DUC01, PUC01
Mode of Operation
DUC01 and PUC01 monitor
both AC and DC
over+under, over+over or
under+under voltage.
Example 1
(no contact input -
under+over voltage - 2 x
SPDT relays (1 x SPDT for
PUC01))
DUC01: One relay operates
when the voltage drops
below the under voltage set
point for more than the
respective delay time. It
releases when the voltage
exceeds the set level plus
the set hysteresis. The other
relay operates when the
voltage exceeds the over
voltage set point for more
than the respective delay
time. It releases when the
voltage drops below the set
level minus hysteresis (the
hysteresis is the same for
both set levels).
PUC01: The relay operates
when the voltage drops
below the under voltage set
level for more than the
respective set delay time or
when it exceeds the over
voltage set level for more
than the respective set delay
time. The relay releases
when the voltage exceeds
the under voltage set level
plus hysteresis and it drops
below the over voltage set
level minus hysteresis (the
hysteresis is the same for
both set levels).
Example 2
(latch enabled active -
under+ under voltage - 2 x
SPDT relays (1 x SPDT for
PUC01))
DUC01: Each relay operates
and latches when the volt-
age drops below the respec-
tive set level for more than
the respective delay time.
Provided that the voltage
has exceeded the respective
set level (see hysteresis),
each relay releases when the
contact input’sconnection is
interrupted.
PUC01: The relay operates
when the voltage drops
below the higher set level for
more than the respective
delay time. Provided that the
voltage has exceeded the
respective set level plus hys-
teresis, the relay releases
when the contact input is
opened.
Example 3
(inhibit enable active - over+
over voltage - DPDT relay
(1 x SPDT for PUC01))
Provided that the contact
input is opened, the relay
operates when the voltage
exceeds the lower set level
for more than the respective
delay time. It releases when
the voltage drops below the
lower set level (see hystere-
sis) or when the contact
input’spins areconnected.
Note:
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay(s) activation.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
A1, A2 or A3, A2 (DUC01)
2, 10 or 11, 10 (PUC01)
D48: 24 to 48 VAC ± 15%
45to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage DC supply AC supply
Supply to input 2 kV 4 kV
Supply to output 4 kV 4 kV
Input to output 4 kV 4 kV
Rated operational power
AC 5 VA
DC 3 W
Supply Specifications
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON 1 or 2 x LED, yellow
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 3 (DUC01), 2 (PUC01)
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions DUC01 45 x 80 x 99.5 mm
PUC01 36 x 80 x 94 mm
Material PA66 or Noryl
Weight Approx. 250 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Product standard EN 60255-6
Approvals UL, CSA
CE Marking L.V. Directive 2006/95/EC
EMC Directive 2004/108/EC
EMC
Immunity According to EN 60255-26
According to EN 61000-6-2
Emissions According to EN 60255-26
According to EN 61000-6-3
General Specifications (cont.)
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
AlarmON delay <100 ms
Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
General Specifications