SPECIFICATION
30W Ultra Slim Step Shape DIN Rail HDR-30 series
HDR-30-5 HDR-30-12 HDR-30-15 HDR-30-24
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
SAFETY STANDARDS
WORKING HUMIDITY
WORKING TEMP.
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
OVERLOAD
OVER VOLTAGE
5V 12V 15V 24V
3A 2A 2A 1.5A
0 ~ 3A 0 ~ 2A 0 ~ 2A 0 ~ 1.5A
15W 24W 30W 36W
80mVp-p 120mVp-p 120mVp-p 150mVp-p
±2.0% ±1.0% ±1.0% ±1.0%
±1.0% ±1.0% ±1.0% ±1.0%
±1.0% ±1.0% ±1.0% ±1.0%
500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load
30ms/230VAC 12ms/115VAC at full load
47 ~ 63Hz
82% 88% 89% 89%
0.88A/115VAC 0.48A/230VAC
COLD START 25A/115VAC 45A/230VAC
105 ~ 160% rated output power
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 ) RH non-condensing
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
968.1K hrs min. MIL-HDBK-217F (25 )℃
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:4KVAC
I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH℃
HDR-30-48
48V
0.75A
0 ~ 0.75A
36W
240mVp-p
±1.0%
±1.0%
±1.0%
90%
13.5 ~ 18V 21.6 ~ 29V10.8 ~ 1 . V3 8
4. ~ . V55 5 43.2 ~ 55.2V
5 75 7.5. ~ V 1 ~ 1 V5 8 18.8 ~ 22.5V 30 ~ 36V 5 . ~ 6 . V7 6 7 2
85 ~ 2 VAC ( ) 120 ~ 3 VDC ( )64 277VAC operational 70 390VDC operational
OPERATING ALTITUDE 2000 meters
UL62368-1, U 508, TUV EN61558-2-16 IEC62368-1, , BSMI CNS14336-1 aL , pproved; Design refer to TUV EN62368-1EAC TP TC 004
EN55024, EN55035, EN61000-6-2, EN61204-3
EMC IMMUNITY
EMC EMISSION
Parameter
Conducted
Radiated
Harmonic Current
Voltage Flicker
Standard
EN55032(CISPR32), CNS13438
EN61000-3-2
Test Level / Note
Class B
-------
EN61000-3-3
Class B
Class A
Parameter
ESD
Radiated Susceptibility
EFT/Burest
Surge
Standard
EN61000-4-2
Test Level /Note
Level 3, 8KV air; Level 2, 4KV contact, criteria A
Level 4,2KV/L-N, criteria A
Conducted
Magnetic Field
EN61000-4-3
EN61000-4-4
EN61000-4-6
EN61000-4-5
EN61000-4-8
EN61000-4-11
Voltage Dips and interruptions
Level 3, criteria A
Level 3, criteria A
Level 3, criteria A
Level 4, criteria A
EN55032(CISPR32), CNS13438
DIMENSIONOTHERS
NOTE
PACKING
35*90*54.5mm (W*H*D)
0.12Kg;96pcs/12.5Kg/1.04CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 f & 47 f parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC
directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
>.95% dip 0 5 periods, 30% dip 25 periods,
95% interruptions 250 periods>
μμ
OVER VOLTAGE CATEGORY According to E 61558, EN50178,EN60664-1, EN62477-1 altitude up to 2000Ⅲ;;N meters
File Name:HDR-30-SPEC 2019-11-25
H , recovers automatically after fault condition is removediccup mode when output voltage 50<%
Constant current limiting recovers automatically after fault condition is removed within 50% ~100% rated output voltage,