Technical Data 2024 Effective December 2015
Supersedes August 2004
BUSSMANN
SERIES
ANL non-time-delay low voltage limiter
Catalog symbol:
• ANL-(amp)
Description:
Non-time-delay low voltage limiter for use in
isolating faults in battery operated systems.
Specications:
Ratings
• Volts 80Vdc or less
• Amps 35-750A
• IR 2700A
Agency information
• UL Recognized, Guide JFHR2, File E56412
• SAE J1171 ignition protected (35-500A)
• RoHS compliant
Catalog numbers (amps)
ANL-35 ANL-150 ANL-350
ANL-40 ANL-175 ANL-400
ANL-50 ANL-200 ANL-500
ANL-60 ANL-225 ANL-600
ANL-80 ANL-250 ANL-675
ANL-100 ANL-275 ANL-750
ANL-125 ANL-300
ANL-130 ANL-325
Dimensions - in (mm):
0.34"
(8.7mm)
0.88"
(22.2mm)
0.88"
(±0.005)
(22.2mm)
0.34"
(±0.005)
(8.7mm)
3.19"
(±0.015)
(81.0mm)
2.44"
(±0.015)
(61.0mm)
Features:
• Element visible through clear window to
easily identify open status
Recommended fuse blocks*:
Description Catalog number
1-pole open stud terminal
block with nylon inserted
locknuts
4164
1-pole open stud terminal
block with standard hex nuts
4164-FR
* Blocks rated to 80Vdc and 800 amps.
Size
• 3.38” long, 09.5” wide, 1.62” tall
Stud centers
• 2.43”
ANL non-time-delay low voltage limiterTechnical Data 2024
Effective December 2015
Eaton and Bussmann are valuable
trademarks of Eaton in the U.S. and other
countries. You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. 2024 — BU-MC15053
December 2015
For Eatons Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Follow us on social media to get the
latest product and support information.
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any
technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Time-current curves – average melt:
10,000
10
100
1000
CURRENT IN AMPS
100
10
1
0.1
0.01
TIME IN SECONDS
AMP RATING
50
35
80
100
130 150
200
225 275
325 350
400
500