Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series 1 of 8 HPS3000 Series 3000 Watts Distributed Power Bulk Front-End Single Output Special Features * 3000 W output power * 40 W/cu-in * Optional customer provided air * 1U x 3U form factor * N+1 Redundant * Hot-swap * Internal OR-ing * 5 V housekeeping * High efficiency 89% @ 200 Vac, 100% load * Variable speed "smart fans" * Two year warranty Compliance * POE Isolation * EMI Class B - EN55022, Level "A" @ 230 Vac * EN61000 Immunity Safety * UL/cUL * CSA * China * Nemko * CB Report * CSA 22.2 60950 60950 CCC TUV 60950 Electrical Specifications Input Input range (operating): Frequency: 180 - 264 Vac 90 - 140 Vac 200 Vac 110 Vac 47 to 63 Hz Input fusing: Inrush current: Internal 25 A fuses 40 A peak Both lines fused Either hot or cold start Power factor: 0.97 typical Meets EN61000-3-2 Harmonics: Meets IEC 1000-3-2 requirements @ 50% load Input current: 19 A max input current Holdup time: 10 ms minimum At full rated load Leakage current: 1.4 mA At 240 Vac Power line transient: MOV directly after the fuse Input range (nominal): Input through Card Edge Connection on same end as DC output Embedded Power for Business-Critical Continuity 230V ac E ffic ienc y 230 Vac Efficiency Rev. 02.22.11_81 HPS3000 Series 2 of 8 100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00 10 20 30 40 50 60 70 80 90 100 % o f T o tal Ou tp u t Po w e r Output Output rating Set point Total regulation range Rated load Minimum load Output noise Output voltage overshoot Transient response 48 V @ 62.0 A 5 Vsb @ 3.0 A 48 V @ 29.4 A 5V @ 3 A 48 V 48 V 5% 5 Vsb 4% 3000 W maximum @ 200 Vac Input 1500 W maximum @ 110 Vac Input 180 - 264 Vac 48 V @ 0.0 A 5 Vsb @ 0.0 A 480 mV max P-P 100 mV max P-P No loss of regulation 5% maximum 5% maximum deviation Max units in parallel Short circuit protection Output isolation Forced load sharing Over current protection (OCP) Up to 4 120% - 130% of rated output Per POE specs Within 10% of all shared outputs 120% to 130% 110% to 140% Over voltage protection (OVP) 110% to 133% 110% to 125% Over temperature protection 10 - 15 deg C above safe operating area 90 - 140 Vac Programmable 96-117% through I2C serial bus Line/load/transient when measured at output connection No derating over operating temp range 48 V output 5 Vsb output Measured with a 0.1F Ceramic and 10 F Tantalum capacitor on any input Nominal Voltage Setting 50% load step @ 1 A/us Step load valid between 10% to 100% of output rating. Total power in 1U 19" rack is 12 KW Output to return >2000 Vac Digital sharing control 48 V output 5 Vsb output 48 V output 5 Vsb output Both PFC and output converter monitored 5 Vsb will operate under overtemperature condition. Built in hysteresis Environmental Specifications Vibration/Shock: Non-operational 5G Sine sweep from 5 Hz to 500 Hz, dwelling at resonant frequencies for 1 hour each Operating temperature: Storage Temperature: Cooling Operating Relative Humidity: Storage Relative Humidity: -10 to +40 C -40 to +85 C External fans with Fan Fail and Fan Speed control 5% to 95% non-condensing 5% to 95% non-condensing Operating Altitude Storage Altitude: RoHS Compliant: Up to 10,000 feet above sea level Up to 30,000 feet above sea level Yes Embedded Power for Business-Critical Continuity Module Information (All units in mm) Rev. 02.22.11_81 HPS3000 Series 3 of 8 Embedded Power for Business-Critical Continuity Pin Assignments Bottom Top Pin Pin 1 2 3 4 5 6 AC LINE AC LINE n.c. AC NEUTRAL AC NEUTRAL n.c. 64 63 62 61 60 59 AC LINE AC LINE n.c. AC NEUTRAL AC NEUTRAL n.c. 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 n.c. n.c. +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN n.c. V_STBY Reserved PRESENT# DCOK/PWOK# SDA HVCC PSON# #ALERT ISHARE 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 n.c. n.c. +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc out +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN +48 Vdc RTN n.c. SYS_GND Reserved ACOK# SMBUS_ALERT_OUT SCL A2 PSKILL A1 A0 Rev. 02.22.11_81 HPS3000 Series 4 of 8 Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series 5 of 8 Timing Diagram AC On AC Input AC On T PWOK_Off_ T Vout_Holdup Main Vout T PWOK_Off_ T AC_On_Delay T PWOK_Off_ T PWOK_On T PWOK_Off_ T PWOK_Off PWOK T PWOK_Delay T PWOK_On T PWOK_On T PSON_PWOK T sb_On 3.3 V Vout T PSON_On_Delay T SB_Vout PS_ON T ACOK_Delay AC_OK AC Input ON / OFF Cycle PSON ON / OFF Cycle Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series 6 of 8 Timing Signal Definitions Turn ON/OFF Timing Item Tvout_rise Tsb_on_delay Description 48 V Output rise time Delay from AC being applied to 5 Vsb being within regulation. Tac_on_delay Delay from AC being applied to all output voltages being within regulation. Tvout_holdup Time all output voltages, including 5 Vsb, stay within regulation after loss of AC. Delay from loss of AC to de-assertion of PWOK 10 msec 5 msec Delay from PSON# active to output voltages within regulation limits. Delay from PSON# de-active to PWOK being de-asserted. Delay from loss of AC input to de-assertion of ACOK#. 5 Tpwok_holdup Tpson_on_delay Tpson_pwok Tacok_delay Tpwok_on Tpwok_off Tpwok_low Tsb_vout Min 5 Max 300 1500 Units msec msec 2000 msec 400 msec 50 msec msec 100 1000 msec 1 1000 msec 10 Delay from output voltages within regulation limits to PWOK asserted at turn on. Delay from PWOK de-asserted to 48 V dropping out of regulation limits. Duration of PWOK being in the de-asserted state during an off/on cycle using AC or the PSON# signal. Delay from 5 Vsb being in regulation to 48 V being in regulation at AC turn on. 100 50 msec 2000 msec Signals and Controls - All Models PSON # The PSON# signal is required to remotely turn on/off the power supply. PSON# is an active low signal that turns on the 48 V power rail. When this signal is not pulled low by the system, or left open, the 48 V output turns off. The 5 Vsb output remains on. This signal is pulled to a standby voltage by a pull-up resistor internal to the power supply. The power supply fan(s) shall operate at the lowest speed. PSON# Signal Characteristic Signal Type PSON# = Low Accepts an open collector/drain input from the system. Pulled-up to the 5 Vsb located in power supply. ON PSON# = Open OFF MIN Logic level low (power supply ON) Logic level high (power supply OFF) Source current, Vpson = low Power up delay: Tpson_on_delay MAX 0V 0.4 V 2.40 V 3.40 V -- 4 mA 5 msec 400 msec Embedded Power for Business-Critical Continuity Rev. 02.22.11_81 HPS3000 Series 7 of 8 PWOK# (Power Good) PWOK# is a power good signal and will be pulled LOW by the power supply to indicate that both the outputs are above the regulation limits of the power supply. When any output voltage falls below regulation limits or when AC power has been removed for a time sufficiently long so that power supply operation is no longer guaranteed, PWOK will be de-asserted to a HIGH state. The start of the PWOK# delay time shall be inhibited as long as the 48 V output is in current limit or the 5 Vsb output is below the regulation limit. PSON# Signal Characteristic Signal Type PWOK = High Open collector/drain output from power supply. Pullup to 5 Vsb external to the power supply. ON PWOK = LOW OFF Logic level low voltage, Isink=4mA Logic level high voltage, Isource=200A MIN MAX 0V 0.8 V 2.0 V 4.80 V Sink current, PWOK = low 4 mA Source current, PWOK = high 2 mA PWOK delay: Tpwok on 100 msec 1000 msec PWOK rise and fall time 100 sec Power down delay: Tpwok off 1 msec 1000 msec Power Supply Present Indicator (PRESENT#) The PRESENT# signal is primarily used to provide a mechanism by which the host system can sense the number of power supplies physically present (operational or not). This pin is connected to ground in the power supply. AC INPUT Present Indicator (ACOK#) The AC OK# signal is used to indicate presence of AC input to the power supply. This signal shall be connected to 5 Vsb through a resistor on the host system side. A logic "Low" level on this signal shall indicate AC input to the power supply is present. A Logic "High" on this signal shall indicate a loss of AC input to the power supply. Signal Type PRESENT# = Low Table 12 ACOK# Signal Characteristics Pull-up to 5 Vsb through a resistor in the host system. Present PRESENT# = High Not present MIN MAX Logic level low voltage, Ising=4mA 0V 0.8 V Logic level high voltage, Isink=50A 2.0 V 4.80 V Sink current, PRESENT# = Low 4 mA Source current, PRESENT# = High 50 A Embedded Power for Business-Critical Continuity Americas LED INDICATORS There will be a green POWER LED (PWR) to indicate that AC is applied to the PSU and standby voltage is available when blinking. This same LED should go solid when the 48 V output is enabled and operational. Rev. 02.22.11_81 HPS3000 Series 8 of 8 5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698 Europe (UK) There will be an Amber Power Supply Fail LED (FAIL) to indicate that the power Waterfront Business Park supply has failed and a replacement of the unit is necessary. Faults including Merry Hill, Dudley UVP, OVP, OTP, or Fan Fail when PSON# is asserted "Logic Low" shall cause the West Midlands, DY5 1LX Kingdom amber LED to turn on. The LED can be turned off by recycling PSON# signal or United Telephone: +44 (0) 1384 842 211 by an AC power interruption more than 1 second. The LED shall be off when Facsimile: +44 (0) 1384 843 355 PSON# is not asserted "Logic Low". Refer to table 13 for conditions of the LED's: Asia (HK) Table 13 LED Indicators Power LED (GREEN) OFF Power Supply Condition No AC power to PSU AC present / Standby Output On Fail LED (AMBER) OFF Blinking OFF Power supply 48 V output ON and OK ON OFF Power supply failure (includes overvoltage, overtemperature) Current limit OFF ON ON Blinking MTBF The power supply has a minimum MTBF of 300K hours using the Bell core 332, issue 6 specification @ 25 C and 40 C, ambient, at full load. With the power supply installed in a system in a 25 C ambient environment and operating at full load, capacitor life shall be 10 years, minimum for ALL electrolytic capacitors contained within this power supply. The power supply shall demonstrate a MTBF level of > 500,000 hours. Quality Assurance Full QAV testing shall be conducted in accordance with Emerson Network Power Standards with reports available upon request. Warranty Emerson Network Power shall warrant the power supply to be free of defects in materials and workmanship for a minimum period of two years from the date of shipment, when operated within specifications. The warranty shall be fully transferable to the end owner of the equipment powered by the supply. Ordering Information Model Number Main Output HPS3000-9 48 Vdc Main Output Current 62.0 A Standby Output Standby Current 5.0 V 3.0 A 14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888 For global contact, visit: www.Emerson.com/ EmbeddedPower techsupport.embeddedpower@ emerson.com While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. (c)2011 Emerson Electric Co.