https://www.phoenixcontact.com/us/products/2861988
07/21/2018Page1/5
Inline terminal-IB IL 24 DO 4-2MBD-PAC-2861988
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline, Digital output terminal, Digital outputs:4, 24 V DC, 500 mA, connection method:3-wire, transmission
speed in the local bus:2 Mbps, degree of protection:IP20, including Inline connector and labeling field
Product Description
The terminal is designed for use within an Inline station.
It is used to output digital signals.
Why buy this product
4 digital outputs
Connection of actuators in 2 and 3-wire technology
Nominal current per output: 500mA
Total current of the terminal: 2A
Short-circuit-proof and overload-protected outputs
Diagnostic and status indicators
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4017918974633
Weight per Piece (excluding packing) 100.000 g
Custom tariff number 85389091
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
https://www.phoenixcontact.com/us/products/2861988
07/21/2018Page2/5
Inline terminal-IB IL 24 DO 4-2MBD-PAC-2861988
Technical data
Dimensions
Width 12.2 mm
Height 140.5 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
Ambient conditions
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
General
Mounting type DIN rail
Net weight 66 g
Note on weight specifications with connector
Operating mode Process data operation with 4 bits
Diagnostics messages Short-circuit / overload of the digital outputs Error message in the
diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Interfaces
Designation Inline local bus
No. of channels 2
Connection method Inline data jumper
Transmission speed 2 Mbps
Inline potentials
Designation Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current consumption max. 65 mA
Power consumption max. 0.49 W
Designation Segment circuit supply (US)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption max. 2 A
Digital outputs
Output name Digital outputs
https://www.phoenixcontact.com/us/products/2861988
07/21/2018Page3/5
Inline terminal-IB IL 24 DO 4-2MBD-PAC-2861988
Technical data
Digital outputs
Connection method Spring-cage connection
Connection technology 3-wire
Number of outputs 4
Type of protection Overload protection, short-circuit protection of outputs
Output voltage 24 V DC (US - 1 V)
Nominal output voltage 24 V DC (voltage difference at Inom ≤ 1 V)
Maximum output current per channel 500 mA
Maximum output current per module 2 A
Nominal load, inductive 12 VA (1.2 H, 50 Ω)
Nominal load, lamp 12 W
Nominal load, ohmic 12 W (48 Ω)
Electrical isolation
Test section 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min.
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.
7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 500
min.
Standards and Regulations
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Classifications
eCl@ss
eCl@ss 4.0 27250302
eCl@ss 4.1 27250302
eCl@ss 5.0 27250302
eCl@ss 7.0 27242604
eCl@ss 8.0 27242604
eCl@ss 9.0 27242604
ETIM
ETIM 2.0 EC001430
ETIM 3.0 EC001599
ETIM 4.0 EC001599
https://www.phoenixcontact.com/us/products/2861988
07/21/2018Page4/5
Inline terminal-IB IL 24 DO 4-2MBD-PAC-2861988
Classifications
ETIM
ETIM 5.0 EC001599
ETIM 6.0 EC001599
UNSPSC
UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 43172015
UNSPSC 12.01 43201404
UNSPSC 13.2 32151602
Approvals
Approvals
Approvals
UL Listed / cUL Listed / EAC / cULus Listed
Ex Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
EAC EAC-Zulassung
cULus Listed
https://www.phoenixcontact.com/us/products/2861988
07/21/2018Page5/5
Inline terminal-IB IL 24 DO 4-2MBD-PAC-2861988
Accessories
Accessories
Labeling panel
Labeling field-IB IL FIELD 2-2727501
Labeling field, width: 12.2 mm
Plug
Inline connector-IB IL SCN-12-OCP-2727624
Connector, colored identification, for digital 4, or 16-channel Inline output terminal blocks
Inline connector-IB IL SCN-12-2726340
Connector, for digital 4 or 16-channel Inline terminals
Terminal marking
Insert strip-ESL 62X10-0809492
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems: Laser printer, mounting type: insert,
lettering field size: 62 x 10 mm
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com