on-position (yellow LED illuminated). If the control
contact is opened, the instantaneous contact switches into off-position
and the set interval t begins (green LED flashes). After the interval t
has expired (green LED illuminated) the delayed contact switches into
off-position (yellow LED not illuminated). If the control contact is closed
again before the interval t has expired, the interval already expired is
erased and is restarted with the next cycle.
U
LED U
R15-16-18
R25-26-28
t
Y1-Y2
<t
G2ZMF11 24-240V
www.tele-online.com
OFF delay with control contact (R20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the output
relay R switches into on-position (yellow LED illuminated). If the control
contact is opened, the set interval t begins (green LED flashes). After the
interval t has expired (green LED illuminated) the output relay switches
into off-position (yellow LED not illuminated). If the control contact
is closed again before the interval t has expired, the interval already
expired is erased and is restarted with the next cycle.
U
LED U
R15-16-18
R25-26-28
t<t
Y1-Y2
ON delay with control contact (Es20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the output relay R switches into on-position
(yellow LED illuminated). This status remains until the control contact is
opened again. If the control contact is opened before the interval t has
expired, the interval already expired is erased and is restarted with the
next cycle.
U
LED U
R15-16-18
R25-26-28
t
Y1-Y2
<t
Single shot leading edge voltage controlled (Wu20)
When the supply voltage U is applied, the output relay R switches into
on-position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay switches into off-position (yellow LED not illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the interval t has expired, the output relay
switches into off-position. The interval already expired is erased and is
restarted when the supply voltage is next applied.
U
LED U
R15-16-18
R25-26-28
t<t
Single shot leading edge with control contact (Ws20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the output
relay R switches into on-position (yellow LED illuminated) and the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the output relay switches into off-position
(yellow LED not illuminated). During the interval, the control contact can
be operated any number of times. A further cycle can only be started
when the cycle run has been completed.
U
LED U
R15-16-18
R25-26-28
tt
Y1-Y2
Functions
Single shot trailing edge with control contact (Wa11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed the
instantaneous contact switches into on-position. When the control
contact is opened, the instantaneous contact switches into off-position,
the delayed contact switches into on-position (yellow LED illuminated)
and the set interval t begins (green LED flashes). After the interval t
has expired (green LED illuminated), the delayed contact switches into
off-position (yellow LED not illuminated). During the interval, the control
contact (and the instantaneous contact) can be operated any number of
times.
A further cycle can only be started when the cycle run has been
completed.
U
LED U
R15-16-18
R25-26-28
tt
Y1-Y2
Flasher pulse first (Bi11)
When the supply voltage U is applied, the instantaneous contact and
the delayed contact switch into on-position (yellow LED illuminated)
and the set interval t begins (green LED flashes). After the interval t has
expired, the delayed contact switches into off-position (yellow LED not
illuminated) and the set interval t begins again. The delayed contact is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
U
LED U
R15-16-18
R25-26-28
t t t t t
Flasher pause first (Bp11)
When the supply voltage U is applied, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired, the delayed contact switches
into on-position (yellow LED illuminated) and the set interval t begins
again. After the interval t has expired, the delayed contact switches
into off-position (yellow LED not illuminated). The delayed contact is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
U
LED U
R15-16-18
R25-26-28
t t t t
ON delay (E20)
When the supply voltage U is applied, the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay R switches into on-position (yellow LED illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the expiry of the interval t, the interval
already expired is erased and is restarted when the supply voltage is
next applied.
U
LED U
R15-16-18
R25-26-28
t<t
G2ZMF11 24-240V
www.tele-online.com
RELEASE 2009/07
Subject to alterations and errors
Dimensions
Connections
15
16 18
25
26 28
A1
A2
Y1
Y2Z1
15
16 18
25 26 28
R2
1
2
3
S
Functions
Single shot trailing edge with control contact (Wa20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). Closing the control contact Y1-Y2 has no influence on
the condition of the output relay R. When the control contact is opened,
the output relay switches into on-position (yellow LED illuminated) and
the set interval t begins (green LED flashes). After the interval t has
expired (green LED illuminated), the output relay switches into off-
position (yellow LED not illuminated). During the interval, the control
contact can be operated any number of times. A further cycle can only
be started when the cycle run has been completed.
U
LED U
R15-16-18
R25-26-28
tt
Y1-Y2
Flasher pulse first (Bi20)
When the supply voltage U is applied, the output relay R switches into
on-position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired, the output relay switches
into off-position (yellow LED not illuminated) and the set interval t begins
again. The output relay is triggered at a ratio of 1:1 until the supply
voltage is interrupted.
U
LED U
R15-16-18
R25-26-28
t t t t t
Flasher pause first (Bp20)
When the supply voltage U is applied, the set interval t begins (green
LED flashes). After the interval t has expired, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
again. After the interval t has expired, the output relay switches into off-
position (yellow LED not illuminated). The output relay is triggered at a
ratio of 1:1 until the supply voltage is interrupted.
U
LED U
R15-16-18
R25-26-28
t t t t t