MW MEAN WELL 120W Single Output Industrial DIN RAIL with PFC Function @ Features : SDR-1 20 series High efficiency 91% and low power dissipation 150% peak load capability Built-in active PFC function, PF>0.93 Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 UL 508 (industrial control equipment) approved EN61000-6-2(EN50082-2) industrial immunity level Built-in DC OK relay contact 100% full load burn-in test 3 years warranty Q G1) e(Q)us S A. FAICBC SPECIFICATION MODEL SDR-120-12 SDR-120-24 SDR-120-48 DC VOLTAGE 12V 24V 48V RATED CURRENT 10A 5A 2.5A CURRENT RANGE 0~10A 0~5A 0~2.5A RATED POWER 120W 120W 120W PEAK CURRENT 15A 7.5A 3.75A PEAK POWER Note.6 180W (3 sec.) OUTPUT | RIPPLE & NOISE (max.) Note.2| 100mVp-p 100mVp-p 120mVp-p VOLTAGE ADJ. RANGE 12~14V 24 ~ 28V 48 ~ 55V VOLTAGE TOLERANCE Note.3) +1.0% +1.0% +1.0% LINE REGULATION +0.5% +0.5% +0.5% LOAD REGULATION +1.0% +1.0% +1.0% SETUP, RISE TIME 1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load HOLD UP TIME (Typ.) 20ms/230VAC 20ms/115VAC at full load VOLTAGE RANGE Note.7 | 88 ~ 264VAC 124 ~ 370VDC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) 0.93/230VAC 0.96/115VAC at full load INPUT EFFICIENCY (Typ.) 89% 91% 90.5% AC CURRENT (Typ.) 1.4A/115VAC 0.7A/230VAC INRUSH CURRENT (Typ.) 35A/115VAC 70A/230VAC LEAKAGE CURRENT <1mA/ 240VAC OVERLOAD Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage >150% rated power, constant current limiting with auto-recovery within 3 seconds and shut down o/p voltage after 3 seconds 14~17V 29 ~ 33V 56 ~ 65V PROTECTION | OVER VOLTAGE Protection type : Shut down o/p voltage, re-power on to recover 95C +5C (TSW) detect on heatsink of power switch EE EU e Protection type : Shut down o/p voltage, recovers automatically after temperature goes down FUNCTION | DC OK REALY CONTACT RATINGS (max.) | 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load WORKING TEMP. -25 ~ +70C (Refer to "Derating Curve") WORKING HUMIDITY 20 ~ 95% RH non-condensing ENVIRONMENT | STORAGE TEMP., HUMIDITY | -40 ~ +85C, 10 ~ 95% RH TEMP. COEFFICIENT +0.03%/C (0 ~ 50C ) VIBRATION Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 SAFETY STANDARDS UI508, TUV EN60950-1, EAC TP TC 004, BSMI CNS14336-1 approved;(meet EN60204-1) WITHSTAND VOLTAGE IIP-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC SAFETY & |ISoLATION RESISTANCE __| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25C/ 70% RH Note 4) EMC EMISSION Compliance to EN55011, EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020, SEMI F47, GL approved MTBF 289.9K hrs min. | MIL-HDBK-217F (25C) OTHERS | DIMENSION 40*125.2*113.5mm (W*H*D) PACKING 0.67Kg; 20pcs/14.4Kg/1.16CUFT NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25C of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6. 3 seconds max., please refer to peak loading curves. 7. Derating may be needed under low input voltage. Please check the derating curve for more details. 8. The ambient temperature derating of 3.5C/1000m with fanless models and of 5C/1000m with fan models for operating altitude higher than 2000m(6500ft) File Name:SDR-120-SPEC 2018-12-14MW 120W Single Output Industrial DIN RAIL with PEC Function SDR-120 series i Mechanical Specification CaseNo.992A _Unit:mm 125.2 TB2 FA RRR RRR Ira . ENEN: RAR CRAR CR ROR 8S R 2 | 2 28 fells 3 Og) Wels Terminal Pin No. Assignment (TB1) Pin No. | Assignment 1 FG | | 2 AC/N wo 3 AC/L CO CO CO CG Co g Terminal Pin No. Assignment (TB2) Pin No. | Assignment ADMISSIBLE DIN-RAIL:T835/7.5 OR TS35/15 1,2 | Relay Contact 3 DC OUTPUT -V 4 DC OUTPUT+V Hi Block Diagram E 3 : + DC OK t o EMI FILTER PFC POWER RECTIFIERS o 4V uP o & SWITCHING 7 & RECTIFIERS CIRCUIT FILTER ov [ 0.C.P. DETECTION FG wv PEC PWM & PFC ex CIRCUIT r CONTROL CONTROL ex O.V.P, @ DC OK Relay Contact Contact Close PSU turns on/ DC OK. Contact Open PSU turns off / DC Fail. Contact Ratings (max.) | 30V/1A resistive load. File Name:SDR-120-SPEC 2018-12-14MW 120W Single Output Industrial DIN RAIL with PFC Function SDR-1 20 series i Peak Loading (1) 120W 100 sec. 3 sec. Hi Derating Curve Others 150 | | 425 For 3 sec. (typ.) 12V | Others 100 | SI C Sash ontinuous | 2 12V 4 607 ] 1 1 1 -25 0 10 20 30 40 50 55 60 70 (VERTICAL) AMBIENT TEMPERATURE (C) (2) 180W 60W 15sec. | 3 sec. Hi Output derating VS input voltage >) 400 a t | 90 4 80 + | 70 | | se 60 7 a = 50; J _l 40 + 4 L 1 L 1 y) 1 L 88 100 410 135 155 230 264 INPUT VOLTAGE (V) 60Hz File Name:SDR-120-SPEC 2018-12-14