1Power Protection and Conditioning
Superior voltage regulation of ±1% sets the CVS series apart
from other power conditioning technologies on the market.
Extremely tight regulation is accomplished by SolaHD’s fer-
roresonant transformer technology. The CVS recreates a well
regulated sinusoidal waveform that is well isolated from input
disturbances including:
Impulses Swells
Brownouts Sags
Severe waveform distortion
No other power conditioning technology provides as
complete a solution against these power quality
disturbances. The CVS series is ideal for applications
where even a small change in voltage level can lead to
unscheduled downtime, misoperation, incorrect data or
scrapped production.
Applications
Industrial automation and control equipment PLCs
Analytical laboratory and factory automating
equipment
• Photo processing equipment
Sound/recording systems
Photographic enlargers
Broadcast equipment
Features
Superior voltage regulation of ±1%
Surge protection tested to ANSI/IEEE C62.41,
Class A & B waveform
Harmonic ltering
Selection Tables: Single Phase
Group 1 – CVS Series, 60 Hz
CVS Hardwired Series – Constant Voltage Transformers
* This unit is Listed only.
Hardwired
Acts as a step-up/step-down transformer
Galvanic isolation provides exceptional
circuit protection
25 year typical mean time between failure
No maintenance required
Certifications and Compliances
Listed
- UL 1012
- CSA C22.2 No. 66
• RoHS Compliant
Related Products
On-line UPS (S4K Industrial)
Surge Protection
Three Phase Power Conditioners
Active Tracking® Filters
VA Catalog
Number Voltage Input Voltage Output Height
in (mm)
Width
in (mm)
Depth
in (mm)
Ship Weight
lbs (kg)
Design
Style
Elec
Conn
30 23-13-030-2 120 120 7.00 (177.8) 4.00 (101.6) 5.00 (127.0) 9.0 (4.08) 1 J
60 23-13-060-2 120 120 7.00 (177.8) 4.00 (101.6) 5.00 (127.0) 9.0 (4.08) 1 J
120 23-22-112-2 120, 240 120 8.00 (203.2) 4.00 (101.6) 5.00 (127.0) 13.0 (5.90) 1 J
250 23-23-125-8 120, 240, 480 120 11.00 (279.4) 6.00 (152.4) 8.00 (203.2) 29.0 (13.15) 1 G
500 23-23-150-8 120, 208, 240, 480 120, 240 13.00 (330.2) 9.00 (228.6) 7.00 (177.8) 42.0 (19.05) 1 H
1000 23-23-210-8 120, 208, 240, 480 120, 240 17.00 (431.8) 9.00 (228.6) 7.00 (177.8) 65.0 (29.48) 1 H
2000 23-23-220-8 120, 208, 240, 480 120, 240 18.00 (457.2) 13.00 (330.2) 10.00 (254.0) 111.0 (50.35) 1 H
3000 23-23-230-8 120, 208, 240, 480 120, 240 19.00 (482.6) 13.00 (330.2) 10.00 (254.0) 142.0 (64.41) 1 H
5000 23-23-250-8 120, 208, 240, 480 120, 240 28.00 (711.2) 13.00 (330.2) 10.00 (254.0) 222.0 (100.70) 1 H
7500 * 23-28-275-6 240, 480 120, 240 27.00 (685.8) 25.00 (635.0) 9.00 (228.6) 365.0 (165.56) 2 J
E47379
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
43
1
Power Protection and Conditioning
Design Styles (CVS and MCR Hardwired)
Style 1 Style 2 Style 3
Specifications
Parameter Condition Value
Input
Voltage
Continuous at full load
(lower input voltage possible at lighter load) +10% to -20% of nominal
For temporary surge or sags +20% to -35% of nominal
Current 1at Full Load & 80% of nominal input voltage Iin (VA/.87)/(Vin x 80%)
Frequency See Operating Characteristics section for details. 60 Hz
Output 2
Line Regulation Vin >80% and <110% of nominal ±1%
Overload Protection At Nominal Input Voltage Current limited at 1.65 times
rated current
Output Harmonic Distortion At Full Load within Input Range 3% total RMS content
Noise Attenuation -Common Mode
-Transverse Mode
40 dB
40 dB
General
Efficiency At Full Load Up to 92%
Storage Temperature Humidity <95% non-condensing -20° to 80°C
Operating Temperature Humidity <95% non-condensing -20° to 50°C
Audible Noise Full Resistive Noise 32 dBA to 65 dBA
Warranty 10 year limited warranty
These styles are single phase only.
Notes:
1 - Consult user manual for fuse sizing.
2 - It is recommended that the unit run at a minimum of 40-50% load.
See the Operating Characteristics section for more details.