1
Power entry modules without line filter DG11
https://www.schurter.com /PG05
Connectors
IEC Appliance Inlet C14 or C18 with Circuit Breaker TA35 2-pole
Screw-on with IP67 and TA35 in white with black
printed symbols
Screw-on with IP67 Snap-in IP40 with TA35 red illuminated and em-
bossed symbols
See below:
Approvals and Compliances
C14
70° C
C18
70° C
Description
- Panel mount :
Screw-on version from front or rear side, snap-in version from front
side
- 2 Functions :
Appliance Inlet , protection class I or II , Circuit breaker type TA35
, 2-pole
- Pre-wired coupling
- V-Lock notch standard
- Quick connect terminal 6.3 x 0.8 mm
Unique Selling Proposition
- Variant tested for IP67 into the appliance
- Various mounting options
- Recessed rocker prevents accidental manipulation
- Compatible with V-Lock cord retention
Characteristics
- Connector and circuit breaker are prewired
- Circuit Breaker non-illuminated or illuminated
- Suitable for use in equipment according to IEC/UL 60950
Other versions on request
- Version without pre-wiring from inlet to circuit breaker
- Protection class II, 70°C
- Variants in white
References
Substitute for type 6135
Component: circuit breakers TA35 Rocker 2Pole
Weblinks
pdf data sheet, html datasheet, General Product Information, Distributor-
Stock-Check, Accessories, Detailed request for product, Landing Page
Technical Data
Ratings IEC 10 A / 250 VAC; 50 Hz
Ratings UL/CSA 15 A / 250 VAC; 60 Hz
Dielectric Strength > 2.5 kVAC between L-N
> 3 kVAC between L/N-PE
(1 min/50 Hz)
Allowable Operation Tempe-
rature
-25 °C to 60 °C
IP-Protection from front side IP40 or IP67 acc. to IEC
60529
Insulation cover Suitable for appliances with protection
class I or II acc. to IEC 61140
Terminal Quick connect terminals 6.3 x 0.8 mm
Panel Thickness S Screw: max 8 mm
Recommended torque min 0.25 Nm
Snap-in : S =1/1.2/1.5/2/2.5/3 mm
Material: Housing Thermoplastic, black, UL 94V-0
appliance inlet/-outlet C14 / C18 acc. to IEC 60320-1
UL 60320-1, CSA C22.2 no. 60320-1
(for cold conditions) pin-temperature 70
°C, 10 A, Protection Class I or II
Circuit Breakers Acc. IEC/EN 60934, UL 1077, CSA
22.2 no. 235
2-pole rocker switch, illuminated or non-
illuminated.
Conditional short circuit Inc:
2000 A
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.
2
Power entry modules without line filter
DG11 https://www.schurter.com /PG05
Connectors
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: DG11
Approval Logo Certificates Certification Body Description
VDE Approvals VDE Certificate Number: 40048151
UL Approvals UL UL File Number: E96454
CCC Approvals CCC CCC Certificate Number: pending
Product standards
Product standards that are referenced
Organization Design Standard Description
Designed according to IEC 60320-1 Appliance couplers for household and similar general purposes
Designed according to UL 60320-1 Standard for Attachment Plugs and Receptacles
Designed according to CSA C22.2 no. 60320-1 General Use Receptacles, Attachment Plugs, and Similar Wiring Devices
Application standards
Application standards where the product can be used
Organization Design Standard Description
Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information
technology equipment.
Compliances
The product complies with following Guide Lines
Identification Details Initiator Description
CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
RoHS SCHURTER AG Directive RoHS 2011/65/EU, Amendment (EU) 2015/836
China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
SCHURTER AG V-Lock system are based on a matching plug-dose combination. The
connector is equipped with a notch intended for use with the latching
cordset. The cord latching system prevents against accidental removal of
the cordset.
Dimensions [mm]
Snap-in mounting for front mount IP40
35
63
R1.5
(51.6)
48.3
32.45 3.3
S
1622.1
5.35
5.65
max. R3
30 ±0.10
59 +0.20
0
+0.10
0
S = Panel thickness
3
Power entry modules without line filter DG11
https://www.schurter.com /PG05
Connectors
Screw-on mounting version A for front mount IP40
R1.5
66
76
35
32.45
1.2
ø 3.4
ø 6.2
3.348.3
(51.6)
1622.1
5.65
5.35
30 ±0.10
66 ±0.10
59 +0.20
0
ø 3.4/M3
max. R3
Screw-on mounting Version A for rear mount IP40
ø 3.4
R1.5
66
76
35
50.1
(51.6)
34.25
1.8
1.5
5.65
5.35
16
22.1
ø 3.4/M3
66 ±0.10
57.2 ±0.10
max. R1
29.2 ±0.10
Screw-on mounting Version B for front mount IP40
5.65
5.35
22.1 16
1.2
ø 6.2
(51.6)
48.3
32.45 3.3
48
38
63
R1.5
ø 3.4 / M3
38 ±0.10
30 ±0.10
59 +0.20
0
max. R3
4
Power entry modules without line filter
DG11 https://www.schurter.com /PG05
Connectors
Screw-on mounting version B for rear mount IP40
48
38
63
R1.5
ø 3.4
50.1
(51.6)
1.8
1.5
34.25
5.65
5.35
16
22.1
38 ±0.10
29.2 ±0.10
ø 3.4 / M3
max. R1
57.2 ±0.10
Screw-on mounting for front mount IP67
38
68
51
42
16
22.1
5.65
5.35
3.332.45
(53.6)
50.3 34.3 ±0.10
42 ±0.10
ø 3.4/M3
max. R3
38±0.10
59+0.20
0
Diagrams
L
N
PE PE'
L' P
1
N' P2
1) 2)
TA35
1) Line
2) Load
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient Temperature [°C] Correction factor
-30 0.76
-20 0.81
0 0.90
+23 1.00
+40 1.03
+50 1.04
+60 1.06
Example: Rated current = 5 A, Environmental temperature = 50 °C --> Correction factor =
1.04, Resulting current = 5.2 A --> Fount to next higher rated current: 6 A
5
Power entry modules without line filter DG11
https://www.schurter.com /PG05
Connectors
Time-Current-Curves
Tripping Characteristics In < 3 A
Time in Seconds
TyppTA35
Nennstrom<3 A (TC-1,TC-2)
Umgebungstemp. +23 °C
1,05 10854321,35
10'000
60
2`000
1`000
500
200
100
50
20
10
[ sec ][ min ]
10
5
1
30
20
5
2
1
0,5
0,3
0,2
0,1
Multiple of Rated Current In
Reference Temperature +23°
Tripping Characteristics In 3 ... 15 A
Time in Seconds
1,05 10854321,35
10'000
60
2`000
1`000
500
200
100
50
20
10
[ sec [ min ]
10
5
1
30
20
5
2
1
0,5
0,3
0,2
0,1
]
> 3–15A (TC-1, TC-2)
TypTA35
Nennstrom
Umgebungs-
temp. +23 °C
Multiple of Rated Current In
Reference Temperature +23°
6
Power entry modules without line filter
DG11 https://www.schurter.com /PG05
Connectors
Rated current In (A)
Other rated currents on request
In Code
1,0 J10
2,0 J20
4,0 040
5,0 050
6,0 060
In Code
8,0 080
10,0 100
12,0 120*
15,0 150*
F120 C0
No other
features
F embossed
H printed white
K printed black
L printed white
M printed black
Surface Illustration Colour of print
Rocker legend
l
0
ON
OFF
ON
OFF
ll
00
Other legends on request
Colours
Switch front Rocker
non-illuminated illuminated
W black white
B black black
3 black red transparent
4 black green transparent
6 black orange transparent
Other colours on request
CBD W
TA35-
ORDER CODE
Switch without CBT CBD
illumination
Switch illuminated 240 V C12 C32
120 V C14 C34
Other versions on request
Table 1 Selection for type TA35
Order example
LINE
LOAD
LINE
LOAD
Number of switched poles 2-pole
Number of protected poles 1 2
*) UL / CSA only
Position of the rocker
legend e.g. I / O
7
Power entry modules without line filter DG11
https://www.schurter.com /PG05
Connectors
Typ Con guration Code
(Example) TA35
DG11 C B D W F 1 2 0 C 0 -000- C6135-XXX - XXX -00
see table 1
Con guration Code
Please note that Schurter will establish an
internal part number for logistics use in
addition to the order code. The format of this
internal part number is, for example:
3-XXX-XXX
Panel Mounting 1)
00 Screw version A front mounting
01 Screw version B front mounting
02 Screw version A rear mounting
03 Screw version B rear mounting
10 Snap-in 1.0 mm
12 Snap-in 1.2 mm
15 Snap-in 1.5 mm
20 Snap-in 2.0 mm
25 Snap-in 2.5 mm
30 Snap-in 3.0 mm
88 Screw version front mounting
(sealed towards housing, IP67)
Color
0 Black
Screw version A Screw version B
1)
Terminal PE
0 Without (PCII)
1 QC 6.3x0.8 mm
Terminal L
1 QC 6.3x0.8 mm (unwired)
3 Connection to TA35 (wired)
Terminal N
1 QC 6.3x0.8 mm (unwired)
3 Connection to TA35 (wired)
All Variants
Config. Code Order Number
DG11-C126F100C0-000-C6135-331-200-00 3-107-924
DG11-CBDWM100C0-000-C6135-331-880-00 3-108-454
DG11-CBDBL100C0-000-C6135-331-010-00 3-108-463
DG11-CBDWM100C0-000-C6135-331-150-00 3-109-713
DG11-CBDWM100C0-000-C6135-331-010-00 3-109-714
DG11-CBDWM100C0-000-C6135-331-020-00 3-109-715
DG11-CBDWM150C0-000-C6135-331-150-00 3-109-716
DG11-CBDWM150C0-000-C6135-331-010-00 3-109-717
DG11-CBDWM150C0-000-C6135-331-020-00 3-109-718
DG11-CBDWM150C0-000-C6135-331-880-00 3-109-719
Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
More information in the HTML data sheet on the variant table
Packaging unit 10 Pcs
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
30.05.2019