Magnum
IEC Low Voltage Air Circuit Breakers
Product Focus
For more information visit: www.cutler-hammer.eaton.com
PG01301002E
For more information visit: www.cutler-hammer.eaton.com
1Introduction
May 2003
PG01301002E
Introduction
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
One Family. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Higher Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Drawout Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Functions and Characteristics
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Characteristics Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Design and Testing Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Nameplate Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation and Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Circuit Breaker Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Trip Units and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fixed Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Drawout Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Phasing on Double-wide Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . 39
Accessory Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Breaker Lock OFF Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Application and Installation Information
Ambient Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Bus Bar Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Altitude Rating Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Watts Loss Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Electrical Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Ordering Information
Factory Configured Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Factory Configured Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Field Option Kits for Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Field Option Kits for Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . 63
Miscellaneous Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engineering Data Reference Chart. . . . . . . . . . . . . . . . . . . . . . . . . . 68
Trip Unit Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Connection Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
For more information visit: www.cutler-hammer.eaton.com
3Overview
May 2003
PG01301002E
Cutler-Hammer Low Voltage Air
Circuit Breakers have set the industry
standard for over three decades.
When reliability and customer
service are paramount, Cutler-
Hammer is the clear choice for IEC
applications
There is a new generation of Cutler-
Hammer Air Circuit Breakers that are
smaller with higher performance
and more versatility.
Magnum
Magnum Low Voltage Air Circuit
Breakers are designed for ultimate
application flexibility, with the
needs of both the power distribution
equipment user and the low voltage
panel assembler in mind.
For maximum safety, a modern,
through-the-door design permits
access to the breaker levering system,
trip unit, controls, and indicators with
the door closed.
High withstand and interrupting
ratings provide for maximum selec-
tivity and system coordination to
meet the needs of the high available
fault currents on today’s electrical
power distribution systems.
Field installable accessories
minimize inventory and permit fully
certified field installation of current
sensors, rating plugs, trip units and
accessories.
A compact and modular family of
breaker frame sizes makes the
design of compact, economical and
versatile enclosures a reality.
Magnum
The New Standard in Low Voltage Air Circuit Breakers
For more information visit: www.cutler-hammer.eaton.com
Magnum circuit breakers are avail-
able in a family of three physical
frame sizes, with the same basic
height and depth, differing only in
width.
The MWN narrow frame is the
highest performing power circuit
breaker of its size and rating class.
Continuous current ratings are
available from 800 to 2000 amperes.
Withstand and interrupting ratings
are available from 40 to 65 kA at
690Vac. The MWN compact size
allows for application in compact
enclosures of many types.
The MWI standard frame is ideally
suited for the construction of vertically
stacked modular IEC Switchgear and
Switchboards. Continuous current
ratings are available from 800 to
3200 amperes in the same frame
with uniform 125 mm pole center
spacing. Withstand ratings are
available to 85 kA at 690 Vac and
interrupting ratings to 100 kA at 440
Vac for improved system coordination
and service continuity.
The MWI double-wide frame is
ideal for application as main and
tie breakers in high capacity power
distribution systems. Continuous
current ratings are available in 4000,
5000, and 6300 amperes. Withstand
and interrupting ratings are available
to 100 kA at 690Vac for maximum
system coordination with down
stream devices.
4 One Family
PG01301002E
May 2003
Three Frame Sizes in One Family
For more information visit: www.cutler-hammer.eaton.com
5Higher Performance
May 2003
PG01301002E
Magnum circuit breakers have the
highest levels of performance
.
Higher interrupting capacity
allows Magnum to be applied on
newer power distribution systems
with higher available fault currents.
Higher short time (withstand)
current ratings along with selective
(LS) Digitrip RMS trip units results in
total selectivity between main, feed-
er, and branch circuit breakers.
Highest Levels of Performance
Interrupting
up to
65 kA
Interrupting
up to
100 kA
Interrupting
up to
100 kA
Short Time
up to
65 kA
Short Time
up to
85 kA
Short Time
up to
100 kA
MWN
Narrow
MWI
Standard
MWI
Double-wide
Icu at 690Vac
40 kA
50 kA
65 kA
65 kA
85 kA
100 kA
85 kA
100 kA
Performance Family
Magnum MWN
Narrow Frame
800 - 2000 A.
Magnum MWI
Standard Frame
800 - 3200 A.
Magnum MWI
Double-wide Frame
4000 - 6300 A.
Continuous Current (A)
800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Note: Icu is 100kA at 440 Vac and 85 kA at 690 Vac.
For more information visit: www.cutler-hammer.eaton.com
The MWN narrow frame drawout
circuit breaker is available in a com-
pact cassette with horizontal pri-
mary stabs and terminals, making it
ideal for single-high, compact enclo-
sures. Optional vertical adapter kits
are available for applications where
bus bar termination in the vertical
plane or multiple stacking of break-
ers is preferred.
The MWI standard frame mates to
a standard size cassette with horizon-
tal primary stabs and terminals.
Uniform 125 mm pole center spacing
makes the cassette ideal for applica-
tions that require stacking of multiple
circuit breakers in a single enclosure
structure. Optional vertical adapter
kits are available where bus bar ter-
mination in the vertical plane is pre-
ferred.
The MWI double-wide frame cir-
cuit breaker uses a double-wide cas-
sette designed to accommodate a
maximum rating of 6300A.
Horizontal primary stabs and termi-
nals are provided as standard.
Optional vertical adapter kits are
available where bus bar termination
in the vertical plane is preferred.
ingle enclosure structure as well.
6 Drawout Cassettes
PG01301002E
May 2003
Simplified Construction with
Three Drawout Cassettes
MWN Narrow Frame Cassette
MWI Standard Frame Cassette
Front View (with circuit breaker) Rear View
Rear View
Front View
For more information visit: www.cutler-hammer.eaton.com
7Overview
May 2003
PG01301002E
Introduction
The Magnum Low Voltage Air Circuit
Breaker affords customers the oppor-
tunity to meet the increasingly complex
requirements of modern distribution
systems. It is designed and tested for
use in low voltage power distribution
assemblies applied at nominal volt-
ages of 220/415, 440, and 500/690 volts
ac. Magnum is available in drawout
and fixed circuit breaker mounting
configurations. High interrupting
ratings up to 100kA without fuses and
continuous current ratings from 800
through 6300 amperes are covered by
three different frame sizes.
Magnum circuit breakers are witnessed
and certified with a KENMA-KEUR
Mark, and are built and tested in an
ISO 9000 certified facility. The circuit
breakers meet or exceed all applicable
EN and IEC standards including:
IEC 947-2 Category B
BS/EN 60947-2
Suitable in IEC 947-1/439-1 Low
Voltage Switchgear
Controls and indicators are function-
ally grouped on the circuit breaker’s
front cover. The through-the-door
drawout design permits easy and
safe access to the front cover controls,
as well as the trip unit and racking
device.
Intelligence Systems
Digitrip microprocessor-based
true rms sensing trip units
Protection and coordination
Energy monitoring and power
quality
Communications
Protective relay features
Integral testing
Hand held test kit
Special Application Circuit Breakers
Non-automatic circuit breakers - a
non-automatic circuit breaker does
not include a trip unit, sensors or
overcurrent release.
1100 Vac air circuit breakers.
Contact Cutler-Hammer for other
special applications.
Functional Techniques
Patented “Heal -Toe” contact
structure
Improved contact material
“C” Loop current path
Braided current path connections
Sealed, removable arc chambers
Reliability, Maintenance and Safety
Front accessible and dedicated
secondary wiring
Finger proof secondary contacts
Drawout rail construction
Front mounted, plug-in accessories
Accessory viewing windows
Proven operating mechanism
Fewer individual parts
Mechanical main contact wear
indicator
One piece removable arc chutes
and covers
Insulating and isolating arc
chambers
Replaceable current path structures,
current sensors and trip units
Magnum circuit breakers utilize one
of a family of microprocessor-based
Digitrip electronic, rms sensing and
programmable trip units to provide
system selectivity, advanced coordi-
nation and communications.
Functional and Flexible
Rigid frame of high strength
engineered thermoset composite
resins
Compact and lightweight
Rugged, maintainable
construction
Three frame sizes
Four position drawout or fixed
mounting configurations
Through-the-door drawout
construction
Common height, depth and door
cutout
Spring stored energy mechanism
Electrical or manual operation
(field convertible)
Field installable accessories.
Performance Plus
Designed and tested to IEC
Standards
Ten continuous current frame sizes
(800 through 6300A without fans)
High interrupting ratings
High withstand ratings
Rated for 100% continuous
operation in enclosure
3 cycle closing
For more information visit: www.cutler-hammer.eaton.com
8 Characteristics Table
PG01301002E
May 2003
Standard Frame (MWI)
800
1000
1250
1600
2000
2500
3200
100/85
85/65
Magnum Frame
Circuit Breaker Characteristics ① ②
Continuous Current Rating (Amps at 40°C)
Interrupt Ratings at 690Vac Icu/Ics (kA rms)
Withstand Rating Icw 1-sec/3-sec (kA rms)
Maximum Break Time (msec)
Maximum Closing Time (msec)
Circuit Breaker Dimensions (mm)
Height
Depth
Width (3-pole)
Width (4-pole)
Height
Depth
Width (3-pole)
Width (4-pole)
Circuit Breaker Weight (kg) 3-pole
4-pole
3-pole
4-pole
3-pole
4-pole
Non-Auto Switch Characteristics
Maximum Interrupt Ratings at 690Vac Icu/Ics
(kA rms)
Withstand Ratings Icw 1-sec/3-sec (kA rms)
Continuous Current Range (Amps)
Close and Latch Current (kA Peak)
Maximum Continuous Current Range (Amps)
Close and Latch Current (kA Peak)
Narrow Frame (MWN)
Circuit breakers equipped with integral trip units have a making current release set to trip instantaneously at 25 x In peak current to prevent
closing on a fault current exceeding that magnitude.
Magnum ACBs carry an IT rating at 440 Vac per EN60947-2 Annex H. Contact Cutler-Hammer for 690 Vac IT applications.
The Icw 1-sec/3-sec rating is 50/30 kA for 2000 amp MWN 50kA breaker.
Standard frame circuit breakers rated 100kA are equipped with a high instantaneous trip set to protect above 85kA rms. Icu is 100kA and Ics
is 85kA at 440 Vac. Icu and Ics are 85kA at 690 Vac.
The approximate weights and dimensions shown are based on horizontal terminals.
Close and latch ratings are applicable only to non-automatic switches. Non-automatic switches should be applied with a suitable external
overcurrent device with instantaneous trip to protect above the published close and latch rating.
The maximum available instantaneous interrupting rating for the standard frame non-automatic switch is 85kA.
MWN
Narrow
Frame
MWI
Standard
Frame
Magnum Characteristics, Dimensions and Weights (continued on next page)
800
1000
1250
40/40
40/–
40/40
40/–
to 1250
43
800
1000
1250
1600
2000
50/50
50/–
30
50
425.7
371.9
317.7
413
524.3
474.2
336
431.3
43
54
48
62
28
32
50/50
50/–
to 2000
55
800
1000
1250
1600
2000
65/65
65/40
65/65
65/40
to 2000
69
Fixed
Drawout
Fixed
Drawout
Cassette
800
1000
1250
1600
65/65
65/–
65/65
65/–
to 1600
55
2000
2500
3200
65/65
65/50
65/65
65/50
2000
69
2500 & 3200
110
800
1000
1250
1600
2000
2500
3200
85/85
85/65
85/85
85/65
to 2000
69
2500 & 3200
110
30
50
425.7
371.9
410.2
537.2
524.3
474.2
431.8
558.8
58 to 68
72 to 86
70 to 86
88 to 112
53 to 56
55 to 68
For more information visit: www.cutler-hammer.eaton.com
9Characteristics Table
May 2003
PG01301002E
MWI
Double-wide
Frame
(continued from previous page)
Magnum Frame
Circuit Breaker Characteristics ① ②
Continuous Current Rating Amps at 40°C
Interrupt Ratings at 690Vac Icu/Ics (kA rms)
Withstand Rating Icw 1-sec/3-sec (kA rms)
Maximum Break Time (msec)
Maximum Closing Time (msec)
Circuit Breaker Dimensions (mm)
Height
Depth
Width (3-pole)
Width (4-pole)
Height
Depth
Width (3-pole)
Width (4-pole)
Circuit Breaker Weight (kg) 3-pole
4-pole
3-pole
4-pole
3-pole
4-pole
Non-Auto Switch Characteristics
Maximum Interrupt Ratings at 690Vac Icu/Ics
(kA rms)
Withstand Ratings Icw 1-sec/3-sec (kA rms)
Continuous Current Range (Amps)
Close and Latch Current (kA Peak)
Maximum Continuous Current Range (Amps)
Close and Latch Current (kA Peak)
Double-wide Frame MWI
4000
65/65
65/–
107.5
144.7
138.8
166
90.3
113.4
65/65
65/–
to 4000
138
4000
5000
6300
85/85
85/–
40
70
425.7
371.9
886.5
1120
524.3
474.2
909
1036
125.2
163.3
157.4
200
96.2
120.7
85/85
85/–
to 4000
138
5000 & 6000
217
4000
5000
6300
100/100
100/–
100/100
100/–
to 4000
138
5000 & 6000
217
Fixed
Drawout
Fixed
Drawout
Cassette
For more information visit: www.cutler-hammer.eaton.com
The Magnum air circuit breaker was
designed and tested to meet the
requirements of the world market.
It is a 100% rated device, designed
to carry 100% of its nameplate current
rating in an enclosure without derating
at a 40°C ambient.
Relative to the pollution degree,
Magnum circuit breakers conform to
the requirements of Clause 6 of IEC
947-2. This states that unless other-
wise stated, the circuit breaker is
intended for installation under envi-
ronmental conditions of Pollution
Degree 3.
Circuit Breakers are built and tested
to applicable standards, including:
International EN 60947-2
Category B
Circuit Breakers are also suitable for
use in:
IEC 947-1/439-1 Low Voltage
Switchgear
10 Design and Testing Standards
PG01301002E
May 2003
Magnum...
...The Only KEMA-KEUR Certified Air Circuit Breaker
KEMA-KEUR Certification
Product Test Certification–All 4 EN 60947-2 Test Sequences
Manufacturing Location Certification
Ongoing compliance ensured with spot facility and field product checks
ISO 9001 ISO 9002
Magnum Air Circuit
Breakers are designed to
ISO 9001
Magnum Air Circuit
Breakers are manufactured
in an ISO 9002 Facility
KEMA–Foremost
independent third
party certification
body in the world
KEMA-KEUR Mark
Indicates certifica-
tion to the highest
and most stringent
KEMA Standards
For more information visit: www.cutler-hammer.eaton.com
11Nameplate Identification
May 2003
PG01301002E
Nameplate Identification
Magnum low voltage power circuit
breakers must be applied within their
nameplate ratings. Nameplates are
prominently displayed on the front of
the circuit breaker, and provide
important information relative to that
specific circuit breaker.
A Magnum circuit breaker is easily
identified by its specific designation.
A
B
Low voltage power circuit breaker family name
Breaker family designation number
CBreaker frame size in amperes
DInterrupting capacity rating
EFactory Equipped Accessories
MWI C32
Circuit Breaker
Type
MWI - Standard and
Double Wide Frames
MWN - Narrow Frame
Interrupting
Capacity
4 - 40,000
5 - 50,000
6 - 65,000
8 - 85,000
C - 100,000
E - 150,000
Frame
Size
08 - 800 Amps
10 - 1000 Amps
12 - 1250 Amps
16 - 1600 Amps
20 - 2000 Amps
25 - 2500 Amps
32 - 3200 Amps
4N - 4000 Amps
5N - 5000 Amps
6N - 6300 Amps
A
B
C
D
E
Magnum Designation Example
Typical Magnum DS Nameplate
Reserved for future breaker
For more information visit: www.cutler-hammer.eaton.com
Sized to Simplify
Magnum low voltage power circuit
breakers are designed for simplified
installation and use.
Three physical frame sizes through
6300 amperes
- More circuit breakers per
square centimeters
- Increased ratings in less space
- Installation economy of
time,material and space
- Closed door circuit breaker
levering
- DISCONNECT, TEST and
CONNECT with door closed
Common height, depth and door
cutout
- Installation ease and economy
Zero clearance mounting with
drawout cassette
- Vertical stacking economy
Four position drawout and fixed
mountings
- Customer flexibility
Fixed mounting with horizontal
or vertical bus bar connections
- Accommodate different bus
configurations
Through-the-door drawout
- Clear access to trip unit, controls
and indicators
12 Installation and Use
PG01301002E
May 2003
Common Height, Depth and Cutout (3-Pole Illustration)
Dotted Line
Represents
CommonCutout
391mm
(14.7”)
417mm”
(16.4”)
894mm”
(34.2”)
Double
4000-6300A
414mm”
(16.3”)
Standard
800-3200A
318mm”
(12.5”)
Narrow
800-1600A
Through-The-Door Drawout (Connect Position Shown)
Circuit
Breaker
Side View
Rear of
Compartment
Primary
Connections
Made
Secondary
Connection Made
Compartment
Front Door
For more information visit: www.cutler-hammer.eaton.com
13Circuit Breaker Features
May 2003
PG01301002E
Summary
Rigid Frame Housing
Magnum circuit breakers use a rigid
frame housing construction of engi-
neered thermoset composite resins.
This material is strong and lightweight
having a strength to weight ratio
twice that of steel. In addition to
high strength structural properties,
this material has excellent dielectric
characteristics and resists arc tracking.
The 3-piece construction provides
support while isolating and insulating
power conductors:
A 2-piece case encloses current
paths and arc chambers. The chambers
act to channel arc gases up and out
during interruption.
The operating mechanism and
accessories sit on the front of the
indicating functions and guiding
operations. Field installable accessory
items can be identified by name and
rating through viewing windows.
An optional padlockable cover limits
access to the “ON” and “OFF” push-
buttons. Complete access to the
“ON” pushbutton can be prevented
with an optional prevent close cover.
case and are covered by an insulating
front cover. Only the cover needs to
be removed to access the mechanism
or add accessories.
The overall strength and rigidity of
the design also contributes to higher
performance capabilities:
Higher Withstand
Higher Interrupting
The Magnum rigid frame housing
design allows for precise construction,
eliminating the need for adjustments.
The significantly reduced frame
deflection during operation along
with stiff component mounting
results in a longer life operating
mechanism.
Operating Panel
The Magnum front cover (next page)
contains a convenient operating
panel with clear words and symbols
Magnum Front Accessible Operating Mechanism and Accessories
Magnum Rigid Frame Construction
Front Cover Case
Secondary Wiring Points
Field Installable Accessories
(3 maximum)
Trip Unit
Electric Charging Motor
Manual Charge Handle
Operations Counter (optional)
Padlockable Levering Device
Access Door
Breaker Position Indicator
7
2
4
3
5
6
8
1
1
2
3
4
5
6
78
For more information visit: www.cutler-hammer.eaton.com
14 Circuit Breaker Features
PG01301002E
May 2003
10
Magnum Drawout Circuit Breaker Front Cover
CONNECT
TEST
DISCONNECT
CONNECT
TEST
DISCONNECT
(Red)
(Green)
(Yellow)
(White)
(Green)
(Red)
5
6
8
7
Red = Connect
Yellow = Test
Green = Disconnect
12
Optional Trip Flag (Pop Out Indicator)
Three Accessory Windows
Trip Unit
Rating Plug
Contact Status (Open-Close)
Spring Status (Charged-Discharged)
2
1
4
3
5
6
Manual “OFF” Button (Push)
Manual “ON” Button (Push)
Manual Charge Handle
Optional Operation Counter
Padlockable Levering Device Access
Door for Drawout Breaker
8
7Colour Coded-Breaker
Position Indicator
Nameplate
Trip Unit Test Port
Trip Unit Cover with Two
Mounting Screws (Mounting
Screws will Accept Customer
Supplied Lead Security Meter
Seals
10
9
11
12
13
14
15
12
3
4
9
5
7
12
3
4
9
10
11
13
14
15
OPEN
PUSH OFF
DISCHARGED
PUSH ON
CLOSED
CHARGED
For more information visit: www.cutler-hammer.eaton.com
15Circuit Breaker Features
May 2003
PG01301002E
Main Contact System
Single Contact Finger
The performance characteristics of
the Magnum air circuit breaker are
primarily attributed to the contact
design and its movement. A single
contact finger is the focal point of the
moving contact. This single contact
performs both the main and arcing
contact functions on different parts
of the same finger.
A complete movable contact assembly
is merely a combination of a number
of single contact fingers. The exact
number of contact fingers required
depends upon the frame size and
interrupting rating of the circuit
breaker.
heel to toe and toe to heel. When the
circuit breaker is closed, the “Heel”
(main contact portion) is in contact
with the stationary contact and carrying
current. At the same time, the “Toe”
(arcing contact portion) is separated
from the stationary arcing contact.
A compact “C Loop” current path per-
mits electromagnetic forces, primarily
produced as a result of a fault current,
to supplement the closing contact
forces provided by the operating
mechanism. This helps to accomplish
two important things:
Operating mechanism does not
have to be as large or heavy
Higher short time ratings (withstand)
are achievable
The braided connectors (flexible shunts)
used to attach each contact finger serve
several important purposes:
Eliminate bolted joints reducing
hot spots
Reduce required mounting space
for primary contacts
Allow contact finger motion for
“Heel - Toe” rocking
Heel-Toe Action
The “Heel-Toe” movement of the
contact fingers is a critical factor in
the efficiency of the Magnum main
contact system. The main contact
portion can be viewed as the “Heel”
and the arcing portion the “Toe.” Its
movement is similar to the rocking of
a foot forward and backward from
Graphic of Single Magnum Contact Finger Magnum Standard Frame (12 Finger) Contact Assembly
Dual
Flexible
Connections
Moving
MainContact
Conductive Pad
(Heel)
Moving
Arcing
Contact
Area
(Toe)
Pivot
Point
Contact
Finger
“Heel”
(Main Contact)
“Toe”
(Arcing Contact)
For more information visit: www.cutler-hammer.eaton.com
Integral Arc Runner
The integral arc runner serves a dual
purpose:
Functions as circuit breaker’ fixed
arcing contact
Functions as a critical part of the
arc chute
contact fingers to a narrow, side-to-
side ledge inside the arc chamber.
When the contacts are in good condi-
tion, the narrow ledge is covered by
the back end of the contacts and not
visible. When the narrow ledge
becomes visible with the primary
contacts closed, contact replacement
is indicated.
Contact Wear Indicator
A contact wear indicator provided for
each primary contact structure permits
their condition to be determined.
This is accomplished by viewing
the contacts while in the closed
position only.
The contact wear indicator is the
relative position of the individual
16 Circuit Breaker Features
PG01301002E
May 2003
Contact Wear Indication
Magnum Arc Running System (Crosssectional View) Integral Arc Runner Viewed from Top of Circuit Breaker
Integral
Arc Runner
Contact Wear Indicator - Contacts
Closed and in Good Condition
Contact Wear
Inspection Area
(Ledge Now Becoming
Visible Under
Contacts)
Contact Wear Indicator - Contacts
Closed and Wear is Indicated
Contact Wear
Inspection Area
Contact Wear
Inspection Area
(Ledge Not Visible
Under Contacts)
Side-to-Side
Ledge Side-to-Side
Ledge
,,,
,,,
,,,
yyy
yyy
yyy
,y
,,,,
,,,,
,,,,
yyyy
yyyy
yyyy
,,
,,
yy
yy
,
,
,
y
y
y
,,yy
,y
xxxxxxxx
xxxxxxxx
x
xx
x
Integral
Arc Runner
Top Arc
Plate
Current
Flow
Current
Flow
For more information visit: www.cutler-hammer.eaton.com
17Circuit Breaker Features
May 2003
PG01301002E
Arc Chambers
Arc chambers, one per pole, are used
to insulate and isolate each pole from
one another, from the rest of the circuit
breaker, and from operating personnel.
Arc Chute
Enclosed within each arc chamber is
an arc chute which mounts over each
set of primary contacts. Alternating
V-shaped arc chute plates effectively
attract the arc and interrupt it. Each
arc chute has a baffled cover to
assist with the speed and efficiency
of the interruption.
Partial Top Rear View Breaker (One Arc Chute Removed) Arc Chute (Bottom View)
Top Arc Plate
for
Arcing Contact
Baffled Cover
Arc Chamber
Alternating
“V” Shaped
Plates
For more information visit: www.cutler-hammer.eaton.com
Manual Operation
On manually operated circuit breakers,
the closing spring is charged manually.
This is accomplished through the use
of the front mounted spring-charge
handle. It takes from 5 to 7 downward
strokes on the handle to complete the
charging process.
Standard manually operated circuit
breakers are closed and opened by
hand using the front mounted
Manual “ON” and Manual “OFF”
buttons respectively. Access to these
buttons can be limited by the use of
an optional, padlockable cover.
Complete access to the “ON” button
can be prevented with an optional
prevent close cover. Spring and
primary contact status indicator
windows are located just above the
pushbuttons.
Optional electrically operated devices
are available to automatically close
or trip open manually operated circuit
breakers, and are field installable.
An optional motor operator is used
to charge the closing spring automat-
ically. It can be field installed in a
manually operated circuit breaker.
Manual circuit breakers are pre-wired
for this addition.
Electrical Operation
The closing spring is charged auto-
matically by the optional motor
operator. It can also be manually
charged.
Manual “ON” and Manual “OFF”
buttons are also provided as
described under manual operation.
Through the use of a mechanical
anti-pump feature, an open circuit
breaker only accepts one attempt to
reclose even if the close command
continues, preventing motor operator
burnout.
A standard circuit breaker with
electrical operation also has optional
electrically operated devices available
to automatically close or trip open
the circuit breaker.
18 Circuit Breaker Features
PG01301002E
May 2003
Magnum Circuit Breaker Being Manually Charged
Motor Operator Installed
Motor Operator
For more information visit: www.cutler-hammer.eaton.com
19Circuit Breaker Features
May 2003
PG01301002E
Breaker Secondary Connectors
(Black)
Magnum secondary connectors pro-
vide reliable low impedance connec-
tions for up to 60 terminal points of
breaker control wiring. The sec-
ondary connectors are black in color
and consist of 2 blocks, each with 30
terminal points. The terminals
receive plug-in type pin and socket
wire terminals. Terminal points have
dedicated locations to receive the
breaker accessory devices and to
facilitate standardized automated
testing of the control wiring and
accessories during breaker manufac-
turing. Labels are provided on the
blocks to assist the customer in ter-
minal point identification and use.
The dedicated secondary connectors
make it easy to add accessories (like
shunt trips, spring release devices,
etc.) to the breaker at the point of use
with field option kits. Wiring removal
from breaker secondary connector is
easily accomplished using an extrac-
tion tool (AMP part number 305183).
Labels Legend
OTS Overcurrent Trip Switch
UVR Undervoltage Release
ATR Automatic Trip Relay
(520M, 520MC and 1150
Trip Units Only)
INCOM PowerNet
Communications Network
A BUS (Future Use)
A/S Auxiliary Contacts
NEUTRAL Neutral Sensor Input
GF SGND Source Earth Input
ZONE Zone Interlocking
ST Shunt Trip
SR Spring Release
MOTOR Charging Motor
LCS Latch Check Switch
Secondary Connector Labels
Top View Secondary ConnectorsCharged
Mounted Secondary Terminal Blocks
Secondary Wiring Removal Tool
Secondary Terminals and Terminal Wires
Open
hinged
Covers
Closed Hinged
Covers with
Testing Holes
Secondary Terminal Blocks
(White)
White secondary terminal blocks can
be provided mounted at the top front
of the breaker for customer use. The
6-point terminal blocks have hinged
IP20 finger-proof covers and are
designed to terminate various cus-
tomer wire terminals including ring
type terminals. Up to 72 terminal
block points can be accommodated
for Standard and Double frame
breakers. Up to 48 terminal block
points can be accommodated for
Narrow Frame breakers.
Wire kits and terminal block kits are
available for use by the panel assem-
bler to custom configure the black
breaker secondary connectors to the
white terminal blocks. As an option,
factory pre-wired cassettes are avail-
able for drawout circuit breakers.
For more information visit: www.cutler-hammer.eaton.com
Digitrip RMS
Trip Unit Summary
Magnum circuit breakers can use any
one of a family of microprocessor-
based, true rms sensing Digitrip RMS
electronic trip units:
Digitrip RMS 220
Digitrip RMS 520i
Digitrip RMS 520Mi
Digitrip RMS 520MCi
Digitrip RMS 1150i
The trip units themselves are self
powered; no external power is
required to operate the portective
systems. Current signal levels and
the control power are derived from
integrally mounted torroidal wound
current sensors. The use of torroidal
wound sensors reduces magnetizing
currents, resulting in improved
metered value accuracy over a broad
range of sensor ratings.
Common Features
All trip units have a green light emit-
ting diode (LED), labeled
Status
,
which blinks approximately once
each second to indicate that the trip
unit is operating normally. This
same
Status
LED will blink at a faster
rate if the trip unit is in a pick-up or
overload condition.
Trip units are interchangeable in the
field, except for Model 520MC and
Model 1150. Contact Cutler-Hammer
for interchangeability details.
A functional local test of a major
portion of every trip unit’s electronic
circuitry and the circuit breaker’s
mechanical tripping action can be
verified through the trip unit’s test
receptacle. Every test receptacle is
supplied with a test receptacle cover.
This is accomplished using a Digitrip
Test Kit which provides a secondary
injection test. A small hand held
functional Test Kit can also be used
to check circuitry and mechanical
tripping functions. In addition, the
model 1150 trip unit has an integral
testing system.
Rating Plugs
All Magnum circuit breaker trip units
use a fixed type rating plug. Rating
plugs are available in ampere ratings
of 200 through 6300 amperes. The
current rating of the rating plug
must match the current rating of the
integrally mounted current sensors.
Therefore, the continuous current
rating of the circuit breaker cannot
be changed by only changing the
rating plug.
The rating plug performs a number
of functions:
It tells the trip unit what the rating
is of the current sensors. A label
on the rating plug clearly states
that the rating plug and current
sensors must have the same rating.
It determines the maximum instan-
taneous setting which is a function
of the current sensor rating.
Lifting the rating plug lid will expose
a small battery which supplies power
for the trip unit’s cause of trip LEDs.
If the rating plug is removed from
the trip unit, the circuit breaker will
open (trip) if it is carrying current.
The rating plug should always be
secured in position when the circuit
breaker is in use.
All trip unit models, except for model
220, have red LEDs on the face of the
trip unit to indicate the cause for an
automatic trip operation, for example
earth fault, overload or short circuit.
They flash red to make the indication.
A battery in the trip unit maintains
the trip indication until the
Reset/Battery Test button is pushed.
The battery is satisfactory if its LED
lights green when the Battery Check
button is pushed.
A clear, tamper-proof, plexiglass
cover sits on the front of the circuit
breaker over the trip unit. This cover
allows the settings to be viewed but
not changed, except by authorized
personnel. The cover is held in place
by two cover screws. Security is
insured by the insertion of a standard
meter seal through the holes in both
of the cover retention screws.
20 Trip Units and Communications
PG01301002E
May 2003
Magnum Hand Held Tester
Rating Plug Installed in Digitrip 1150
For more information visit: www.cutler-hammer.eaton.com
21Trip Units and Communications
May 2003
PG01301002E
Digitrip 220
The Digitrip 220 Trip Unit is
designed to provide basic overcurrent
protection with maximum economy.
The Model 220 is available on
Narrow and Standard Frame
Magnum Circuit Breakers up to 3200
amperes. Product features include:
LI Protection Option
Unit Status LED (Green)
Indicator
Microprocessor-Based True
RMS Sensing
Long Delay Pick-up Setting
fixed at In
Long Delay Time Setting fixed
at 10 seconds at 6xIn
Long Time (Thermal) Memory
Trip
Overtemperature Trip when
temperature exceeds 85°C
Instantaneous Pick-up
adjustable from 2x to 10x In and M1
Neutral Protection
Test Port with cover to receive
Hand Held Tester
Note:
The Digitrip 220+ is coming soon.
The Digitrip 220+will replace the
Digitrip 220 Trip Unit some time in
late 2003. The Digitrip 220+Trip Unit
will have the following features
when it is phased into production:
The Long Delay Pick-up
Setting will be changed to
adjustable from 0.4 to 1.0 Ir
The Long Delay Tiime Setting
will be changed to adjust-
able from 2 to 24 seconds at 6 x Ir
LED (Red) Trip Indicators will
be added for Long Delay and
Instantaneous Trip Functions
Battery Included to Power
Cause of Trip LEDs
Reset/Battery Test Pushbutton
Contact Cutler-Hammer for the future
availability of the Digitrip 220+Trip
Unit.
For more information visit: www.cutler-hammer.eaton.com
Digitrip 520 and 520i
The Digitrip 520 Trip Unit is a
versatile trip unit with added features
designed to provide increased flexi-
bility in overcurrent protection and
coordination. The Model 520 is
available on all Magnum Circuit
Breakers. Product features include:
LSI and LSIG Protection
Options with adjustable
Instantaneous Off Setting
Unit Status LED (Green)
Microprocessor-Based True
RMS Sensing
Long Delay Pick-up Setting
adjustable from 0.4 to 1.0 Ir
Long Delay Time Setting
adjustable from 2 to 24 seconds
at 6 x Ir
Long Time (Thermal) Memory
Trip
Overtemperature Trip when
temperature exceeds 85°C
Short Delay Pick-up setting
adjustable from 2 to 10 Irand M1
Short Delay Time Setting
adjustable flat response from 0.1
to 0.5 seconds and I2t Response at
0.1, 0.3 and 0.5 seconds
Adjustable Instantaneous Pick-
up Settings, Off, 2x to 10x Inand
M1
Earth Pick-up Setting adjustable
from .25 to 1.0 x In
Neutral Protection (Model LSI
Trip Unit)
Earth Time Setting adjustable
flat response from 0.1 to 0.5 seconds
and I2t Response at 0.1, 0.3 and 0.5
seconds
Zone Interlocking of Short
Time and Earth Fault Time
Delay Functions
Test Port with Cover to receive
Hand Held Tester
LED (Red) Trip Indicators for
Long Delay, Short Delay,
Instantaneous and Ground Fault
Trip Functions
Battery Included to Power
LEDs
Reset/Battery Test Pushbutton
22 Trip Units and Communications
PG01301002E
May 2003
For more information visit: www.cutler-hammer.eaton.com
23Trip Units and Communications
May 2003
PG01301002E
Digitrip 520M and 520Mi
The Digitrip 520M Trip Unit
includes all the features of the 520
Trip Unit with the following additions:
LSI,LSIG and LSIA Protection
Options with adjustable
Instantaneous Off Setting
4 Digit LCD Display
Step Pushbutton to Scroll
through the LCD Display Data:
PH1 Phase 1 (A) Current
PH2 Phase 2 (B) Current
PH3 Phase 3 (C) Current
PH4 Neutral Current
PH5 Earth Current
HI Highest Phase Current
OL Overload Condition
HELP Trip Unit Error
Magnitude of Trip Current
Optional Earth Alarm/Power
Supply Module:
Powers the trip unit’s 4
Digit LCD Display through the
breaker secondary contacts
with a customer supplied
voltage source:
24-48 Vdc
110 Vac
220 Vac
Provides a earth fault alarm
contact (when used with LSIA)
Provides a earth fault trip
contact (when used with LSIG)
Provides a High Load Alarm
contact (when used with LSI)
Alarm Contact rating (with
resistive load):
0.5 Amp at 220 Vac
1.0 Amp at 110 Vac
1.0 Amp at 24-48 Vdc
High Load Indicator LED (RED)
(LSI Trip Units)
Note: If an Earth Alarm/Power
Supply Module is not provided, the 4
Digit LCD Display will power up
when the 3 phase currents reach
approximately 20% of the sensor rat-
ing or 30% of a single phase current.
For more information visit: www.cutler-hammer.eaton.com
Digitrip 520MC and 520MCi
The Digitrip 520MC Trip Unit
includes all the features of the 520M
Trip Unit, but also includes ampere-
based communications capability.
The 520MC Trip Unit has the following
additions:
Communications Functions
and Data:
Transmit LED (Red) indicates
when trip unit is transmitting
INCOM signal
Device Settable INCOM
Address from 001 to 999 hexa-
decimal
Bkr Status (Open, Closed,
Tripped)
PH1 Phase 1 (A) Current
PH2 Phase 2 (B) Current
PH3 Phase 3 (C) Current
PH4 Neutral Current
PH5 Earth Current
LDPU Long Delay Pick-up
SDT Short Delay Trip
INST Instantaneous Trip
GNDT Earth Fault Trip
PLUG Plug Trip
MCR Making Current
Release
OTEMP Over Temperature
HL High Load (LSI only)
Earth Alarm/Power Supply
Module is Supplied as
Standard to power trip unit
communications functions
The 520MC is designed for applications
where communication capability is
specified with maximum economy.
The 520MC Trip Unit communicates
current-based information, but does
not have the voltage, power, harmonic
or remote control capability of the
Digitrip 1150 Trip Unit. The 520MC
is ideally suited for application on
feeder breakers and can be used in
tandem with mains and tie breakers
that are equipped with the full
capability of the 1150 Trip Unit.
Note: Digitrip 520MC requires
PowerNet Version 3.2 or higher if
PowerNet Software is used.
24 Trip Units and Communications
PG01301002E
May 2003
For more information visit: www.cutler-hammer.eaton.com
25Trip Units and Communications
May 2003
PG01301002E
Digitrip 520M/MC
Control Voltage Remote
Ground
Fault Trip
Ground
Fault Alarm
Ground Alarm / Power Supply Module
G-Alarm
K2-1
K2-3
K2-6
Output +
Output -
J3-1
J3-2
J3-3
J4-4
J4-3
J4-1
A-10
A-11
A14
A-15
G-ALM 1
G-ALM 2
ATR Volt.
ATR COM
J4-2
Contact Rating (resistive load)
AC 0.5A @ 230VAC
AC 1A @ 120VAC
DC 1A @ 48VDC
Verify input voltage rating before energizing circuit.
When used in conjunction with a T. U. Cat. 5MWLSIG,
5MLSIG, 5CWLSIG or 5CLSIG, will indicate GF trip.
When used in conjunction with T.U. Cat. 5MLSIA or
5CLSIA, will indicate GF alarm.
When used in conjunction with a Trip Unit having
LSI protection, will indicate High Load alarm.
120 VAC
230 VAC
24-48 VDC
7802C83G01
7802C83G02
7802C82G01
Style
Number
Available
Input Voltages 2
2
5
1
3
4
Earth Alarm/Power Supply Module for
520M or 520MC Trip Units
Wiring Diagram for 520M Family Models with
Earth Alarm/Power Supply Module
Earth Earth
Earth
Trip Unit Cat 5MLSI
will indicate high load alarm.
For more information visit: www.cutler-hammer.eaton.com
Digitrip 1150+ and 1150i+
The Digitrip 1150 +is an
enhanced version of the 1150
trip unit that provides comprehensive
protection, metering, communications,
relay and remote control capabilities.
For a complete listing of the Digitrip
1150+Trip Unit capabilities, refer to
its Instruction Leaflet. The following
is a brief first level summary of the
1150+product features:
LSI,LSIG and LSIA Protection
24 Character Digital LED
Display
Unit Status LED (Green)
Indicator
Programmable Protective
Settings:
I2T and I4T Curves
IEC A Curve - Normal Inverse
IEC B Curve - Very Inverse
IEC C Curve - Extremely
Inverse
Neutral Protection
(Model LSI Trip Unit)
Instantaneous Off Setting
Earth Fault Trip or Alarm
Undervoltage and
Overvoltage Protection (Trip or
Alarm)
Underfrequency and
Overfrequency Protection (Trip
or Alarm)
Reverse Power (Trip)
Voltage Unbalance
Protection (Trip or Alarm)
Phase Rotation (Alarm)
Long Time (Thermal) Memory
Trip
Overtemperature Trip when the
temperature exceeds 85°C
View Selection Touch Pads for
Local Metering Display:
Current (1% Accuracy, Three
Phase, Neutral and Earth
Voltage L-L (1% Accuracy)
Frequency 0.05 Hz)
Power & Energy (2% Accuracy)
Kilowatts (kW)
Kilowatt Hours (kWH)
Kilovoltamperes (kVAR)
kVA Hours
Fixed 15 Minute Demand
for kW, kVAR & kVA
Sliding 15 Minute
Demand for kW or kVA
Test Port with cover to receive
Digitrip Hand Held Tester
Power Receptacle for Auxiliary
Power Module to power up trip
unit when breaker is in the
Disconnect or Remove Position
Internal Self-Test
Accessory Bus for additional
programmable contacts
Battery Included to Power
LEDs
Reset/Battery Test
Pushbutton
Power Factor Including
Min and Max
Power Quality Monitoring,
Trip and Alarm:
Waveform Capture
% Total Harmonic
Distortion
Kilovoltamperes (kVAR)
Programmable Alarm
Contacts
Breaker Control (Remote Open
& Close via Communications)
Operations Counter
26 Trip Units and Communications
PG01301002E
May 2003
For more information visit: www.cutler-hammer.eaton.com
27Trip Units and Communications
May 2003
PG01301002E
Communications Functions
and Data:
Communications information and
functions are comprehensive.
Refer to the 1150 Trip Unit
Instruction Leaflet I.L. 70C1036H03
for complete details and capabili-
ties.
Power Relay Module
The Power Relay Module is provided
with the 1150 Trip Unit to perform
the following features:
Power Supply to power the trip
unit’s 24 Character LED display and
communications functions. The
power relay module requires an
external customer supplied voltage
source that is wired through the
breaker secondary contacts. The
source voltage is selected at order
entry and includes the following
voltage options with ± 10% tolerance
and 10VA burden.
24-48 Vdc
120 Vac
240 Vac
Programmable Relay Contacts
via the Digitrip 1150 Trip Unit trip
and alarm programming menus:
Contact A: Alarming and
Tripping Relay for use with the trip
unit protective functions.
Contact B: Block close relay
prohibits the remote closing of the
circuit breaker
Contact C: This latch relay will
hold status upon loss of auxiliary
power
Alarm Contact Ratings
(resistive load):
0.5 Amp at 230 Vac
1.0 Amp at 120 Vac
1.0 Amp at 24-48 Vdc
Potential Transformer (PT)
Module
The PT module provides system line
voltage information to the Digitrip
1150 Trip Unit. It consists of a 3-phase,
3-wire input and 3-wire output step
down transformer with a wye to wye
hookup. A white disconnecting plug
is provided to disconnect the PT
Module circuit from the line voltage
during dielectric testing.
The PT Module primary input voltage
connection is selected when the
breaker is ordered to accommodate
normal or reverse feed application.
PT Module line-side pr load-side
voltage connections are made via
hard wire termination to the breaker
upper or lower conductors.
The normal convention is that the
breaker line side is the upper con-
ductors, with power flowing through
the breaker from top to bottom. In
reverse feed applications, the bottom
conductors are the line side with
power flowing through the breaker
from bottom to top. In this case the
trip unit will indicate REVERSE
POWER, but the reading can be
made an absolute value by installing
a jumper from B3 to B7 on the
breaker secondary contacts.
Power Relay Module for 1150 Trip Unit
PT Module with Dielectric Disconnect Plug
For more information visit: www.cutler-hammer.eaton.com
28 Trip Units and Communications
PG01301002E
May 2003
Power Relay Module Connection to 1150 Trip Unit
SR
L
L
110
220
230 VAC
110 VAC
For more information visit: www.cutler-hammer.eaton.com
29Trip Units and Communications
May 2003
PG01301002E
Accessory Bus
The accessory bus feature on the
Digitrip 1150 Trip Unit permits the
application of additional discrete
programmable relay contacts by the
use of one or more Digital Relay
Modules. The accessory bus is
brought out from the trip unit to
secondary terminals A17 and A18 for
external connections to the Digital
Relay Modules via twisted pair
communications cable.
Digital Relay Module
The Digital Relay Module is mounted
by DIN Rail, separate from the circuit
breaker. Up to 4 Digital Relay
Modules (addresses 001 to 004) can
be applied per circuit breaker. Each
Digital Relay Module has has relays
with form C contacts rated at 10 amps
maximum at 250 Vdc. A control voltage
source of 120 Vac ±20% or 38-125
Vdc is required to power each unit.
Programming
The Digitrip 1150 Trip Unit can be
programmed to drive the Digital
Relay Module relay contacts for any
combination of the following:
Auxiliary Switch
Bell Alarm
Long Delay Trip
Short Delay Trip
Instantaneous Trip
Earth Fault Trip
Earth Fault Alarm
High Load Alarm
Deadman
Watchdog
INCOM Network with Remote Master Computer BIM II
1
1
2
3
3
1
2
3
0 0 1 0 0 2
Cut-off Shield or connect to
unused customer
terminal -- Do not Ground.
Twisted Pair.
No. 18 AWG.
Breaker
Interface
Monitor
(BIM )
ΙΙ
Typical Magnum
Circuit Breaker
with Digitrip Trip Unit
3 Digit
INCOM
Address
Baud Rate
1200 or 9600
See View A
Typical IBM
Compatible
Computer
View A
(Y)
(BL)
Refer to Master Circuit Breaker Connection Diagrams in Appendix C.
Modular telephone connector, Type RJ11, supplied by user.
Ground shielding at computer BIM as shown. Where devices
are daisy-chained, interconnect shielding, but do not ground the connection.
100 ohm ½ watt carbon resistor required at last breaker. See T.D. 17-513.
See Appendix D-11 for programming INCOM function.
AEM is compatible with Digitrip 1150 with AEM firmware version 7.1and the
Digitrip 1150 set in the DT 910 COMM mode. (See page D-11)
Breaker Interface Module (BIM ) Version 3.12 is compatible with Digitrip 1150
Cat # 1****. BIM version 3.13 or greater is compatible with Digitrip 1150
Cat # 1**** and Cat # 11****.
ΙΙ
ΙΙ ΙΙ
ΙΙ
ΙΙ1
1P
NOTICE
100 OHM 1/2W terminating
resistor required on network
even if network is unused
Earth
Earth earth
BIM II as
For more information visit: www.cutler-hammer.eaton.com
30 Trip Units and Communications
PG01301002E
May 2003
Digital Relay Accessory Module
110
For more information visit: www.cutler-hammer.eaton.com
31Trip Units and Communications
May 2003
PG01301002E
MODBUS TRANSLATOR Wiring
110
For more information visit: www.cutler-hammer.eaton.com
32 Trip Units and Communications
PG01301002E
May 2003
Trip Unit Summary Table
In = Rating Plug and Sensor Rating
Ir = Long Delay Pickup Setting
Test set for secondary injection
Model 220+will be available in the second half of 2003. Long Delay Pickup will be adjustable 0.4-1.0 x (In), Long Delay time will be adjustable 2-24 seconds. Cause of Trip Indicators with Battery Back-up
will be added. Contact Cutler-Hammer for availability.
Model 1150i+will be available in the second half of 2003. Over and Undervoltage Alarm or Trip, Over and Underfrequency Alarm or Trip, Voltage Unbalance Alarm or Trip, Reverse Power Trip, and Phase
Rotation Alarm will be added. Contact Cutler-Hammer for availability.
TRIP UNIT TYPE DIGITRIP 220 DIGITRIP 520i DIGITRIP 520Mi DIGITRIP 520MCi DIGITRIP 1150i
Ampere Range 200A-3200A 200A-6300A 200A-6300A 200A-6300A 200A-6300A
Interrupting Rating at 690V 40 through 100kA 40 through 100kA 40 through 100kA 40 through 100kA 40 through 100kA
rms Sensing Yes Yes Yes Yes Yes
PROTECTION AND COORDINATION
Protection Ordering Options LI LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA
Fixed Rate Plug (In) Yes Yes Yes Yes Yes
Overtemperature Trip Yes Yes Yes Yes Yes
Long Long Delay Pickup 1.0 x (In) Fixed 0.4-1.0 x (In) 0.4-1.0 x (In) 0.4-1.0 x (In) 0.4-1.0 x (In)
Delay Long Delay Time I2t at 6 x Ir 10 seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds
Protection Long Delay Time I4t No No No No 1-5 Seconds
(L) Long Delay Thermal Memory Yes Yes Yes Yes Yes
High Load Alarm No No No No 0.5 - 1.0 x (Ir)
Short Short Delay Pickup No 200-1000% x (Ir) and M1 200-1000% x (Ir) and M1 200-1000% x (Ir) and M1 200-1000% x (Ir) and M1
Delay Short Delay Time I2t at 8 x Ir No 100-500 ms 100-500 ms 100-500 ms 100-500 ms
Protection Short Delay Time Flat No 100-500 ms 100-500 ms 100-500 ms 100-500 ms
(S) Short Delay Time ZSI No Yes Yes Yes Yes
Instantaneous Instantaneous Pickup 200-1000% x (In) 200-1000% x (In) and M1 200-1000% x (In) and M1 200-1000% x (In) and M1 200-1000% x (In) and M1
Protection Making Current Release Yes Yes Yes Yes Yes
(I) Off Position No Yes Yes Yes Yes
Earth Earth Fault Alarm No No Yes Yes Yes
Fault Earth Fault Pickup No 25-100% x (In) 25-100% x (In) 25-100% x (In) 24-100% x (In)
Protection Earth Fault Delay I2t at .625 x ln No 100-500 ms 100-500 ms 100-500 ms 100-500 ms
(G) Earth Fault Delay Flat No 100-500 ms 100-500 ms 100-500 ms 100-500 ms
Earth Fault ZSI No Yes Yes Yes Yes
Earth Fault Thermal Memory No Yes Yes Yes Yes
Neutral Protection (N) Yes Model LSI Only Model LSI Only Model LSI Only Model LSI Only
SYSTEM DIAGNOSTICS
Cause of Trip LEDs No Yes Yes Yes Yes
Magnitude of Trip Information No No No Yes Yes
Remote Signal Contacts No No Yes Yes Yes
Programmable Contacts No No No No Yes
SYSTEM MONITORING
Digital Display No No 4 Char. LCD 4 Char. LCD 24 Char. LED
Current (%) Full Scale Sensor No No Yes Yes Yes +/- 1%
Voltage (%) L to L No No No No Yes
Power and Energy (%) No No No No Yes
Apparent Power kVA and Demand No No No No Yes
Reactive Power kVAR No No No No Yes
Power Factor No No No No Yes
Crest Factor No No No No Yes
Power Quality - Harmonics No No No No Yes
% THD No No No No Yes
SYSTEM COMMUNICATIONS
Type No No No INCOM/PowerNet INCOM/PowerNet/Trip Link
Power Supply N/A N/A PRM in Breaker PRM in Breaker PRM in Breaker
ADDITIONAL FEATURES
Trip Log (3 Events) No No No No Yes
Electronic Operations Counter No No No No Yes
Testing Method Test Set Test Set Test Set Test Set Integral and Test Set
Waveform Capture No No No No Yes
For more information visit: www.cutler-hammer.eaton.com
33Trip Units and Communications
May 2003
PG01301002E
Current Sensor
Toroidally wound current sensors
are installed at the rear of the circuit
breaker on the lower horizontal ter-
minals. They are available in ampere
ratings of 200 through 6300 amperes,
and must match the current rating
of the installed rating plug.
The sensors produce an output current
proportional to the load current.
Under preselected conditions of cur-
rent magnitude and time, the sensors
furnish the trip unit with a signal and
the energy required to open (trip) the
circuit breaker.
The current rating of the installed
sensors can be easily viewed from
the rear of the circuit breaker
through small viewing windows.
The viewing windows are part of the
sensor cover plate which is removed
to change the sensors.
Neutral current sensors are available
for customer installation. The addi-
tional sensor is not supplied with the
circuit breaker and must be ordered
separately. They are wired to the trip
unit through the secondary contacts
on the circuit breaker.
Mechanical Trip Flag Pop-Out
Indicator
The mechanical trip flag pop-out
indicator is an overcurrent indication
feature that can be supplied as an
option on Magnum Circuit Breakers
with integral trip units. This device
is located just above the trip unit on
the breaker’s front faceplate. In the
event the trip unit trips the breaker
on an overcurrent condition, the red
trip flag releases and pops out to
give local visual indication. This
trip indication is in addition to any
LED trip indication provided by the
trip unit.
The red flag can be reset by manually
pushing it back in. The circuit breaker
can be re-closed, even if the flag is
not reset. An optional Overcurrent
Trip Switch (OTS) is available in the
event that an electrical lock-out is
required on an overcurrent trip
condition.
Making Current Release
The Making Current Release (MCR) is
a standard safety feature provided
on all Magnum Circuit Breakers that
are equipped with integral trip units.
The MCR provides an instantaneous
trip when closing on a fault current
which exceeds a specified magnitude.
The MCR is non-adjustable and preset
Wiring
Plug
Toroidal
Current
Sensor
Sensor Rating
Viewing
Window
Current
Sensor
Cover
Sensor
Rating
Rating Plugs and Matching Sensors
Current Sensor Cover in Place Over Sensors Current Sensor Cover and One Sensor Removed
Neutral Sensor (unmounted)
Ratings (Amperes)
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
2500
3000
3200
4000
5000
6300
Note: Refer to Tables 3.4, 3.5 and 3.6 in the
section entitled
Circuit Breaker Catalog
Number
for the availability of sensor and rat-
ing plug ratings for specific circuit breaker
frame sizes.
For more information visit: www.cutler-hammer.eaton.com
to trip the breaker when the peak
instantaneous current exceeds 25 x
In (In is established by the breaker’s
current sensors and rating plug).
The MCR is enabled for only the first
two cycles following the circuit
breaker closing operation. When the
MCR trips the breaker, the red trip
flag of the mechanical indicator will
pop out and the red Instantaneous
LED of the trip unit will flash if the
breaker is so equipped.
Bell Alarm/Overcurrent Trip
Switch (OTS)
The Bell Alarm/Overcurrent Trip
Switch (OTS) is an overcurrent indi-
cation feature that can be supplied
as an option on Magnum Circuit
Breakers with integral trip units.
The OTS is physically mounted on
the Mechanical Trip Flag Pop-out
Indicator. The OTS Switch includes
2 Form C contacts that are wired to
the breaker secondary terminals as
shown in the Magnum breaker
connection diagram. These contacts
are available for external wiring to
provide remote trip indication or for
electrical lock-out of a circuit breaker
as required.
In the event the trip unit trips the
breaker on an overcurrent condition,
the red flag of the Mechanical Trip
Flag Pop-ot Indicator releases and
pops out and the OTS contacts
change state. The OTS Switch can
be reset by manually pushing in the
red trip flag. When the trip flag is
reset, the OTS Switch contacts return
to their normal state.
High Instantaneous Trip
Magnum Circuit Breakers that are
rated 100kA and manufactured in the
Standard Frame with 800 to 3200
ampere continuous current ratings
(MWIC08 to MWIC32) are equipped
with a high instantaneous trip. This
instantaneous trip system consists of
small air core sensors (one per
phase) which produce a signal and
transmit it back to the trip unit.
When the fault current approaches
the 85kA withstand rating of the cir-
cuit breaker,
to be closed into repeated overload
conditions, the breaker will trip in
successively shorter times to allow
for the cooling of the load circuit.
When the overload condition returns
to normal, the LTM function begins
to slowly reset and will fully reset
back to the normal Long Delay
Time setting after about 10 minutes,
provided that another overload is not
experienced.
In some applications, for example
fire pump, electric welders or during
primary injection current testing, it
may be desirable to defeat the LTM.
This can be accomplished at the trip
unit by moving a jumper located
inside the cavity behind the test port
cover located at the front of the trip
unit to the Inactive position. The
LTM can be reactivated by returning
the jumper to the Active position.
the trip unit trips the breaker instan-
taneously. This allows the breaker to
be applied on a power distribution
system with a 100kA available fault
current while main-taining selectivity
up to 85kA.
Long Time Memory (LTM)
Long Time Memory (Thermal
Memory) is a standard feature on
Magnum Circuit Breakers supplied
with integral trip units. The thermal
memory function provides overtem-
perature protection on load circuits
against the effects of repeated over-
load conditions. If a breaker is
closed soon after an overload trip
and the current again exceeds the
Long Delay Setting, the LTM reduces
the time to trip to allow for the fact
that the load circuit temperature is
higher than normal due to the previous
overload condition. If the breaker
continues
34 Trip Units and Communications
PG01301002E
May 2003
Digitrip RMS 1150 Programmable Trip Unit Installed
Test
Receptacle
(with
Cover)
Rating
Plug
Auxiliary
Power
Module
Port
In = 800A
Trip Flag
Pop-Out
Indicator
For more information visit: www.cutler-hammer.eaton.com
35Trip Units and Communications
May 2003
PG01301002E
Over-Temperature Trip
Magnum Circuit Breakers equipped
with integral trip units have an over-
temperature trip function provided as
a standard feature. The over-temper-
ature trip is designed to trip the
breaker when the internal tempera-
ture of the trip unit exceeds 85°C.
This is the approximate manufactur-
er’s published maximum tempera-
ture rating for the trip unit electronic
components. An 85°C temperature
inside the trip unit indicates that
there are much higher temperatures
and potentially significant heating
problems elsewhere on the circuit
breaker.
When the over-temperature function
trips the breaker, the red trip flag of
the mechanical indicator will pop-out
and the red Long Time Delay LED of
the trip unit will flash is the breaker
is so equipped.
Ground Fault Provisions and
Protective Schemes
As a standard feature, Magnum
Circuit Breakers are internally wired
with provisions for ground fault
protection. However, ground fault
protection is provided only if the
breaker is equipped with a trip unit
with optional LSIG protection.
Ground fault protection can be easily
added to breakers not originally
equipped with a ground fault trip
unit. For example, an LSI trip unit
can simply be changed out with a
like model trip unit that has LSIG
protection. Modifications to the circuit
breaker internal wiring are generally
not required as long as the trip unit
changeout is with a like model trip unit.
To provide for maximum application
flexibility, breaker ground fault provi-
sions are wired out to the breaker
secondary terminals for external use.
The secondary terminals can be
easily configured to accommodate
the most common ground fault
schemes, including:
NOTE: For detailed wiring
diagrams that describe all
ground fault sensing options
and wiring connections, refer to
the Trip Unit Instruction Leaflet.
Multiple Source/Multiple Ground
Multiple Source/Multiple Ground
sensing schemes are also possible
on systems with multiple sensors.
Zone Interlocking
Zone Selective Interlocking is a
standard feature provided on
Magnum Circuit Breakers that are
supplied with Digitrip 520i or higher
trip units. The trip unit Short Time
and Ground Fault Time Delay Zone
Interlock function is wired out to
breaker secondary terminals B8 and
B9 for customer use.
The zone interlock function provides
for hard-wired selective circuit breaker
coordination in the power distribution
system. When employed, breaker
secondary terminals B8 and B9 are
connected to establish zones of
downstream and upstream breakers
using 3 wires: Zin, Zout, and a common
wire to establish the zone.
NOTE: For detailed wiring dia-
grams that describe zone selective
interlocking schemes and wiring
connections, refer to the trip
unit instruction leaflet.
In the event that a fault current on
the system exceeds the trip unit
Short Time or Ground Fault pick-up
settings or the Short Delay Setting
2xIr is exceeded, the breaker nearest
to the fault trips instantaneously. At
the same time the trip unit sends a
logic signal to the connected
upstream trip unit to restrain it from
tripping immediately and follow its
protective delay settings. Coordination
is maintained, the breaker closest to
the fault trips first and power is only
selectively disrupted.
NOTE: If zone interlocking is not
employed, it may be defeated
by installing a shorting jumper
across breaker secondary termi-
nals B8 and B9.
Installing a jumper in this manner
defeats the zone interlock function
and tells the trip unit to follow its set
Short Time and Ground Fault Time
protective delays. If breaker sec-
ondary terminals B8 and B9 are left
as open circuit, the trip unit Short
Time and Ground Fault Time Delay
functions will trip instantaneously if
the system fault current exceeds the
pick up setting.
Residual Sensing
Residual sensing is the standard or
default wiring configurations provided.
It is also the most common mode of
ground fault sensing used in 3-pole
and 4-pole breaker applications. One
current sensor per pole on each
phase conductor is provided internal
to the circuit breaker. When 3-pole
breakers are applied on 3 phase, 4
wire systems, an external sensor
matched to the breaker sensor ratio
is mounted on the Switchgear neutral
bus and wired to the breaker secondary
contacts to connect all sensors in the
residual circuit.
Source Ground Sensing
Source ground sensing is commonly
found on 3 pole breakers applied as
a main breaker on single-ended radial
or on double-ended systems where
a mid-point grounding electrode is
employed.
To configure a breaker for source
ground sensing, a shorting jumper is
applied to breaker secondary contacts
B6 and B7 to defeat the residual
sensing mode. An external current
sensor is mounted directly on the
bonding conductor to ground to
measure the ground current flowing
in the grounding electrode conductor
and all other grounding conductors.
The sensor is then wired to the breaker
secondary contacts B4 and B5.
NOTE: The secondary current
rating of the sensors must be 1
ampere.
Zero Sequence Sensing
Zero sequence sensing is applied on
main and feeder breakers, and other
breakers employed in zone interlocking
ground protection schemes.
To configure a breaker for zero
sequence sensing, a shorting jumper
is applied to breaker secondary con-
tacts B6 and B7 to defeat the residual
sensing mode. Zero sequence sensors
with 1000:1 and 100:1 ratios are
available for mounting in the
switchgear cable compartment. The
sensor internal window dimensions
are 114 x 342 mm (4.5 x 13.5 inches)
for accommodating power cables.
The zero sequence sensors are wired
to breaker secondary contacts B4
and B5.
For more information visit: www.cutler-hammer.eaton.com
Fixed Mounted Circuit Breakers
Magnum fixed mounted circuit
breakers are commonly applied in
specialty power distribution enclo-
sures and switchboards manufac-
tured by Low Voltage Power
Assemblers.
The fixed circuit breaker construction
is simple and economic because
there are no drawout system compo-
nents. The breaker bolts directly to
the enclosure main bus, which
allows for efficient current transfer
under loaded conditions. This
improves thermal management and
provides for the design of compact
enclosures with shallow depth.
Full visual and physical access to the
circuit breaker trip unit, controls, and
indicators is available through the
compartment front panel. A door
frame and escutcheon kit is available
as an option to provide a finished
trim to the front panel cutout.
Extensive accessorization capability
of the breaker is retained, including
trip units, internal accessories, lock-off
devices, and mechanical interlocks.
Primary Terminations
Horizontal pre-drilled terminal pads
are provided as a standard feature
for use in terminating the breaker to
the enclosure bus. Optional vertical
adapters can be factory installed or
are available as field option kits to
provide the capability to terminate
the enclosure bus in the vertical
plane. Field option kits are also
available for front connected
applications.
If the benefit of front accessible
dedicated terminal blocks at the top
front of the breaker is desired, the
terminal block mounting bracket
included in the secondary connection
terminal kit can be used. Catalog
Number MSECBK white terminal block
kits can be purchased and assembled
to the mounting bracket. Catalog
Number MSECWR wire kits can be
purchased to connect the white
terminal block to the black AMP
connector block points.
Mounting Feet
Metal mounting feet are provided as
a standard feature for use in securely
bolting the breaker to the enclosure.
Secondary Connections
Two black 30-pin AMP connector
blocks are located at the top front of
the breaker to receive up to 60 points
of external secondary wiring. A
secondary connection terminal kit is
included with each fixed breaker to
provide for several wiring options.
The most economic solution is to
terminate external wiring directly to
the black AMP connector blocks.
Catalog Number MWK40 wire bundle
kits with 30 wires 40 inches long can
be purchased for this purpose. The
wire bundles can also be self-fabricated
by the enclosure manufacturer,
provided the proper AMP terminal
and crimping tool are used.
36 Fixed Circuit Breakers
PG01301002E
May 2003
Closeup of Fixed Circuit Breaker’s Connection Possibilities
Fixed Circuit Breaker (front view)
Optional
Vertical
Adapter
Standard
Horizontal
Connection
Mounting
Foot
For more information visit: www.cutler-hammer.eaton.com
37Drawout Circuit Breakers
May 2003
PG01301002E
Drawout Circuit Breakers
Magnum drawout circuit breakers
are commonly applied in specialty
power distribution enclosures,
switchgear and switchboards manu-
factured by Low Voltage Panel
Assemblers.
The Magnum drawout circuit breaker
construction is a through-the-door
design. Full visual and physical
access to the trip unit and all breaker
controls and indicators is available
through the compartment front
panel. For maximum safety, circuit
breaker levering can be performed
with the compartment door closed.
When the circuit breaker is in the
OPEN position, a padlockable access
door can be raised to receive the
levering device. No special device is
required. Levering can be accom-
plished with a common 10 mm size
square drive and rachet. When
inserted, the levering device holds
the levering access door open. As
long as the access door is raised
open, the breaker is held in the “trip-
free” condition. The breaker can be
levered to three positions in the cell
compartment. Colour coded position
indicators are provided on the breaker
front panel to provide positive indi-
cation of each position:
Green = DISCONNECT
Yellow = TEST
Red = CONNECT.
Secondary Disconnect Contacts
The breaker secondary disconnecting
contacts engage or disconnect with
the cassette secondary contacts as
the breaker is levered into or out of
the TEST position.
Primary Disconnecting Contacts
The primary disconnecting contacts
(finger clusters) engage or disconnect
with the cell compartment bus stabs
as the breaker is levered into or out
of the CONNECT position.
The primary disconnecting contacts
are mounted on the rear of the
breaker so that they can be easily
inspected or replaced. All breaker
frames have horizontal primary dis-
connects.
Circuit Breaker Being Levered
CONNECT
TEST
DISCONNECT
CONNECT
TEST
DISCONNECT
Rear View Standard Frame Breaker
Horizontal
Primary
Disconnect
Rear View Narrow Frame Breaker
Horizontal
Primary
Disconnect
For more information visit: www.cutler-hammer.eaton.com
Drawout Cassette
A drawout circuit breaker is used in
combination with a fixed drawout
cassette. The cassette provides for
all the required fixed drawout features
as well as fixed primary and secondary
connections. Mounting locations for
cell (TOC) switches, primary safety
shutters and various key interlocks
are part of the cassette design.
The cassette has built in horizontal
stabs and primary terminals.
Optional bolt-on 90 degree adapters
are available to rotate the primary
terminals on the rear of the cassette to
a vertical orientation; these can be
used on either the line, load or both
primary connection.
It should be noted that short circuit
currents create very large electro-mag-
netic forces on the bus bars which
must be adequately supported by the
assembly builder. Outline drawings
for each cassette give minimum dis-
tances from the rear of the cassette
wherein adequate bus bar supports
must be provided. The design of
these supports depends upon the bus
bar configuration and short circuit rat-
ing and is the responsibility of the
assembly builder.
38 Drawout Circuit Breakers
PG01301002E
May 2003
Narrow Frame Breaker and Cassette
Rear View
Standard Frame Cassette
The cassette's drawout extension
rails can be padlocked to prevent a
circuit breaker from being inserted
during maintenance periods. In
addition, the cassette includes all
required safety interlocks which
function with the circuit breaker's
interlock system to insure safe
operation.
An arc hood is positioned above
where the circuit breaker's arc chutes
will be allowing for zero clearance
mounting when vertically stacked in
an assembly. Mounting holes are
provided at the rear and in the floor
of the cassette for secure mounting
in an assembly.
For more information visit: www.cutler-hammer.eaton.com
39Phasing on Double-Wide Breakers
May 2003
PG01301002E
Phasing on Double-Wide Frame
Breakers
Magnum circuit breakers manufac-
tured in the double-wide frame have
two available phasing configurations
which must be confirmed when the
breaker is ordered.
The phasing convention is determined
facing the front of the breaker from
left to right. For 4-pole applications,
the neutral is located on the left and
is rated 100% of the breaker continuous
current rating. The following phasing
configurations are available:
3-Pole AABBCC
4-Pole NNAABBCC
3-Pole ABCABC
4-Pole NNABCABC
The type of phasing selected
depends on how the circuit breaker
will be applied in the enclosure and
the type of Cutler-Hammer power
distribution enclosure that it will be
applied in.
AABBCC or NNAABBCC Phasing
AABBCC phasing is the convention
commonly used in IEC Switchboards
using Magnum Circuit Breakers.
The AABBCC convention is recom-
mended for most switchgear assembler
manufacturing their own power
distribution enclosures. It is ideal for
applications where the breaker is
mounted single high (one breaker in
a structure).
ABCABC or NNAABCABC
Phasing
ABCABC phasing is available, but not
common in IEC Switchgear
Applications. Contact Cutler-
Hammer for more information.
Magnum Double-Wide Frame Breaker with AABBCC Phasing (front and rear views)
For more information visit: www.cutler-hammer.eaton.com
Accessory Devices
A variety of accessory devices are
available for use with Magnum circuit
breakers. Unless otherwise stated,
they are all considered optional
devices in the sense that they are not
provided as standard on a manually
operated circuit breaker. Available
accessories are identified here and
discussed in general terms. For
more detailed information and/or
installation instructions, refer to indi-
vidual instruction leaflets dedicated
to the accessories.
Magnum circuit breaker accessories
are designed to fit all frame sizes.
The accessories fall into one of three
categories:
Plug-in electrical
Internal electrical
Mechanical
Plug-In Electrical Accessories
There are four Magnum Plug-In
electrical accessories. Three can be
viewed for identification by name
and rating through viewing windows
located in the right front of the circuit
breaker(Figure 1). All four are plug-in
type and can be factory installed or
field installed.
The four Plug-In accessories are:
Shunt Trip (ST)
Spring Release (SR)
Undervoltage Release (UVR)
Auxiliary Switch
Shunt Trip (ST) - The ST (Shunt
Trip Device, Figures 2and 3) is an
optional accessory device that is
mounted internal to the circuit break-
er. The ST acts to electrically open
the circuit breaker when its trip coil
is energized by a rated trip voltage
signal (Table 1) that is applied
through the breaker secondary con-
tacts, typically by a control switch or
other similar device. The ST has a
dedicated auxiliary switch with con-
tacts that change state as the breaker
opens, cutting off trip voltage signal
to the trip coil.
A second shunt trip (with the same
or different control voltage) can be
mounted in the same space as the
Undervoltage Release (UVR). When
a second shunt trip is used, one of
the auxiliary switch stages must be
used to provide the trip coil cut off
contact.
40 Accessory Devices
PG01301002E
May 2003
Operational Opening
Control Voltage Range Inrush Power Time
Voltages 70-110% Consumption (ms)
24 Vdc
48 Vdc
110-125 Vdc
220-250 Vdc
110-127 Vac
208-240 Vac
17-26 Vdc
34-53 Vdc
77-138 Vdc
154-275 Vdc
77-140 Vac
146-264 Vac
250 W
250 W
450 W
450 W
450 VA
450 VA
35
35
35
35
35
35
Required for less than 35 ms
Table 1 Shunt Trip Ratings
Figure 1 Through-the-Window Electrical Accessories
Accessory Viewing Windows
Figure 2 Shunt Trip with Cutoff
Switch
Figure 3 Shunt Trip Switch Installed
For more information visit: www.cutler-hammer.eaton.com
41Accessory Devices
May 2003
PG01301002E
Spring Release (SR) - The SR
(Spring Release Device, Figure 4) is
an optional accessory device that is
mounted internal to the circuit break-
er. The SR acts to electrically close
the circuit breaker when its close coil
is energized by a rated close voltage
signal (Table 2) applied through the
breaker secondary contacts, typically
by a control switch or other similar
device.
The breaker must be ready to close
for the SR to close the circuit breaker.
The breaker stored energy springs
must be fully charged and the trip
latch must be in the reset (not the
trip) position. If the close voltage
signal is applied before these two
conditions are met, the SR will not
close the circuit breaker. The close
voltage signal must be removed and
then reapplied at a time when the
breaker is ready to close.
Latch Check Switch Wired For
External Use - The LCS can also
be wired to the breaker secondary
contacts. One Form C contact is
provided for remote indication that
the breaker is ready to close for
use in breaker external customer
control wiring.
Undervoltage Release - The under-
voltage release is an optional device
on both manually and electrically
operated circuit breakers (Figure 5).
It opens the circuit breaker when its
supply voltage falls to between 35-
60% of rated voltage. If the release
is not energized to 85% of its supply
voltage, the circuit breaker cannot
be closed electrically or manually
(Table 3).
Latch Check Switch (LCS) - The
LCS (Latch Check Switch) is an
optional accessory switch mounted
internal to the circuit breaker that
changes state when the breaker is
ready to close (the closing springs
are fully charged and trip latch is in
the reset position). The LCS is very
useful in fast transfer and automatic
transfer applications when it is
important that the breaker responds
to close on a single close voltage sig-
nal of rated magnitude. The LCS is
available in two versions:
Latch Check Switch Wired To
Spring Release - The LCS can be
wired directly to the Spring
Release Device to provide a con-
tact closure when the breaker is
ready to close. This delays the
voltage signal to the Spring
Release until the breaker is ready
to close.
Figure 4 Spring Release with
Optional Latch Switch
Operational Closing
Control Voltage Range Inrush Power Time
Voltages 70-110% Consumption (ms)
Table 2 Spring Release Ratings
Required for less than 200 ms
24 Vdc
48 Vdc
110-125 Vdc
220-250 Vdc
110-127 Vac
208-240 Vac
17-26 Vdc
34-53 Vdc
77-138 Vdc
154-275 Vdc
77-140 Vac
146-264 Vac
250 W
250 W
450 W
450 W
450 VA
450 VA
40
40
40
40
40
40
Figure 5 Undervoltage Release Figure 7 Shunt Trip, Spring Release
and Undervoltage Release Installed
For more information visit: www.cutler-hammer.eaton.com
Internal Electrical Accessories
Other electrical accessories are
mounted inside the circuit breaker.
They can be factory or site installed.
There are two different internally
mounted accessories:
Overcurrent Trip Switch (Bell
Alarm)
Motor Operator
Overcurrent Trip Switch (Bell
Alarm) - An overcurrent trip switch
(bell alarm) is an optional device
(Figure 8). It provides an electrical
indication when a circuit breaker trips
as a result of the trip unit reacting to
an overcurrent condition. Opening as
a result of a circuit breaker’s manual
open button, shunt trip or undervoltage
release does not cause the overcurrent
trip switch to operate. The overcurrent
trip switch has (2a 2b) Form C contacts
(Table 4).
The status of the contacts
changes when the trip indicator pops
out. This permits the
switch to be used as an alarm
or in conjunction with a spring
release to block a subsequent remote
electrical closing signal.
42 Accessory Devices
PG01301002E
May 2003
Table 3 Undervoltage Release
Operational Dropout ① ➁ Opening
Control Voltage Range Volts Inrush/Continuous Time
Voltages 85-110% 30-60% Power Consumption (ms)
24 Vdc
32 Vdc
48 Vdc
110-125 Vdc
220-250 Vdc
110-127 Vac
208-240 Vac
380-415 Vac
480 Vac
600 Vac
20-26 Vdc
27-35 Vdc
41-53 Vdc
94-138 Vdc
187-275 Vdc
94-140 Vac
177-264 Vac
323-457 Vac
408-528 Vac
510-660 Vac
7-14 Vdc
10-19 Vdc
14-29 Vdc
33-75 Vdc
66-150 Vdc
33-76 Vac
62-144 Vac
114-249 Vac
144-288 Vac
180-360 Vac
250 W/18 W
275 W/15 W
275 W/18 W
450 W/10 W
450 W/10 W
450 VA/10 VA
400 VA/10 VA
480 VA/10 VA
400 VA/10 VA
400 VA/10 VA
70
70
70
70
70
70
70
70
70
70
Required for 200 ms
Required for 400 ms
Figure 8 Mechanical Trip Indicator
with Associated Overcurrent Trip
Switch
Mechanical
Trip
Indicator
Auxiliary Switch - An auxiliary
switch is an optional accessory
device that is mounted internal to the
circuit breaker. Each auxiliary switch
stage (Figure 6) has 2a (normally
open) and 2b (normally closed) con-
tacts wired to the breaker secondary
contacts for customer use in remote
indication or external electrical
schemes. (See Table 4for auxiliary
switch contact ratings.) The contacts
change state as the breaker opens
and closes.
A maximum of 3 switch stages of
2a/2b contacts can be mounted in
Magnum Standard and Double
Frame Circuit Breakers for a total of
6a and 6b available contacts. If more
than two switch stages are required
on the Narrow Frame Breaker, refer
the application to Cutler-Hammer.
Due to the 48 point secondary termi-
nal block limitation on the Narrow
Frame Breaker, only 2 stages of 2a/2b
contacts can be mounted if the full
compliment of breaker internal
accessories are employed. However,
if the breaker is not fully acces-
sorized, the Narrow Frame Breaker
can accommodate 3 auxiliary switch
stages of 2a/2b contacts.
Figure 6 Auxiliary Switch (2A/2B)
Table 4 Auxiliary Switch,
Overcurrent Trip Switch and
Cell Switch Contact Ratings
Control Contact Rating
Voltages Inductive Load
(amperes)
250 Vac
125 Vdc
250 Vdc
10
0.5
0.25
For more information visit: www.cutler-hammer.eaton.com
43Accessory Devices
May 2003
PG01301002E
Figure10 Motor Operator Installed
in Narrow Frame Circuit Breaker
Motor Operator - A Motor operator
is an electric motor assembly internally
mounted in the circuit breaker
(Figures 9 and 10). It charges the
closing springs electrically for remote
or local operation. The motor operator
can be factory or site installed (Table
10).
To convert a manually operated circuit
breaker to an electrically operated
circuit breaker, a motor operator kit
is available.
Table 5 Motor Operator
Control Operational Running Typical Power Maximum
Voltage Range Current Inrush Consumption Charging Time
Voltages 85-110 % (A. avg.) Current (watts or VA) (seconds)
24 Vdc
48 Vdc
110-125 Vdc
220-250 Vdc
110-127 Vac
208-240 Vac
20-26
41-53
94-138
187-225
94-140
177-264
12.0
5.0
2.0
1.0
2.0
1.0
300% of Running
500% of Running
600% of Running
600% of Running
600% of Running
600% of Running
300
250
250
250
250
250
5
5
5
5
5
5
AC voltages are 50/60Hz
Figure 9 Motor Operator Kit
For more information visit: www.cutler-hammer.eaton.com
Door Escutcheon - The door
escutcheon is a molded frame used
to seal the space between the circuit
breaker and the compartment door
cutout. It is supplied with a mounting
gasket (Figure16).
IP54 Cover - A hinged dome
shaped cover attaches to the metal
compartment door to provide water-
proof protection for the circuit break-
er (Figure 17).
Cassette Cell Switch - The cassette
cell switch (Figures 14 and 15) is
also known as the cell position
switch or the TOC (Truck Operated
Cell) switch. The cell switch is an
optional accessory that is provided in
kit form for installation by the panel
assembler. Up to 3 cell switch
stages, each with 4 Form C contacts
can be mounted on the right hand
side of the cassette. (See Table 4for
cell switch contact ratings.) One
stage can be mounted on each of the
DISCONNECT, TEST, or CONNECT
mounting locations on the cassette.
The switch contacts change state
when the breaker is levered into the
DISCONNECT, TEST, or CONNECT
positions. Wires are provided for
each set of Form C contacts for ter-
mination to the breaker secondary
terminal blocks (white) or other cus-
tomer supplied terminal blocks in the
breaker cell compartment. The con-
tacts are generally used for remote
indication or for customer use in
external breaker control schemes.
44 Accessory Devices
PG01301002E
May 2003
Figure 16 Door Escutcheon and
Gasket
Figure 17 IP54 Cover
Figure 14 Cell Switch (Drawout
Position Indicator) Unmounted
Figure 15 Cell Switches Mounted
on Cassette
Figure 12 Safety Shutters in Closed
Position Figure 13 Safety Shutters in Open
Position
Cassette Safety Shutters -
Automatically operated insulatin type
safety shutters are available for use
with the drawout cassette. When the
drawout circuit breaker is levered
from the CONNECT position, the
shutters automatically close to cover
the fixed primary contacts (Figure
12). When the circuit breaker is lev-
ered into the cassette, the shutters
automatically open permitting prima-
ry connections to be made (Figure
13).
Mechanical Accessories
There are six optional mechanical
type accessories:
Operations Counter
Cassette Safety Shutters
Cassette Cell Switch
Door Escutcheon
Waterproof Cover
Mechanical Interlock
Operations Counter - The operations
counter is a mechanical device used
to provide a record of the number of
circuit operations. It is mounted in
the lower right portion of the circuit
breaker and can be viewed through
the front cover (Figure 11).
Figure 11 Operations Counter
Operations
Counter
For more information visit: www.cutler-hammer.eaton.com
45Accessory Devices
May 2003
PG01301002E
Mechanical Interlock - A family of
mechanical interlocks are available to
interlock the closing of two or three
Magnum circuit breakers. The
mechanical interlock holds one or
more circuit breakers tripped (prevents
closure) when others are closed. A
lever assembly is mounted on each
breaker which interfaces with the
pole shaft and the tripper bar. The
lever assemblies are interconnected
with either cables or rods, depending
upon the relative orientation of the
breakers. Rods can be used only
when the circuit breakers to be inter-
locked are vertically stacked. Cables
can be used for any orientation of
the breakers. Mechanical interlocks
are available for both fixed and drawout
circuit breakers and in both 2-way
and 3-way versions. An illustration
of a 2-way cable interlock mounted
on two drawout circuit breakers is
shown in Figure 18. In addition,
refer to Table 6 for the possible
mechanical interlock configurations.
Figure 18 Cassette-Mounted 2-Way
Cable Interlock
Table 6 Mechanical Interlock Configurations
Type of Number of Breakers Possible
Interlock Interlocked Description of Interlocks Interlock Logic
Type 2
Type 31
Type 32
Type 33
Across 2 Breakers
Across 3 Breakers
Across 3 Breakers
Across 3 Breakers
One Normal Power Supply (A)
One Emergency Power Supply (B)
Two Normal Power Supplies (A & C)
One Emergency Power Supply (B)
Circuit Breakers A and C can be closed if B is
open. B can only be closed if A and C are open.
Two Power Supplies (A & C)
One Bus Tie Breaker (B)
One or two breakers out of 3 can be closed at the
same time.
Three Power Supplies (A, B & C)
Normal or Emergency, only one of which can be
closed at a time.
A B
0 0
1 0
0 1
A B C
0 0 0
1 0 0
0 1 0
0 0 1
1 0 1
A B C
0 0 0
1 0 0
0 1 0
0 0 1
1 1 0
0 1 1
1 0 1
A B C
0 0 0
1 0 0
0 1 0
For more information visit: www.cutler-hammer.eaton.com
Breaker Lock OFF Devices
Magnum DS Circuit Breakers are
equipped with a variety of lock
off devices for both the Circuit
Breaker and the Drawout Cassette to
maximize safety during equipment
operation and maintenance.
Padlockable Levering Device
Access Door - The levering Device
access door includes padlock provi-
sions as a standard feature on all
drawout circuit breakers. It is
designed to receive a padlock up to
8 mm (0.312 inches) in diameter.
When the access door is padlocked
shut, the breaker levering tool cannot
be inserted, preventing the breaker
from being levered to another
position (Figure 1).
Access Door - The padlockable
pushbutton cover is an optional
factory configured or field option kit
accessory that mounts on the breaker
faceplate. It is available with either
molded plastic or metal frames with
clear plastic hinged blocking plates
(Figure 2). When they are closed
and padlocked, the blocking plates
prevent access to the breaker PUSH
OFF and PUSH ON mechanical push-
buttons. This device can also be
configured with an additional plate to
block only the PUSH ON pushbutton.
A small hole is pre-drilled in the
blocking plates to provide emergency
access with a special tool as required
per the National Electric Code. The
padlockable pushbutton cover will
receive a padlock with up to a 8 mm
(0.312 inches) diameter.
Cassette Lock Provisions - The
cassette lock provisions field option
kit is an accessory that mounts on
the side of a circuit breaker cassette
(Figure 4). The customer must specify
if the lock is to be located on the left
or right-hand side of the cassette.
When installed, the device holds the
breaker trip-free when the breaker is
levered to the CONNECTED position.
This prevents the breaker from being
closed and circuit energized.
Single or multiple cylinder Kirk,
Castell or Ronis locks can be accom-
modated. The device can be used
with commonly applied breaker
interlocking schemes such as
Main-Tie-Main configurations, etc.
Breaker OFF Key Lock Provisions
-The breaker OFF key lock is an
optional accessory that allows the
breaker to be locked in the OFF posi-
tion with the key removed, prevent-
ing the breaker from being closed. It
is primarily intended for use on fixed
mounted circuit breakers, but can
also be applied on drawout breakers
(Figure 3).
When selected as a factory configured
option, the breaker includes a pre-
drilled hole covered with a plastic
cap on the breaker front cover. A
lock provisions hardware kit is
shipped with the breaker to facilitate
installation of a single Kirk, Castell
or Ronis cylinder lock. The cylinder
lock is generally provided and
assembled to the breaker at the point
of use by the enclosure manufacturer
or customer. For existing breakers,
a breaker key lock provisions field
option kit is also available. To facilitate
installation, a drill point mark is
located on the inside of the breaker
front cover to identify the drilling
location for the key lock installation.
46 Breaker Lock OFF Devices
PG01301002E
May 2003
Figure 1 Closeup of Padlockable
Levering Device Access Door
Figure 2 ON-OFF Pushbutton
Lockable Cover Plate
Figure 3 Cover Mounted Key Lock
“OFF”
Key Lock
Figure 4 Cassette Mounted Key Lock
For more information visit: www.cutler-hammer.eaton.com
47Breaker Lock OFF Devices
May 2003
PG01301002E
Cassette Shutter Lock
Provisions - As a standard feature,
the narrow frame cassette shutter
system includes provisions to pad-
lock the shutter in the CLOSED posi-
tion when the breaker is withdrawn.
The shutter lock provisions will receive
a padlock with up to a 0.312 inches
(8 mm) diameter.
For more information visit: www.cutler-hammer.eaton.com
Ambient Temperature
This table gives derating factors for
circuit breakers operating in switch-
boards at various internal ambient
temperatures. The switchboard’s
internal ambient should be estimated
using the calculation methods of IEC
890, 1997 or an equivalent method.
Bus Bar Recommendations
The bus bar sizes shown in the table
are those specified in IEC 947-1
and/or used by Cutler-Hammer in
their circuit breaker type testing.
They are for 3 meter long bus bar
with the faces vertical and painted
flat black. For other bus bar configu-
rations, larger bus bar sizes may be
required or the circuit breaker may
have to be derated. Refer to the
table in this section entitled “Circuit
Breaker Continuous Current Ratings
at Different Ambients” for derating
information at higher ambient tem-
peratures. Refer to the two graphic
examples below.
48 Application and Installation Information
PG01301002E
May 2003
Circuit Breaker Continuous Current at Different Ambients
Continuous Current
Current By Breaker
Type (Amperes)
MWN-408, 608
MWI-508, 608, 808, C08
MWN-410, 610
MWI-510, 610, 810, C10
MWN-412, 612
MWI-512, 612, 812, C12
MWN-516, 616
MWI-616, 816, C16
MWN-520, 620
MWI-620, 820, C20
MWI-625, 825, C25
MWI-632, 832, C32
MWI-64N, 84N, C4N
MWI-850, C5N
MWI-863, C6N
Ambient Temperature (°C)
40
800
1000
1250
1250
1600
1600
2000
2000
2500
3200
4000
5000
6300
45
800
1000
1250
1250
1600
1600
2000
2000
2500
3150
4000
5000
6300
50
800
1000
1250
1250
1600
1600
2000
2000
2500
3100
4000
5000
6200
55
800
1000
1200
1250
1600
1600
1900
2000
2500
3000
4000
5000
6000
60
800
1000
1100
1250
1500
1600
1800
2000
2500
2800
4000
5000
5600
70
800
1000
1000
1250
1350
1600
1650
2000
2500
2550
4000
5000
5100
Bus Bar Sizes and Quantities
Maximum Service
Current, Amperes
(40°C Ambient)
800
1000
1250
1600
2000
2500
3200
4000
5000
6300
Circuit Breaker
Frame (MWN- &
MWI-)
08
10
12
16
20
25
32
40
50
63
Recommended
Bus Bar Quantities
and Sizes
(mm)
(2) 5 x 50
(2) 5 x 60
(2) 5 x 80
(2) 5 x 100
(3) 5 x 100
(4) 5 x 100
(3) 10 x 100
(4) 10 x 100
(5) 10 x 100
(6) 10 x 100
(in)
(1) .25 x 3.0
(2) .25 x 2.0
(2) .25 x 3.0
(2) .25 x 3.0
(3) .25 x 3.0
(4) .25 x 3.0
(3) .25 x 6
(4) .25 x 6
(5) .25 x 6
(6) .25 x 6
(T) (5mm)
(60mm)
(W)
Example 1
T = Thickness of Bus Bar
W = Width of Bus Bar
Example 2
Illustration of 2 5mm by 60mm Bus
Bars stacked to carry 800 amperes
For more information visit: www.cutler-hammer.eaton.com
49Application and Installation Information
May 2003
PG01301002E
Altitude Rating Factors
Magnum circuit breakers can be
applied at their full voltage and cur-
rent ratings up to a maximum alti-
tude of 2000 meters above sea level.
When installed at higher altitudes, the
ratings are subject to correction fac-
tors. Short circuit current is not
affected as long as the voltage is
rated in accordance with the table.
Watts Loss Data
Refer to the table for Magnum resis-
tance and watts loss data to be used in
IEC 890 temperature rise calculations.
Altitude
(Meters)
2000
2150
2300
2450
2600
2750
2900
3050
3200
3350
3500
3650
3800
3950
5000
Voltage
Correction
1.000
0.989
0.976
0.963
0.950
0.933
0.917
0.900
0.883
0.867
0.850
0.833
0.817
0.800
0.700
Current
Correction
1.000
0.998
0.995
0.993
0.990
0.987
0.983
0.980
0.977
0.973
0.970
0.967
0.963
0.960
0.940
Altitude Rating Factors Magnum Resistance and Watts Loss Data
Circuit
Breaker
Frame
MWN-408
MWN-410
MWN-412
MWN-508
MWN-510
MWN-512
MWN-516
MWN-520
MWN-608
MWN-610
MWN-612
MWN-616
MWN-620
MWI-408
MWI-608
MWI-808
MWI-C08
MWI-410
MWI-610
MWI-810
MWI-C10
MWI-412
MWI-612
MWI-812
MWI-C12
MWI-616
MWI-816
MWI-C16
MWI-620
MWI-820
MWI-C20
MWI-625
MWI-825
MWI-C25
MWI-632
MWI-832
MWI-C32
MWI-640
MWI-840
MWI-C40
MWI-850
MWI-C50
MWI-863
MWI-C63
DC Resistance
/pole)
Fixed
24
24
24
24
24
24
24
18
18
18
18
18
18
24
15
12
12
15
15
12
12
15
15
12
12
15
12
12
12
12
12
8
8
8
8
8
8
6
6
6
4
4
4
4
DC Resistance
/pole)
Drawout
60
60
60
42
42
42
42
36
36
36
36
36
36
60
33
24
24
33
33
24
24
33
33
24
24
33
24
24
24
24
24
20
20
20
20
20
20
12
12
12
10
10
10
10
AC Watts Loss
(Total 3 Poles)
Fixed
60
95
150
60
95
150
240
280
45
70
110
180
280
60
40
35
30
60
60
50
50
85
90
70
70
150
120
120
190
190
190
200
200
200
320
320
320
380
380
380
400
400
620
620
AC Watts Loss
(Total 3 Poles)
Drawout
150
240
370
110
170
260
420
560
90
140
220
360
560
150
85
70
60
130
130
95
95
185
200
140
140
330
240
240
330
380
380
500
500
500
800
800
800
750
750
750
1000
1000
1550
1550
Estimate based on RAC/RDC = 1.30, total loss at fully rated current.
For more information visit: www.cutler-hammer.eaton.com
Recommended Electrical
Clearances
The following electrical clearance
information is provided as guidance
when installing drawout or fixed circuit
breakers in an enclosure. Refer to
the graphic representations and the
associated dimensional table.
Recommended Enclosure Size
and Ventilation
A graphic of a typical enclosure and
an associated table of dimensions
are provided as guidance for circuit
breaker enclosure design with
respect to the enclosure size and the
required amount of ventilation space.
50 Application and Installation Information
PG01301002E
May 2003
Breaker Enclosure To Insulated To Grounded With Cell Switch
Mounting Dimension Surface Metal Surface or Key Lock
Drawout A0 0 0
B 25 25 25/75
Fixed A 150 250 -
B30 70 -
Electrical Clearance Dimensions (mm)
Recommended Enclosure Electrical Clearances
Do Not Block Vent
Openings in
Drawout Cassette
100
Cell
Switch
(optional)
Key Lock
(optional)
AA
BB
Minimum Enclosure Size and Ventilation
Width Cassette Width + 75 mm
Height 550 mm
Depth 450 mm (Front Compartment)
Ventilation 160 cm2(800-3200A)
320 cm2(4000-6300A)
Recommended Enclosure/Ventilation Dimensions
H
W
D
V
D
W
H
V
V
Top or Rear
Vent Open Area
Rear or Bottom
Vent Open Area
For more information visit: www.cutler-hammer.eaton.com
51Factory Configured Breakers
May 2003
PG01301002E
Factory Configured Circuit
Breakers
Magnum Air Circuit Breakers are
ordered using a 25-digit catalog
numbering system that allows for
maximum options and flexibility.
Circuit breaker configuration is
achieved by using a simple 2-step
process.
Note: If the breaker is drawout
construction and a cassette is
required, the cassette must be
configured separately.
Step 1: Select a 10-Digit Breaker
Catalog Number Prefix.
Choose the breaker prefix from
Tables 5.1, 5.2, 5.3 or 5.4 based
on the following:
Drawout of Fixed Construction
Number of Poles
Continuous Current Rating
Magnum Frame Type
Interrupting Rating
Short Time Withstand
Phasing (Double-wides only)
Catalog Position 20 establishes
if an optional OTS/Bell Alarm Switch
and/or a Mechanical Trip Indicator is
installed per Table 3.14.
Catalog Position 21 establishes
if an optional Padlockable
Pushbutton Cover is installed per
Table 5.15.
Catalog Position 22 establishes
if an optional Key Interlock Provision
is installed per Table 5.16.
Catalog Position 23 establishes
if an optional Latch Check Switch is
installed per Table 5.17 and/or
designates the voltage connection if
an 1150 Trip Unit is supplied.
Catalog Position 24 establishes
if the breaker is shipped alone or in a
cassette with options per Table
5.18.
Catalog Position 25 is reserved
for Cutler-Hammer use per Table
5.19.
Step 2: Select Breaker Catalog
Positions 11 through 25 to
designate factory installed
options as follows:
Catalog Positions 11 and 12
establish the sensor and rating plug
ratings per Tables 5.5, 5.6
and 5.7.
Catalog Positions 13 and 14
establish the trip unit type per Table
5.8.
Catalog Position 15 establishes
if an optional Shunt Trip is installed
per Table 5.9.
Catalog Position 16 establishes
if an optional Motor Operator is
installed per Table 5.10.
Catalog Position 17 establishes
if an optional Spring Release Device
is installed per Table 5.11.
Catalog Position 18 establishes
if an optional Undervoltage Release
or Second Shunt Trip is installed per
Table 5.12.
Catalog Position 19 establishes
if optional Auxiliary Switches are
installed per Table 5.13.
For more information visit: www.cutler-hammer.eaton.com
52 Factory Configured Breakers
PG01301002E
May 2003
Catalog Number Character Positions
1 2 3 4 5 6 7 8 9 10 111213141516171819202122232425
Character Description
Position
3 Circuit Breaker Frame
4 Interrupting/Withstand Rating
5 & 6 Continuous Amperes and Phasing (Facing
Front of Breaker)
7 Poles and Neutral (Facing Front of Breaker)
8 Mounting Configuration and Load Terminals
9 Nameplate Language
10 Used by Cutler-Hammer
11 & 12 Sensor and Rating Plug Rating
13 & 14 Trip Unit and Protection (and External Control
Voltage When Required)
15 Shunt Trip (ST)
Character Description
Position
16 Motor Operator for Charging Closing Spring
17 Spring Release Device (SRD)
18 Undervoltage Release (UVR) or 2nd. Shunt
Trip (ST)
19 Auxiliary Switch
20 OTS/Bell Alarm Switch and/or Mechanical
Indicator
21 Padlock Provisions for Close & Open Buttons
22 Operations Counter and/or Keylock Provisions
23 Latch Check Switch/Trip Unit Line Voltage
Connection for 1150 Trip Unit
24 Shipping Instructions
25 Used by Cutler-Hammer
Figure 5-1 Circuit Breaker 25-character Catalog Number Selections
MW A X
For more information visit: www.cutler-hammer.eaton.com
53Factory Configured Breakers
May 2003
PG01301002E
Table 5.1 Magnum Drawout Mounted Circuit Breakers
(First 10 Character Positions of Catalog Number)
This selection is for a drawout circuit breaker with primary disconnecting contacts (finger clusters).
Continuous
Current Rating
Amps at 40°C
800
1000
1250
800
1000
1250
1600
2000
800
1000
1250
1600
2000
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
4000
5000
6300
Magnum ACB
Frame Type
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Double
Double
Double
Double
Double
Double
Double
Interrupting
Rating (kA) at
690V Icu/Ics
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
85/85
85/85
85/85
85/85
85/85
85/85
85/85
100/85
100/85
100/85
100/85
100/85
100/85
100/85
65/65
85/85
85/85
85/85
100/100
100/100
100/100
Icw Withstand
Rating (kA)
1-Sec/3-Sec
40/--
40/--
40/--
50/--
50/--
50/--
50/--
50/30
65/40
65/40
65/40
65/40
65/40
65/--
65/--
65/--
65/--
65/50
65/50
65/50
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
65/--
85/--
85/--
85/--
100/--
100/--
100/--
3-Pole Catalog
Number
Positions 1-10
MWN4083LEA
MWN4103LEA
MWN4123LEA
MWN5083LEA
MWN5103LEA
MWN5123LEA
MWN5163LEA
MWN5203LEA
MWN6083LEA
MWN6103LEA
MWN6123LEA
MWN6163LEA
MWN6203LEA
MWI6083LEA
MWI6103LEA
MWI6123LEA
MWI6163LEA
MWI6203LEA
MWI6253LEA
MWI6323LEA
MWI8083LEA
MWI8103LEA
MWI8123LEA
MWI8163LEA
MWI8203LEA
MWI8253LEA
MWI8323LEA
MWIC083LEA
MWIC103LEA
MWIC123LEA
MWIC163LEA
MWIC203LEA
MWIC253LEA
MWIC323LEA
MWI64N3LEA
MWI84N3LEA
MWI85N3LEA
MWI86N3LEA
MWIC4N3LEA
MWIC5N3LEA
MWIC6N3LEA
3-Pole
Phasing
(Left to Right)
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
AABBCC
AABBCC
AABBCC
AABBCC
AABBCC
AABBCC
AABBCC
4-Pole Catalog
Number
Positions 1-10
MWN4084LEA
MWN4104LEA
MWN4124LEA
MWN5084LEA
MWN5104LEA
MWN5124LEA
MWN5164LEA
MWN5204LEA
MWN6084LEA
MWN6104LEA
MWN6124LEA
MWN6164LEA
MWN6204LEA
MWI6084LEA
MWI6104LEA
MWI6124LEA
MWI6164LEA
MWI6204LEA
MWI6254LEA
MWI6324LEA
MWI8084LEA
MWI8104LEA
MWI8124LEA
MWI8164LEA
MWI8204LEA
MWI8254LEA
MWI8324LEA
MWIC084LEA
MWIC104LEA
MWIC124LEA
MWIC164LEA
MWIC204LEA
MWIC254LEA
MWIC324LEA
MWI64N4LEA
MWI84N4LEA
MWI85N4LEA
MWI86N4LEA
MWIC4N4LEA
MWIC5N4LEA
MWIC6N4LEA
4-Pole
Phasing
(Left to Right)
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
Narrow Frame Drawout Circuit Breaker
Standard Frame Drawout Circuit Breaker
Double Frame Drawout Circuit Breaker
Magnum air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure
Interrupting ratings shown are also applicable at 380V/415V/440V/500V/690V unless otherwise indicated.
Phasing left to right when facing front of breaker. Neutral is rated 100% kf continuous current.
Icu is 100kA at 440Vac and 85kA at 690Vac. Ics is 85kA at 690Vac and below.
Magnum ACBs carry an IT rating at 440Vac per EN 60947-2 Annex H. Contact Cutler-Hammer for 690Vac IT applications.
For more information visit: www.cutler-hammer.eaton.com
54 Factory Configured Breakers
PG01301002E
May 2003
Table 5.2 Magnum Fixed Mounted Circuit Breakers
(First 10 Character Positions of Catalog Number)
This selection is for a fixed circuit breaker with fixed mounting feet and horizontal terminal pads for bus connections.
Continuous
Current Rating
Amps at 40°C
800
1000
1250
800
1000
1250
1600
2000
800
1000
1250
1600
2000
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
4000
5000
6300
Magnum ACB
Frame Type
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Double
Double
Double
Double
Double
Double
Double
Interrupting
Rating (kA) at
690V Icu/Ics
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
85/85
85/85
85/85
85/85
85/85
85/85
85/85
100/85
100/85
100/85
100/85
100/85
100/85
100/85
65/65
85/85
85/85
85/85
100/100
100/100
100/100
Icw Withstand
Rating (kA)
1-Sec/3-Sec
40/--
40/--
40/--
50/--
50/--
50/--
50/--
50/30
65/40
65/40
65/40
65/40
65/40
65/--
65/--
65/--
65/--
65/50
65/50
65/50
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
85/65
65/--
85/--
85/--
85/--
100/--
100/--
100/--
3-Pole Catalog
Number
Positions 1-10
MWN4083HEA
MWN4103HEA
MWN4123HEA
MWN5083HEA
MWN5103HEA
MWN5123HEA
MWN5163HEA
MWN5203HEA
MWN6083HEA
MWN6103HEA
MWN6123HEA
MWN6163HEA
MWN6203HEA
MWI6083HEA
MWI6103HEA
MWI6123HEA
MWI6163HEA
MWI6203HEA
MWI6253HEA
MWI6323HEA
MWI8083HEA
MWI8103HEA
MWI8123HEA
MWI8163HEA
MWI8203HEA
MWI8253HEA
MWI8323HEA
MWIC083HEA
MWIC103HEA
MWIC123HEA
MWIC163HEA
MWIC203HEA
MWIC253HEA
MWIC323HEA
MWI64N3HEA
MWI84N3HEA
MWI85N3HEA
MWI86N3HEA
MWIC4N3HEA
MWIC5N3HEA
MWIC6N3HEA
3-Pole
Phasing
(Left to Right)
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
AABBCC
AABBCC
AABBCC
AABBCC
AABBCC
AABBCC
AABBCC
4-Pole Catalog
Number
Positions 1-10
MWN4084HEA
MWN4104HEA
MWN4124HEA
MWN5084HEA
MWN5104HEA
MWN5124HEA
MWN5164HEA
MWN5204HEA
MWN6084HEA
MWN6104HEA
MWN6124HEA
MWN6164HEA
MWN6204HEA
MWI6084HEA
MWI6104HEA
MWI6124HEA
MWI6164HEA
MWI6204HEA
MWI6254HEA
MWI6324HEA
MWI8084HEA
MWI8104HEA
MWI8124HEA
MWI8164HEA
MWI8204HEA
MWI8254HEA
MWI8324HEA
MWIC084HEA
MWIC104HEA
MWIC124HEA
MWIC164HEA
MWIC204HEA
MWIC254HEA
MWIC324HEA
MWI64N4HEA
MWI84N4HEA
MWI85N4HEA
MWI86N4HEA
MWIC4N4HEA
MWIC5N4HEA
MWIC6N4HEA
4-Pole
Phasing
(Left to Right)
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NABC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
NNAABBCC
Narrow Frame Fixed Circuit Breaker
Standard Frame Fixed Circuit Breaker
Double Frame Fixed Circuit Breaker
Magnum air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure).
Interrupting ratings shown are also applicable at 380V/415V/440V/500V/690V unless otherwise indicated.
Fixed breakers have (H) horizontal terminals. Vertical adapters (V) are priced separately.
Phasing Left to Right when facing front of circuit breaker - Neutral rated 100% of continuous current
Icu is 100kA at 440Vac and 85kA at 690Vac. Ics is 85kA at 690Vac and below.
Magnum ACBs carry an IT rating at 440Vac per EN 60947-2 Annex H. Contact Cutler-Hammer for 690Vac IT applications.
For more information visit: www.cutler-hammer.eaton.com
55Factory Configured Breakers
May 2003
PG01301002E
Table 5.3 Basic Drawout Mounted Air Circuit Breaker
(Tested to EN 60947-2 Cat B; witnessed and certified with a KEMA-KEUR Mark)
Special Application – 1100 Vac Air Circuit Breakers – Drawout and Fixed Mounting (Tables 5.3 and 5.4)
A Basic Drawout Mounted Air Circuit Breaker includes a manually operated breaker frame (moving portion) only with primary disconnecting contacts
(finger clusters) and one current sensor per phase.
Continuous
Current Rating
Amps at 40°C
3200
Magnum ACB
Frame Type
Standard
Interrupting
Rating (kA) at
690V Icu/Ics
25/25
Icw Withstand
Rating (kA)
1-Sec/3-Sec
--/--
3-Pole Catalog
Number
MWK2323LEA
3-Pole
Phasing
(Left to Right)
ABC
4-Pole Catalog
Number
MWK2324LEA
4-Pole
Phasing
(Left to Right)
NABC
Magnum air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure
Phasing left to right when facing front of breaker. Neutral is rated 100% kf continuous current.
Table 5.4 Basic Fixed Mounted Air Circuit Breaker
(Tested to EN 60947-2 Cat B; witnessed and certified with a KEMA-KEUR Mark)
A Basic Fixed Mounted Air Circuit Breaker includes a manually operated breaker frame only with horizontal rear terminals, one current sensor per phase,
and one secondary terminal block mounting bracket.
Continuous
Current Rating
Amps at 40°C
3200
Magnum ACB
Frame Type
Standard
Interrupting
Rating (kA) at
690V Icu/Ics
25/25
Icw Withstand
Rating (kA)
1-Sec/3-Sec
--/--
3-Pole Catalog
Number
MWK2323HEA
3-Pole
Phasing
(Left to Right)
ABC
4-Pole Catalog
Number
MWK2324HEA
4-Pole
Phasing
(Left to Right)
NABC
Magnum air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure
Phasing left to right when facing front of breaker. Neutral is rated 100% kf continuous current.
For more information visit: www.cutler-hammer.eaton.com
56
PG01301002E
May 2003
Factory Configured Breakers
Tables 5.5, 5.6 and 5.7 Magnum Factory Installed Current Sensors and Rating Plugs Option for Fixed or
Drawout Circuit Breakers (Character Positions 11 and 12 of Catalog Number)
Depending on the circuit breaker frame type, select current sensors and rating plugs from Tables 5.5, 5.6 or 5.7. One current sensor per phase and one
rating plug are included as standard with all fixed and drawout circuit breakers unless a circuit breaker is a non-automatic switch. Select NN for charac-
ter positions 11 and 12 if the circuit breaker is non-automatic (without integral trip unit protection). Select the current sensor and rating plug rating by
circuit breaker frame size. For 3-pole circuit breaker earth fault applications on 3-phase, 4-wire circuits, external neutral mounted current sensors must
be ordered separately.
Table 5.5 Available Current Sensors and Rating Plugs for Narrow Frame
Catalog Number
Positions
11 and 12
NN - None
20
16
13
12
10
08
07
06
04
03
05
02
2000A
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
1600 A
1600
1250
1200
1000
800
630
600
400
300
250
200
1250 A
1250
1200
1000
800
630
600
400
300
250
200
800 A
800
630
600
400
300
250
200
Table 5.6 Available Current Sensors and Rating Plugs for Standard Frame
Catalog Number
Positions
11 and 12
NN - None
32
30
25
20
16
13
12
10
08
07
06
04
03
05
02
3200 A
3200
3000
2500
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
2500 A
2500
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
2000 A
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
1600 A
1600
1250
1200
1000
800
630
600
400
300
250
200
1250 A
1250
1200
1000
800
630
600
400
300
250
200
1000 A
1000
800
630
600
400
300
250
200
Table 5.7 Available Current Sensors and Rating Plugs for Double Frame
Catalog Number
Positions
11 and 12
NN - None
63
50
40
32
25
20
6300 A
6300
5000
4000
3200
5000 A
5000
4000
3200
2500
4000 A
4000
3200
2500
2000
1000 A
1000
800
630
600
400
300
250
200
800 A
800
630
600
400
300
250
200
Non-Automatic Switch
For more information visit: www.cutler-hammer.eaton.com
57
May 2003
PG01301002E
Factory Configured Breakers
Table 5.8 Factory Installed Trip Unit Option for Fixed or Drawout Circuit Breakers
(Character Positions 13 and 14 of Catalog Number)
Catalog Number
Positions
13 and 14
NN
NN
NN
NN
22
52
5W
M2
MW
MT
MU
MV
MJ
MK
ML
ME
MC
MF
CT
CU
CV
CJ
CK
CL
CE
CC
CF
1W
1N
1P
1R
1S
1T
Digitrip RMS
Trip Unit
Non-Automatic
Non-Automatic
Non-Automatic
Non-Automatic
220
520
520i
520M
520Mi
520M
520M
520M
520Mi
520Mi
520Mi
520M
520M
520M
520MC LSI
520MC LSI
520MC LSI
520MCi LSIG
520MCi LSIG
520MCi LSIG
520MC LSIA
520MC LSIA
520MC LSIA
1150i
1150i
1150i
1150i
1150i
1150i
Functions
3-Pole ACB
3-Pole ACB
4-Pole ACB
4-Pole ACB
LI
LSI
LSIG
LSI
LSIG
LSI
LSI
LSI
LSIG
LSIG
LSIG
LSIA
LSIA
LSIA
LSI
LSI
LSI
LSIG
LSIG
LSIG
LSIA
LSIA
LSIA
LSI
LSI
LSI
LSIG & LSIA
LSIG & LSIA
LSIG & LSIA
Trip Unit
Power Supply
Voltage
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
None
None
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
24/48 VDC
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
Available on
Magnum
Frame(s)
Narrow/Standard
Double
Narrow/Standard
Double
Narrow/Standard
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Digitrip 520MC Trip Unit requires PowerNet Software version 3.2 or higher if PowerNet is used
Power Relay Module mounted integral to circuit breaker receives power from an external customer supplied source wired through the
breaker secondary contacts. The external source powers the trips unit digital display (520M, 520MC and 1150), and relays
No Power Relay Module provided for 520M trip unit when this catalogue code is selected. The Digital display powered from current sen-
sorsand the circuit breaker must carry 20% rated sensor current to power digital display.
Digitrip 1150 has programmable relay trip or alarm contacts for trip unit protective and high load functions.
The maximum available instaneous interrupting rating for the Magnum Standard Frame Non-Automatic Switch is 85kA when the breaker
is used with a suitable external overcurrent protective device with instantaneous protection.
Power Relay
Module Alarm or
Trip Contact
None
None
None
None
None
None
None
None
None
High Load Alarm
High Load Alarm
High Load Alarm
Earth Trip
Earth Trip
Earth Trip
Earth Alarm
Earth Alarm
Earth Alarm
High Load Alarm
High Load Alarm
High Load Alarm
Earth Trip
Earth Trip
Earth Trip
Earth Alarm
Earth Alarm
Earth Alarm
Programmable
Programmable
Programmable
Programmable
Programmable
Programmable
Digitrip 220 Trip Unit Digitrip 520i Trip Unit Digitrip 520Mi Trip Unit Digitrip 520MCi Trip Unit Digitrip 1150i Trip Unit
For more information visit: www.cutler-hammer.eaton.com
58
PG01301002E
May 2003
Factory Configured Breakers
Table 5.9 Factory Installed Shunt Trip (ST) Option
for Fixed or Drawout Circuit Breakers (Character
Position 15 of Catalog Number)
Catalog Number
Position 15
N
A
R
C
H
Voltage
(AC: 50/60 Hz)
None
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
Refer applications requiring capacitor trip
devices to Cutler-Hammer
Table 5.10 Factory Installed Motor Operator
Option for Fixed or Drawout Circuit Breakers
(Character Position 16 of Catalog Number)
For electrically operated circuit breakers, select a Motor Operator and
Spring Release Device (SRD) and (if required) a Shunt Trip (ST).
Catalog Number
Position 16
M
N
P
L
K
W
T
Voltage
(AC: 50/60 Hz)
Manual Operated
110 - 125 Vac
220 - 250 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
Table 5.11 Factory Installed Spring Release Device
(SRD) Option for Fixed or Drawout Circuit Breakers
(Character Position 17 of Catalog Number)
Catalog Number
Position 17
N
A
R
C
H
Voltage
(AC: 50/60 Hz)
None
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
Table 5.12 Factory Installed Undervoltage Release
(UVR) or Second Shunt Trip Attachment (STA)
Option for Fixed or Drawout Circuit Breakers
(Character Position 18 of Catalog Number)
Catalog Number
Position 18
N
A
R
C
H
E
F
G
X
J
K
1
2
3
4
Voltage
(AC: 50/60 Hz)
None
110 - 127 Vac
208 - 240 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
32 V dc
380 - 415 Vac
480 Vac
600 Vac
110 - 127 Vac
208 - 250 Vac
24 Vdc
48 Vdc
Refer requests for Time Delay UVRs to Cutler-Hammer.
Digitrip 1150 Trip Units have an integral adjustable time delay undervoltage trip
function from the line voltage.
An external customer supplied panel mounted Time Delay Undervoltage Relay can
also be applied, wired through the breaker secondary contacts to a Shunt Trip
Attachment for Time Delay Undervoltage protection.
Each second Shunt Trip Attachment includes its own cut-off switch.
UVR
Release Type
① ➁ ➂ ➃
None
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Second Shunt Trip
Second Shunt Trip
Second Shunt Trip
Second Shunt Trip
Motor Spring
Charging Cycle
Time (sec)
None
5
5
5
5
5
5
Table 5.13 Factory Installed Auxiliary Switch
Option for Fixed or Drawout Circuit Breakers
(Character Position 19 of Catalog Number)
Catalog Number
Position 19
N
2
4
6
Contact Type
None
2a/2b
4a/4b
6a/6b
Rëfer applications requiring 6a/6b contacts on the Narrow Frame Breaker to Cutler-
Hammer.
Except when a Second Shunt Trip Attachment is selected, which occupies a 2a/2b
contact mounting position.
Comments
4a/4b maximum on Narrow Frame
6a/6b maximum on Double or Standard Frames
Table 5.14 Factory Installed Bell Alarm/OTS Switch
Option for Fixed or Drawout Circuit Breakers
(Character Position 20 of Catalog Number)
Catalog Number
Position 20
E
N
Y
Mechanical
Trip Indicator
No
Yes
Yes
OTS Switch
with 2 Form C Contacts
No
No
Yes
This option is for circuit breakers with trip units only, not available on
Non-Automatic Circuit Switches.
For more information visit: www.cutler-hammer.eaton.com
59
May 2003
PG01301002E
Factory Configured Breakers
Table 5.15 Factory Installed
Padlockable Pushbutton Cover Option for
Fixed or Drawout Circuit Breakers
(Character Position 21 of Catalog Number)
Catalog Number
Position 21
N
M
P
C
H
Description
None
Metal Frame (Open and Close)
Plastic Frame (Open and Close)
Block Close PB Metal Frame
Block Close PB Plastic Frame
Table 5.16 Factory Installed Operations
Counter/Key Interlock Provisions Option for
Fixed or Drawout Circuit Breakers
(Character Position 22 of Catalog Number)
Catalog Number
Position 22
N
K
C
R
A
Y
L
H
Counter Type
No Counter
No Counter
No Counter
No Counter
Operations Counter
Operations Counter
Operations Counter
Operations Counter
Key Interlock provision includes a hole in the front cover with
cap plus provisions hardware kit for customer installation of
customer supplied cylinder lock.
Keylock Provision
No Lock
Kirk Lock
Castell Lock
Ronis Lock
No Lock
Kirk Lock
Castell Lock
Ronis Lock
Table 5.17 Factory Installed Latch Check
Switch/Metering Trip Unit Configuration
Option for Fixed or Drawout Circuit Breakers
(Character Position 23 of Catalog Number)
Catalog Number
Position 23
N
M
L
Y
C
D
Latch Check Switch
(LCS) Connection
None (Default)
None
Latch Check Switch wired to Spring Release
Latch Check Switch wired to Spring Release
Latch Check Switch for External Wiring (1 Form C)
Latch Check Switch for External Wiring (1 Form C)
Metering Trip Unit Line Voltage Connection
(Applicable only when Digitrip RMS 1150 Trip
Unit is selected in Catalog Positions 13 and 14)
Upper Terminal Voltage Connection
Lower Terminal Voltage Connection
Upper Terminal Voltage Connection
Lower Terminal Voltage Connection
Upper Terminal Voltage Connection
Lower Terminal Voltage Connection
The Latch Check Switch monitors the circuit breaker trip latch
and readiness to close.
Form C contact wired through circuit breaker secondary contacts for external use.
Table 5.18 Circuit Breaker and Cassette
Shipping Instructions
(Character Position 24 of Catalog Number)
Configure the drawout cassette and cassette options using Figure 5-2
(Cassette Catalog Number Selections) and its accompanying tables.
Catalog
Number
Position 24
A
C
C
P
P
S
S
W
W
Shipment
Description
Fixed or
Drawout ACB
Alone
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Magnum ACB
Frame Type
All Frames
Narrow
Standard
Narrow
Standard
Narrow
Standard
Narrow
Standard
Shutters
Not
Applicable
No Shutters
No Shutters
No Shutters
No Shutters
Shutters
Shutters
Shutters
Shutters
Pre-Wired
Cassette
Secondary
Terminal
Blocks
Not Wired
Not Wired
Not Wired
Pre-Wired
Pre-Wired
Not Wired
Not Wired
Pre-Wired
Pre-Wired
Table 5.19 Future Use By Cutler-Hammer
(Character Position 25 of Catalog
Catalog Number
Position 25
X
Description
Future Factory
Option
Double-wide and Standard cassettes ship separately from breakers
For more information visit: www.cutler-hammer.eaton.com
60
PG01301002E
May 2003
Factory Configured Drawout
Cassettes
Factory configured cassettes for dra-
wout Magnum Power Circuit
Breakers are ordered using a 15-digit
catalog numbering system. Cassette
configuration is achieved by using a
simple 2-step process.
Step 1: Select a 7-Digit Cassette
Catalog Number Prefix.
Choose the cassette prefix from
Tables 5.20 and 5.21 based on the
following:
Magnum Cassette Type
Number of Poles
Magnum Breaker Frame Type
Continuous Current Rating
Magnum Frame Type
Step 2: Select Cassette Catalog
Positions 8 through 15 to desig-
nate factory installed options as
follows:
Catalog Positions 8 and 9 per
Table 5.22 are reserved for a future
option.
Catalog Position 10 establish-
es if optional shutters are installed
per Table 5.23.
Catalog Positions 11 through
13 per Table 5.24 are reserved for
future options.
Catalog Positions 14 and 15
establishes if the cassette is pre-
wired per per Table 5.25.
Factory Configured Cassettes
Catalog Number Character Positions
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Character Description
Position
1 Cassette Family
2 Future Use
3 & 4 Continuous Amperes
5 Poles
6 Rear Terminals
7 Arc Hood
8 Future Use
Character Description
Position
9 Future Use
10 Shutters
11 Future Use
12 Future Use
13 Future Use
14 Cassette Wiring
15 Cassette Shipping
Figure 5-2 Drawout Cassette 15-character Catalog Number Selections
WNNNNC
Narrow Frame Cassette
(Front and Rear Views)
For more information visit: www.cutler-hammer.eaton.com
61
May 2003
PG01301002E
Factory Configured Cassettes
Table 5.20 Cassettes for Drawout Circuit Breakers
(First 6 Character Positions of Catalog Number)
Cassette standard features include an arc hood, provisions for secondary terminal blocks includ-
ing wiring, and a cell rejection kit. Cassettes may be shipped with the circuit breaker by specifying
breaker Catalog Character Position 24.
Catalog Number
Positions
1 to 6
NN203H
EN203H
EN323H
EN403H
EN503H
NN204H
EN204H
EN324H
EN404H
EN504H
Poles
3 pole
3 pole
3 pole
3 pole
3 pole
4 pole
4 pole
4 pole
4 pole
4 pole
Continuous
Current Rating (A)
at 40°C
800-2000
800-2000
2500-3200
4000
5000-6300
800-2000
800-2000
2500-3200
4000
5000-6300
Table 5.22 Cassette Door Escutcheon and Gasket Kit Option
(Positions 8 and 9 of Catalog Number)
Catalog Number
Positions 8 and 9
DN
XN
Table 5.23 Cassette Shutters Option
(Character Position 10 of Catalog Number)
Shutters can be factory installed or are also available as a field installation kit for
customer installation.
Catalog Number
Position 10
N
S
Description
No Shutters
Shutters Installed
Magnum ACB
Frame Type
All Frames
All Frames
Table 5.24 Future Cassette Option
(Positions 11 to 13 of Catalog Number)
Catalog Number
Position
11 - 13
NNN
Table 5.25 Pre-wired Cassettes Option
(Character Positions 14 and 15 of Catalog Number)
Pre-wired cassettes include wiring and terminal blocks mounted and
wired to secondary contacts ready to receive the circuit breaker.
Catalog Number
Positions
14 and 15
NC
WC
Voltage
(AC: 50/60 Hz)
Unwired
Pre-wired
Magnum
Circuit Breaker
Frame Type
Narrow
Standard
Standard
Double
Double
Narrow
Standard
Standard
Double
Double
Table 5.21 Cassette Arc Hood
(Positions 7 of Catalog Number)
Catalog Number
Position 7
A
K
Factory installed cassette arc hood option.
Description
600 Vac Breakers
1100 Vac Breakers
Door Escutcheon
& Gasket Kit
Included
Not Included
Factory fitted option to ship kit with cassette.
Poles
3 and 4 pole
3 and 4 pole
Continuous
Current Rating (A)
at 40°C
All Ratings
All Ratings
Cassette Type
All Cassettes
Magnum
Breaker Frame
All Frames
All Frames
Continuous
Rating (A)
All
All
For more information visit: www.cutler-hammer.eaton.com
62
PG01301002E
May 2003
Field Option Kits for Cassettes
Table 5.26 Cassette Shutter Field Option Kit
Pre-wired cassettes include wiring and terminal blocks mounted and wired
to secondary contacts ready to receive air circuit breaker.
Magnum
Breaker Frame
Narrow
Standard
Double
Narrow
Standard
Double
Poles
3 pole
3 pole
3 pole
4 pole
4 pole
4 pole
Continuous
Current Rating (A)
800-2000
800-3200
4000-6300
800-2000
800-3200
4000-6300
Catalog Number
MDNSHTR3P
MISHTR332
MISHTR363
MDNSHTR4P
MISHTR432
MISHTR463
Table 5.27 Cassette Cell Switch Field Option Kit
This is a field installable kit for use with drawout cassettes and is for customer installation. The
switch changes position when the circuit breaker is levered to the CONNECT position. The kit
includes the switch, mounting bracket and hardware for customer installation. The switch kit also
includes pre-installed wiring for easy field installation to cassette cell secondary terminal blocks.
Magnum Breaker
Frame and
Cassette Types
All
All
All
All
Catalog Number
MICELLSW1
M4CS
M8CS
M12CS
Description
4 Form C Contacts
4 Form C Contacts
8 Form C Contacts
12 Form C Contacts
Type
Switch Only
Kit with Mounting Bracket
Kit with Mounting Bracket
Kit with Mounting Bracket
Table 5.28 Cassette Cell Lock
Provision Field Option Kit
This is a field installable kit for use with dra-
wout cassettes and is for customer installation.
The kit includes mounting provisions for single
or multi-cylinder Kirk or Castell locks provided
and fitted to the cassette by the customer.
Catalog Number
MCASSPRL
MCASSPRR
Lock
Left Side
Right Side
Table 5.29 Secondary Contact Wiring
Field Option Kit
Description
Secondary Terminal Block Kit
Secondary Terminal Wire Kit
Secondary Terminal Wire Kit
Secondary Terminal Repair Kit
with Extraction Tool
Catalog Number
MSECBK
MSECWR
MKW40
MSECTOOL
Kit Contents
Ouantity 15 6-Point Terminal Blocks with Labels
Quantity 90 Wires for Connecting Secondary Blocks
Quantity 30 Wires 40 Inches Long for Fixed Circuit Breaker Connecting Secondary Blocks
Quantity 12 Wires, Quantity 2 6-point Terminal Blocks, and 1 Amp, Inc. Removal Tool
This is a field installable kit for use in wiring fixed circuit breakers or drawout circuit
breaker cassette secondary contacts or for adding option kits in the field. Each kit can be
used to complete as many as three circuit breakers, depending on the number and type of
accessories required for the the circuit breaker.
Pin Removal Tool can be purchased directly from AMP, Inc. under Part Number 3205183
For more information visit: www.cutler-hammer.eaton.com
63
May 2003
PG01301002E
Field Option Kits for Circuit Breakers
Table 5.30 Shunt Trip (STA)
Field Option Kit
This is a field installable kit for fixed or drawout circuit breakers.
The kit includes a shunt trip attachment (STA) with plug-in
wires, a cut-off switch and instructions. Refer applications
requiring capacitor trip devices to Cutler-Hammer.
Voltage
(AC:50/60Hz)
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
Catalog Number
MST1
MST2
MST3
MST4
Table 5.31 Motor Operator
Field Option Kit (For Charging Closing Spring)
This is a field installable kit for fixed or drawout circuit
breakers. The kit includes a motor operator assembly,
which includes a motor cut-off switch and instructions.
Voltage
(AC:50/60Hz)
110 - 125 Vac
220 - 250 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
Catalog Number
MMOTN
MMOTP
MMOTL
MMOTK
MMOTW
MMOTT
Table 5.32 Spring Release Device (SRD)
Field Option Kit
This is a field installable kit for fixed or drawout circuit
breakers. The kit includes spring release device (SRD)
assembly with plug-in wires and instructions.
Voltage
(AC:50/60Hz)
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
Catalog Number
MSRA
MSRR
MSRC
MSRH
Table 5.34 Auxiliary Switch
Field Option Kit
This is a field installable kit for fixed or drawout circuit
breakers. Note that a maximum of 4a/4b contacts
apply to the Narrow Frame and a maximum of 6a/6b
apply to the Standard and Double Frames.
Switch Type
2a/2b Contacts
Catalog Number
MAUX2
Table 5.35 Undervoltage Release (UVR)
Field Option Kit
This is a field installable kit for fixed or drawout circuit
breakers. The kit includes an undervoltage release
device and instructions.
Voltage
(AC:50/60Hz)
110 - 127 Vac
208 - 240 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
32 Vdc
380 - 415 Vac
480 Vac
600 Vac
Catalog Number
MUVRA
MUVRR
MUVRC
MUVRH
MUVRE
MUVRF
MUVRG
MUVRX
MUVRJ
MUVRK
UVR Release
Type ① ② ➂ ➃
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
On applications requiring Time Delay Undervoltage Protection, refer requests for
Time Delay UVRs to Cutler-Hammer..
Digitrip 1150 Trip Units have an integral adjustable time delay undervoltage trip
function from the line voltage.
An external customer supplied panel mounted Time Delay Undervoltage Relay can
also be applied wired through the breaker secondary contacts to a Shunt Trip
Attachment for Time Delay Undervoltage protection.
Each second Shunt Trip Attachment includes its own cut-off switch.
Table 5.36 Trip Indication Field Option Kits
These are field installable kits for fixed or drawout circuit breakers.
They are for breakers with with trip units only, and not available on
Non-Automatic Breakers.
Contacts
None
2 Form C
2 Form C
Catalog
Number
MDTRIND
MDTRINDBA
MOTS
Table 5.37 Operations Counter
Field Option Kit
This is a field installable kit for fixed or drawout circuit
breakers. It also requires a circuit breaker mechanical
pop-out indicator kit, if the existing circuit breaker
does not have an indicator.
Kit Type
Mechanical Counter
Catalog Number
MCOUNT
Table 5.33 Latch Check Switch Field Option Kit
This is a field installable kit for fixed or drawout circuit breakers includes
LCS assembly 1 Form C contact, plug-in wires and instructions.
Catalog Number
MLSC1
MLSC2
Description
Latch Check Switch for Wiring Internally to Spring Release
Latch Check Switch with 1 Form C Contact for Remote Indication
Trip Indication Kit Description
Mechanical Pop-out Trip Indicator Kit
Bell Alarm/Ots Kit with Mechanical Trip Indicator
Bell Alarm/OTS Contact Kit
Manual Reset only.
For use with breakers that have mechanical pop-out trip indicator option already
installed.
For more information visit: www.cutler-hammer.eaton.com
64
PG01301002E
May 2003
Field Option Kits for Circuit Breakers
Table 5.38 Padlockable Pushbutton Cover
Field Option Kit
This is a field installable kit for fixed or drawout circuit
breakers. Padlocks are not included and must be provided
by customer.
Cover Type
Plastic
Metal
Catalog Number
MCOVH
MCOVC
Table 5.39 Breaker Key Lock Provisions
Field Option Kit
This is a field installable kit for fixed or drawout
circuit breakers. The kit includes mounting
hardware and brackets to mount single cylinder
lock for locking circuit breaker in the Open
position. The cylinder lock and key are not
included and must be supplied bt customer.
Lock Type
Castell
Ronis
Kirk
Catalog Number
MBRLCKC
MBRLCKR
MBRLCKK
Table 5.41 Sensor/Rating Plug
Field Change-out Kit
This is a field installable kit for changing the sensor/rating plug rating
on fixed or drawout circuit breakers. Narrow and Standard Frame kits
include 1 rating plug plus 3 sensors for 3-pole or 4 sensors for 4-pole
circuit breakers. Double Frame kits include 1 rating plug plus 6 sensors
for 3-pole or 8 sensors for 4-pole circuit breakers. The rating plug rat-
ing and the sensor rating in the kit match. The sensor ampere rating
selected cannot exceed the circuit breaker frame and ampere rating.
Note: For 3 pole breaker ground fault applications on 3 phase, 4 wire
circuits, external mounted sensors must be ordered separately.
Magnum Frame
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Double
Double
Double
Double
Double
Double
Double
Sensor Rating
(A)
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
2500
3000
3200
2000
2500
3000
3200
4000
5000
6300
3-Pole
Catalog Number
M3NRG0200
M3NRG0250
M3NRG0300
M3NRG0400
M3NRG0600
M3NRG0630
M3NRG0800
M3NRG1000
M3NRG1200
M3NRG1250
M3NRG1600
M3NRG2000
M3SRG0200
M3SRG0250
M3SRG0300
M3SRG0400
M3SRG0600
M3SRG0630
M3SRG0800
M3SRG1000
M3SRG1200
M3SRG1250
M3SRG1600
M3SRG2000
M3SRG2500
M3SRG3000
M3SRG3200
M3RRG2000
M3SRG2500
M3RRG3000
M3RRG3200
M3SRG4000
M3RRG5000
M3SRG6300
4-Pole
Catalog Number
M4NRG0200
M4NRG0250
M4NRG0300
M4NRG0400
M4NRG0600
M4NRG0630
M4NRG0800
M4NRG1000
M4NRG1200
M4NRG1250
M4NRG1600
M4NRG2000
M4SRG0200
M4SRG0250
M4SRG0300
M4SRG0400
M4SRG0600
M4SRG0630
M4SRG0800
M4SRG1000
M4SRG1200
M4SRG1250
M4SRG1600
M4SRG2000
M4SRG2500
M4SRG3000
M4SRG3200
M4RRG2000
M4RRG2500
M4RRG3000
M4RRG3200
M4SRG4000
M4SRG5000
M4SRG6300
Table 5.40 Neutral Current Sensor
This is a field installable external accessory for use with fixed
or drawout circuit breakers. The fourth sensor is for mount-
ing on enclosure neutral in 3-pole circuit breaker earth fault
applications on 3-phase, 4-wire systems.
Magnum Frame
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Double
Double
Double
Sensor
Rating
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
2500
3000
3150
3200
4000
5000
6300
Sensor Qty.
Required per
3-Pole Breaker
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
Catalog Number
9253C03H01
9253C03H02
9253C03H03
9253C03H04
9253C03H05
9253C03H14
9253C03H06
9253C03H07
9253C03H08
9253C03H15
9253C03H09
9253C03H10
9253C03H11
9253C03H12
9253C03H16
9253C03H13
9253C03H10
9253C03H11
9253C03H13
The cover can be configured to block the Open and Close
Pushbuttons or just the Close Pushbutton.
Use With Customer Supplied
Lock and Key Number
Castell # FGCL4008
Ronis # 1104A
Kirk Lock # KC40---10 & Key KC4
For more information visit: www.cutler-hammer.eaton.com
65
May 2003
PG01301002E
Field Option Kits for Circuit Breakers
Table 5.42 Primary Terminal Adapter Field Option Kits
This field installation kit is for changing fixed circuit breakers or drawout cassettes from hori-
zontal to desired configuration.
Terminal
Adapter
Kit Type
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Magnum
Frame Type
Narrow
Standard
Standard
Standard
Double
Double
Narrow
Standard
Standard
Standard
Double
Double
Narrow
Narrow
Standard
Standard
Double
Double
Narrow
Narrow
Standard
Standard
Double
Double
Breaker
Poles
3
3
3
3
3
3
4
4
4
4
4
4
3
3
3
3
3
3
4
4
4
4
4
4
Continuous
Current
(A)
800 - 2000
800 - 1600
Up to 2000
2500 - 3200
4000
5000 - 6300
800 - 2000
800 - 1600
Up to 2000
2500 - 3200
4000
5000 - 6300
800 - 1250
800 - 2000
800 - 2500
800 - 3200
4000
5000 - 6300
800 - 1250
1600 - 2000
800 - 2500
800 - 3200
4000
5000 - 6300
Interrupting
Rating
(kA)
Up to 65
Up to 65
Up to 100
All
All
All
Up to 65
Up to 65
Up to 100
All
All
All
Up to 65
Up to 65
Up to 65
85 & 100
All
All
Up to 65
Up to 65
Up to 65
85 & 100
All
All
Catalog Number
MVADP320N
MVADP16
MVADP20
MVADP32
MVADP40
MVADP50
MVADP420N
MVADP416
MVADP420
MVADP432
MVADP440
MVADP450
NFC312KT
NFC320KT
SFNTC325
SFNTC332
Contact C-H
Contact C-H
NFC412KT
NFC420KT
SFNTC425
SFNTC432
Contact C-H
Contact C-H
Table 5.43 Mechanical Interlock Configurations
Reference Chart for Mechanical Interlock Kits
Type of
Interlock
Type 2
Type 31
Type 32
Type 33
Number of Breakers
Interlocked
Across 2 Breakers
Across 3 Breakers
Across 3 Breakers
Across 3 Breakers
Description of Interlocks
One Normal Power Supply (A)
One Emergency Power Supply (B)
Two Normal Power Supplies (A and C)
One Emergency Power Supply (B)
Circuit breakers A and C can be closed if B
is open. B can only be closed if A and C are open.
Two Power Supplies (A and C)
One Bus Tie Breaker (B)
One or Two Breakers out of 3 can be
closed at the same time
Three Power Supplies (A, B and C)
Normal or Emergency, only one of which
can be closed at a time
Possible Interlock
Logic
A B
0 0
1 0
0 1
A B C
0 0 0
1 0 0
0 1 0
0 0 1
1 0 1
A B C
0 0 0
1 0 0
0 1 0
0 0 1
1 1 0
0 1 1
1 0 1
A B C
0 0 0
1 0 0
0 1 0
0 0 1
For more information visit: www.cutler-hammer.eaton.com
66
PG01301002E
May 2003
Field Option Kits for Circuit Breakers
Table 5.44 Mechanical Interlock Assembly Kits
This is an external field installation kit for fixed or drawout circuit breakers. Select a Mechanical
Interlock Kit and Rod or Cable Kits (Table 5.43) for complete assembly as indicated.
Configuration
of Interlocked
Breakers
2 Way
2 Way
3 Way
3 Way
3 Way
2 Way
2 Way
3 Way
3 Way
3 Way
Type of Breaker
Fixed
Fixed
Fixed
Fixed
Fixed
Drawout
Drawout
Drawout
Drawout
Drawout
Interlock Kit
Type
Rod Type 2
Cable Type 2
Cable Type 31
Cable Type 32
Cable Type 33
Rod Type 2
Cable Type 2
Cable Type 31
Cable Type 32
Cable Type 33
Catalog Number
of Kit
MI2FR
MI2FC
MI31FC
MI32FC
MI33FC
MI2DR
MI2DC
MI31DC
MI32DC
MI33DC
Comments
Kit also requires 1 Rod Kit
Kit also requires 1 Cable Kit
Kit also requires 2 Cable Kits
Kit also requires 3 Cable Kits
Kit also requires 3 Cable Kits
Kit also requires 1 Rod Kit
Kit also requires 1 Cable Kit
Kit also requires 2 Cable Kits
Kit also requires 3 Cable Kits
Kit also requires 3 Cable Kits
Table 5.45 Rod or Cable Kits
This is an external field installation kit for fixed or drawout circuit
breakers. It is required for the assembly of Mechanical Interlock
Assembly Kits (Table 5.42)
Kit Type
Rod Type
Cable Type
Cable Type
Cable Type
Cable Type
Catalog Number
of Kit
MIR
MIC5
MIC6
MIC8
MIC10
Comments
Includes 2 Rods 910 mm long 3 feet) each
Includes 2 Cables 1520 mm long (5 feet) each
Includes 2 Cables 1830 mm long (6 feet) each
Includes 2 Cables 2440 mm long 8 feet) each
Includes 2 Cables 3050 mm long (10 feet) each
Cassette-Mounted 2-Way Cable
Interlock
For more information visit: www.cutler-hammer.eaton.com
67
May 2003
PG01301002E
Miscellaneous Accessories
Table 5.46 Miscellaneous Accessories
Description
Levering Device
Lifting Yoke (3-pole Narrow Frame)
Lifting Yoke (3-pole Standard Frame)
Lifting Yoke (3-pole Double Frame)
Lifting Yoke (4-pole Narrow Frame)
Lifting Yoke (4-pole Standard Frame)
Lifting Yoke (4-pole Double Frame)
Roll on Floor Lifting Device
Magnum Trip Unit Tester
Triplink Cable
Door Escutcheon and Gasket Kit
IP54 Door Cover Kit
Non-Automatic Circuit Breaker Cover
Cassette Rejection Bracket Kit
Capacitor Unit for Breaker Capacitor Trip
Mmint MODBUS Translator
Digital Relay Accessory Module
Catalog Number
None Required
8651C91G09
8651C91G02
8651C91G05
8651C91G10
8651C91G07
8651C91G08
6727D63H20
MTST1
5720B59G01
MDES
MDESC
MTUNACI
MCELLREJBK
Contact C-H
MMINT
DRAM
Kit Contents/Accessory Function
Special levering device not required. Use 10 mm socket and drive set
Fits 3-pole Narrow Frame Circuit Breaker
Fits 3-pole Standard Frame Circuit Breaker
Fits 3-pole Double Frame Circuit Breaker
Fits 4-pole Narrow Frame Circuit Breaker
Fits 4-pole Standard Frame Circuit Breaker
Fits 4-pole Double Frame Circuit Breaker
Lifts breaker fitted with lofting yoke from above
Hand-Held Tester fpr Digitrip 220, 520, 520M and 520MC Trip Units
Downloads Trip Unit Settings from one Digitrip RMS 1150 Trip Unit to another
Escutcheon, Gasket and Mounting Hardware
IP54 Cover, Gasket and Mounting Hardware
Cover Trip Unit Cavity on Non-Automatic Breakers
Circuit Breaker Cell Rejection Bracket Kit (Cassette Mounting)
Enclosure Mounted AC Capacitor Unit for circuit breaker Capacitor Trip
Translates INCOM for up to 32 Communicating Trip Units to Modbus
Used with Accessory Bus on Digitrip 1150 Trip Unit
Breaker Maintenance and Handling
Breaker Trip Unit Test Devices and Accessories
Miscellaneous Breaker and Enclosure Accessories
Peripheral Devices
For more information visit: www.cutler-hammer.eaton.com
68
PG01301002E
May 2003
Appendix
Engineering Data Reference Chart
Sections
Breaker Instruction
Book
Trip Unit IL
Breaker Accessory
and Field Option Kit
Cassette Accessory
and Field Option Kit
Miscellaneous
Accessories
Renewal Parts Kit
Reference #
2C12060H05
2C13060H03
70C1036H03
70C1037H04
70C1080H02
2C14766H01
2C14761H01
2C14762H01
2C14760H01
2C13769H02
2C13769H01
2C12769H01
2C12769H02
2C12865H01
2A11851H10
2C12895H01
2C13761H01
2C13763H01
2C13760H01
2C13766H01
2C13795H03
2C13820H01
2C14763H01
2C14764H01
2C14765H01
2C12894H01
2C14767H01
2C13764H01
2C12093H01
2C12093H02
2C13768H01
2C13765H01
2C13860H01
2C14691H01
2C14694H01
2C14694H02
2C14696H01
2C12766H01
2C12767H01
2C12768H01
2C12860H01
2C12861H01
2C12862H01
2C12863H01
2C12864H01
2C13790H01
2C14695H01
2C12896H01
2C12896H02
2C12898H01
2C12760H01
2C12761H01
2C12762H01
2C12763H01
2C12764H01
2C12866H01
2C12867H01
2C13762H01
2C12061H02
2C12897H01
2C12899H01
2C13767H01
2C15860H01
Product Description
Magnum DS Fixed/Drawout Power Circuit Breakers (ANSI)
Magnum Fixed/Drawout Power Circuit Breakers (IEC)
Digitrip Models 1150 & 1150i Trip Units (includes 1150P)
Digitrip Models 220, 220+, 520, 520i, 520Mi, 520MC & 520MCi Trip Units
Ground Fault Alarm Power Supply
Breaker Auxiliary Switch Field Option Kit
Breaker Spring Release Field Option Kit
Breaker Shunt Trip Field Option Kit
Breaker Undervoltage Release Field Option Kit
Breaker Motor Operator Field Option Kit (For Narrow, Standard & Double Frame)
Breaker Motor Operator Field Option Kit (For Standard & Double Frame Only)
Latch Check Switch for use with Spring Release Field Option Kit
Latch Check Switch (accessible) Field Option Kit
Charging Handle Replacement Kit
Center Pull Handle Replacement Parts Kit
Pushbutton Cover Field Option Kit
Breaker Kirk Key Interlock Provision Field Option Kit
Breaker Castell Key Interlock Provision Field Option Kit
Breaker Ronis Key Interlock Provision Field Option Kit
Breaker Pop-out Trip Indicator with Switches Field Option Kit
Fixed Breaker Secondary Terminal Mounting Bracket Field Option Kit
Front Mounted Standard Terminal Field Option Kit
800-1600A Vertical Adapter Field Option Kit
2000A Vertical Adapter Field Option Kit
3000-3200A Vertical Adapter Field Option Kit
Door Escutcheon with Gasket Field Option Kit
Breaker Operations Counter Field Option Kit
Non-Auto Breaker Trip Unit Cover Field Option Kit
3 Pole ANSI Cassette Shutters Field Option Kit
4 Pole ANSI Cassette Shutters Field Option Kit
IEC 800-3200A Cassette Shutters Field Option Kit
IEC 4000-6300A Cassette Shutters Field Option Kit
Cassette Universal Bus Adapter Field Option Kit
Cassette Key Interlock Provision Field Option Kit
ANSI Cassette Cell Switch Field Option Kit
IEC Cassette Cell Switch Field Option Kit
Cassette CT Shorting & Jumper Block Field Option Kit
Fixed Breaker 2-Way Cable Interlock Field Option Kit
Fixed Breaker 2-Way Rod Interlock Field Option Kit
Drawout Breaker 2-Way Rod Interlock Field Option Kit
Drawout Breaker 2-Way Cable Interlock Field Option Kit
Drawout Breaker MI31 3-Way Cable Interlock Field Option Kit
Fixed Breaker MI31 3-Way Cable Interlock Field Option Kit
Drawout Breaker MI32 3-Way Cable Interlock Field Option Kit
Fixed Breaker MI32 3-Way Cable Interlock Field Option Kit
Secondary Wiring Kit to 6 Point Termination Block Field Option Kit
6 Point Terminal Block Field Option Kit
Drawout Breaker 1100V Arc Hood Barrier Field Option Kit
Fixed Breaker 1100V Arc Hood Barrier Field Option Kit
Fixed Breaker Arc Hood Barrier Field Option Kit
Breaker Stationary Contact Replacement Kit
Breaker Moving Contact Replacement Kit
Breaker Secondary Disconnect Block Replacement Kit
Breaker Terminal Block Replacement Kit
Breaker Accessory Tray Replacement Kit
Levering Mechanism Assembly Replacement Kit
Levering Door Mechanism Assembly Replacement Kit
Breaker Current Sensor & Rating Plug Replacement Kit
Hatchet Assembly Replacement Parts Kit
Drawout 2500-3200A Breaker Vertical Adapter Replacement Kit
Drawout Breaker Standard/Double Frame Rejection Bracket Replacement Kit
Cassette Standard/Double Frame Rejection Bracket Replacement Kit
Drawout Breaker Narrow Frame Rejection Bracket Replacement Kit
For Use with or Installation of
Installation, Operation and Maintenace
Installation, Operation and Maintenace
2A11799G40 - G44
2A11799G01 - G33
7802C83G01/G02
2A11796
2A11792
2A11791
2A11793
2A11794G41 - G46
2A11794G22 - G35
2C13797G01
2C13797G02
2A10892
2A11851
2C12890
2C12891G01
2C12891G02
2C12891G03
1B93491
2C13794
2A10820
2A11795G01, G11 & G41
2A11795G02, G12 & G42
2A11795G48, G49, G53, G54, G56 G58
2C12893
2A10890
2A11797
2C12998
2C12998
1B93096
1B93098
2A10670
1B93091
1B93090
2C13793
1B93094
2A11857G02, 2A11858G01
2A11856G02, 2A11859G02
2A11856G01, 2A11859G01
2A11857G01, 2A11858
2A11857G03/G07, 2A11858
2A11857G04/G08, 2A11858
2A11857G05, 2A11858
2A11857G06, 2A11858
1B93093
1B93092
2A10800G02
2A10800G12
2C12898
2A10896
2C12761
2A10899
2A10854
2A10891
2A10855
2A10894
2A11798
2A11855
2A11795G48-49 & G53-54
2A11893G01, G02
1B92695G01, G02 & G51
2A11893G92-G94
For more information visit: www.cutler-hammer.eaton.com
69
May 2003
PG01301002E
Appendix
For more information visit: www.cutler-hammer.eaton.com
70
PG01301002E
May 2003
Appendix
For more information visit: www.cutler-hammer.eaton.com
71
May 2003
PG01301002E
Appendix
For more information visit: www.cutler-hammer.eaton.com
72
PG01301002E
May 2003
Appendix
For more information visit: www.cutler-hammer.eaton.com
73
May 2003
PG01301002E
Appendix
For more information visit: www.cutler-hammer.eaton.com
74
PG01301002E
May 2003
Appendix
For more information visit: www.cutler-hammer.eaton.com
75
May 2003
PG01301002E
Appendix
For more information visit: www.cutler-hammer.eaton.com
76
PG01301002E
May 2003
Appendix
For more information visit: www.cutler-hammer.eaton.com
77
May 2003
PG01301002E
Appendix
For more information visit: www.cutler-hammer.eaton.com
78
PG01301002E
May 2003
Appendix
For more information visit: www.cutler-hammer.eaton.com
79
May 2003
PG01301002E
Appendix
For more information visit: www.cutler-hammer.eaton.com
80
PG01301002E
May 2003
Appendix
For more information visit: www.cutler-hammer.eaton.com
81
May 2003
PG01301002E
Appendix
For more information visit: www.cutler-hammer.eaton.com
82
PG01301002E
May 2003
Appendix
Connection Diagram Digitrip 220/520/520i/520M/520Mi/520MC/520MCi (100-3200A)
For more information visit: www.cutler-hammer.eaton.com
83
May 2003
PG01301002E
Appendix
Connection Diagram Digitrip 520/520i/520M/520Mi/520MC/520MCi (5000A ABCABC Phasing)
For more information visit: www.cutler-hammer.eaton.com
84
PG01301002E
May 2003
Appendix
Connection Diagram Digitrip 520/520i/520M/520Mi/520MC/520MCi (5000A AABBCC Phasing)
For more information visit: www.cutler-hammer.eaton.com
85
May 2003
PG01301002E
Appendix
Connection Diagram Digitrip 1150, 1150i (100-3200A)
16. JUMPERING B-3 (NPOW) TO B-7 TERMINAL WILL ELIMINATE
REVERSE POWER CONDITION.
SEE NOTE 16
For more information visit: www.cutler-hammer.eaton.com
86
PG01301002E
May 2003
Appendix
Connection Diagram Digitrip 1150/1150i (5000A ABCABC Phasing)
15. JUMPERING B-3 (NPOW) TO B-7 TERMINAL WILL ELIMINATE
REVERSE POWER CONDITION.
SEE NOTE 15
For more information visit: www.cutler-hammer.eaton.com
87
May 2003
PG01301002E
Appendix
Connection Diagram Digitrip 1150/1150i (5000A AABBCC Phasing)
15. JUMPERING B-3 (NPOW) TO B-7 TERMINAL WILL ELIMINATE
REVERSE POWER CONDITION.
SEE NOTE 15
For more information visit: www.cutler-hammer.eaton.com
88
PG01301002E
May 2003
Appendix
Narrow Frame Cassette Overall Dimensions (3 and 4 pole, 800-2000A)
NOTES: 1. IMPERIAL DIMENSIONMS ARE INCHES ON TOP, METRIC
DIMENSIONS ARE [mm] BOTTOM.
2. ALL DIMENSIONS ARE REFERENCE ONLY.
For more information visit: www.cutler-hammer.eaton.com
89
May 2003
PG01301002E
Appendix
Standard Frame Cassette Overall Dimensions (3 and 4 pole, 800-3200A)
For more information visit: www.cutler-hammer.eaton.com
90
PG01301002E
May 2003
Appendix
Double Wide Frame Cassette Overall Dimensions (3 pole, 4000-6300A)
For more information visit: www.cutler-hammer.eaton.com
91
May 2003
PG01301002E
Appendix
Double Wide Frame Cassette Overall Dimensions (4 pole, 4000-6300A)
For more information visit: www.cutler-hammer.eaton.com
92
PG01301002E
May 2003
Appendix
Narrow Frame Fixed Overall Dimensions (3 and 4 pole, 800-2000A)
For more information visit: www.cutler-hammer.eaton.com
93
May 2003
PG01301002E
Appendix
Standard Frame Fixed Overall Dimensions (3 and 4 pole, 800-1600A)
For more information visit: www.cutler-hammer.eaton.com
94
PG01301002E
May 2003
Appendix
Standard Frame Fixed Overall Dimensions (3 and 4 pole, 2000A)
For more information visit: www.cutler-hammer.eaton.com
95
May 2003
PG01301002E
Appendix
Standard Frame Fixed Overall Dimensions (3 and 4 pole, 3200A)
For more information visit: www.cutler-hammer.eaton.com
96
PG01301002E
May 2003
Appendix
Double Wide Frame Fixed Overall Dimensions (3 and 4 pole, 4000-6300A)
For more information visit: www.cutler-hammer.eaton.com
97
May 2003
PG01301002E
For more information visit: www.cutler-hammer.eaton.com
May 2003
PG01301002E