10 Amp . . . . . . . . . . 250 240 LSMT 250 340 LSMT 250 440 LSMT
15 Amp . . . . . . . . . . 250 240 LSND 250 340 LSND 250 440 LSND
20 Amp . . . . . . . . . . 250 240 LSNG 250 340 LSNG 250 440 LSNG
30 Amp . . . . . . . . . . 250 240 LSNL 250 340 LSNL 250 440 LSNL
40 Amp . . . . . . . . . . 250 240 LSNP 250 340 LSNP 250 440 LSNP
50 Amp . . . . . . . . . . 250 240 LSNT 250 340 LSNT 250 440 LSNT
75 Amp . . . . . . . . . . 250 240 LSPB 250 340 LSPB 250 440 LSPB
80 Amp . . . . . . . . . . 250 240 LSPD 250 340 LSPD 250 440 LSPD
100 Amp . . . . . . . . . . 250 240 LSPK 250 340 LSPK 250 440 LSPK
150 Amp . . . . . . . . . . 250 240 LSPZ 250 340 LSPZ 250 440 LSPZ
200 Amp . . . . . . . . . . 250 240 LSRL 250 340 LSRL 250 440 LSRL
300 Amp . . . . . . . . . . 250 240 LSRX 250 340 LSRX 250 440 LSRX
400 Amp . . . . . . . . . . 250 240 LSSC 250 340 LSSC 250 440 LSSC
500 Amp . . . . . . . . . . 250 240 LSSF 250 340 LSSF 250 440 LSSF
600 Amp . . . . . . . . . . 250 240 LSSJ 250 340 LSSJ 250 440 LSSJ
800 Amp . . . . . . . . . . 250 240 LSSN 250 340 LSSN 250 440 LSSN
1 Kiloamp . . . . . . . . . . 250 240 LSVA 250 340 LSVA 250 440 LSVA
1.2 Kiloamp . . . . . . . . . . 250 240 LSVB 250 340 LSVB 250 440 LSVB
1.5 Kiloamp . . . . . . . . . . 250 240 LSVC 250 340 LSVC 250 440 LSVC
2.0 Kiloamp . . . . . . . . . . 250 240 LSVE 250 340 LSVE 250 440 LSVE
3.0 Kiloamp . . . . . . . . . . 250 240 LSVJ 250 340 LSVJ 250 440 LSVJ
7
AC Ammete rs Cont’d
Size 11⁄221⁄231⁄241⁄2
200 200 200
Series Series Series
Type
Rating
& Scale
AC AMMETERS — TRANSFORMER-RATED, 0-5 AMPERES, 25 - 500 Hz, PIVOT AND JE WEL, IRON VANE
Horizon Lin e
Specifications
Accuracy: All DC and AC iron-vane; ±2%
of full-scale, AC rectifie r type; ±3%
of full scale (wi th 60 Hz sine wave at 25º C).
When standard 60 Hz iron vane ammeters
are use d at the extreme limits of 20 or 400
Hz, additional error (approx. .75%) may be
experience d. Expanded-scale voltmeters;
±.5% of full scale value.
ANSI Specif ica tion: All meters me et ANSI
Specifications C- 39.1.
Overload: Voltmeters (AC and DC) - 50%
momentary, 20% sustained. Ammeters
(AC and DC) momentary: 10 time s the
rated cur rent for 10 consecutive intervals
of .5 second with a 1 minute interval
betwe en successive applications; sustained:
20% for six hours.
Scale Dat a: 90 degree rotation.
Scale Lengt h:
Size Horizon Line
11⁄2" 1.50"
21⁄2" 2.06"
31⁄2" 2.88"
41⁄2" 3.93"
Insulation Level: All meters (except 11⁄2"),
2600 VRMS Hi-pot, 11⁄2"-1500 VRMS Hi-pot.
Burden Data: AC ammeter-5 amps, 0.5 va
max. 0.5 power-facto r lagging, @60 Hz. AC
Voltmeter-unity power factor.
Respons e Time and Overshoot:
Response time: 3 seconds (max.) for 21⁄2",
31⁄2", 41⁄2" size for microammeters: 2
seconds (max.) for all other DC ratings,
and 2.5 seconds (max.) for AC ratings.
Maximum of 40% ove rshoot.
Dimensions: Se e page 36- 37.
How To Order
To Order Horizon Line panel meters use
the appropriate catalog numbers provide d
in the tables. Taut band instruments have
a 251 prefix number, Pivot & jewel instrume nts
have a 255 prefix number, except AC Iron Vane
prefix which is 251.
Ordering Examples:
1. 21⁄2", 300 V DC Voltmeter, zero lef t, taut
band - 251 220 RXRX
2. 21⁄2", 300 V DC Voltmeter, zero lef t,
pivot & jewel - 255 220 RXRX
3. 21⁄2", 300 VAC (Iron Vane) pivot & jewel -
251 244 RXRX
Severe-duty meters a re available to meet UL
1437 requirements. UL version, wi th flame
retardant window and base, is not offered in
11⁄2". To order, add /UL or /CUL af ter catalog
number, or contact factor y. For ratings and
scales not liste d contact factor y.
S
C
A
L
E
O
N
L
Y
(See page 29 for Transformers)
Type 251 and 255
Horizon Line