Form No. FWA 130
Page 1 of 2
BIF Doc #720001
Bussmann®
FWA 130V 1000-4000A
Electrical Characteristics Ordering Information Dimensions Curves
Rated I2t (A2Sec) Carton See Page
Current Clearing Watts Part Carton Weight Figure or
Type RMS-Amps Pre-arc at 130V Loss Number Qty. (lbs) Number (BIF #)
1000 170000 460000 60 FWA-1000AH
______________________________________________________________________________________
1200 270000 730000 70 FWA-1200AH
______________________________________________________________________________________
1500 520000 1400000 78 FWA-1500AH
______________________________________________________________________________________
FWA 2000 860000 2400000 108 FWA-2000AH 1 3.3 Fig. 1 35785301130V ______________________________________________________________________________________
2500 1500000 4100000 130 FWA-2500AH
______________________________________________________________________________________
3000 2100000 5700000 150 FWA-3000AH
______________________________________________________________________________________ ______________
4000 3400000 9200000 257 FWA-4000AH Fig. 2
nInterrupting rating 200kA RMS Symmetrical. 1 kg = 2.2 l bs 1 lb = 0.45 kg
nWatts loss provided at rated current.
n(130 Vdc/Interrupting Rating 50kA) U.L. Recognition on 1000 through 2000 amperes.
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other volt-
ages, the clearing I2t is found by multi-
plying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL, which may appear across the fuse
during its operation as a function of the
applied working voltage, Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power loss-
es at load currents lower than the rated
current. The correction factor, Kp, is
given as a function of the RMS load cur-
rent, Ib, in % of the rated current .
1301046526
1.5
1.0
0.5
0.3
0.2
0.15 Eg
KUL
Eg
200
100
100 15050
300
Kp
1.0
0.8
0.4
0.5
0.6
0.3
0.2
0.1 30 40 50 60 70 80 90 100%
Ib
Electrical Characteristics
7-11-01 SB01191
7-11-01 SB01191
®
Form No. FWA 130
Page 2 of 2
BIF Doc #720001
Bussmann®
FWA 130V 1000-4000A
1.875 1.875
BC
CB
D
Order # Fig. B C D Thread Depth
FWA-1000AH-2000AH 1 2.0 1.0 Tapped ‹Ω•∑-24 ≈ ⁄Ω™∑
FWA-2500AH-3000AH 1 3.0 1.5 Tapped ⁄Ω™∑-20 ≈ ⁄Ω™∑
FWA-4000AH 2 3.5 1.5 1.5 Tapped ⁄Ω™∑-20 ≈ ⁄Ω™∑
Dimension in inches.
1mm = 0.0394∑ 1∑ = 25.4mm
Dimensions
Fig. 1: 1000-3000 Amp Range Fig. 2: 4000 Amp Range
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition
uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications.
Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves
the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all pos-
sible applications.