R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
Bussmann®
CATALOG SYMBOL: JCK, JCK-A, JCK-B, JCH, JCL, JCL-A,
JCL-B, JCG, JCR, & JCR-B
R-RATED
MEDIUM V OLTA GE
CURRENT LIMITING
2400V AC — JCK, JCK-A, JCK-B, JCH
4800V AC — JCL, JCL-A, JCL-B, JCG
7200V AC — JCR, JCR-B
MAX. DESIGN VOLTAGE 2540V AC — JCK, JCK-A,
JCK-B, JCH
5080V AC — JCL, JCL-A
JCL-B, JCG
8300V AC — JCR, JCR-B
U.L. RECOGNIZED: 2540V AC — JCK, JCK-A
5080V AC — JCL, JCL-A
U.L. RECOGNIZED (GUIDE #MSSS2, FILE # E96676)
R-Rated medium voltage fuses are back-up current limiting
fuses used in conjunction with medium voltage motors and
motor controllers.
The JCK-A, JCL-A, & JCR are supplied with Westinghouse
Ampguard Hookeye.
This single hookeye i s on one end of the fuse and aids in the
inser tion and removal of the fuse.
Current limiting fuses may be designated as R-Rated if they
meet the following requirements:
1. The fuse will safely interrupt all currents between its mini-
mum and maximum interrupting ratings.
2. The fuse will melt in a range of 15 to 35 seconds at a
value of 100 times the “R’number (ANSI C37.46).
Bussmann R-Rated current limiting fuses are designed for
use with medium voltage starters to provide shor t-circuit pro-
tection for the motor and motor controller.
These fuses offer a high level of fault current interruption in a
self-contained, non-venting package which can be mounted
indoors or in an enclosure.
Open fuse indication on all fuses.
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
10-10-01 SB01396
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR, & JCR-B
Page 1 of 8
BIF Doc #6001
Specifications
Buss Maximum Dimensions (Inches) Max. Int. Cap. Min. Int. Cap.
Catalog No. Amperage Design Voltage A B C Construction Amps (Asym.) Amps (Sym.) Amps (Sym.)
2400V; R-Rated; Indoor/Enclosure (See Figure 1)
JCK-2R 70 2R 2540V 11.24 3.0 3.0 Single 80,000 50,000 165
JCK-3R 100 3R 2540V 11.24 3.0 3.0 Single 80,000 50,000 220
JCK-4R 130 4R 2540V 11.24 3.0 3.0 Single 80,000 50,000 320
JCK-5R 150 5R 2540V 11.24 3.0 3.0 Single 80,000 50,000 410
JCK-6R 170 6R 2540V 11.24 3.0 3.0 Single 80,000 50,000 480
JCK-9R 200 9R 2540V 11.24 3.0 3.0 Single 80,000 50,000 720
JCK-12R 230 12R 2540V 11.24 3.0 3.0 Single 80,000 50,000 970
JCK-18R 390 18R 2540V 11.24 3.0 3.0 Double 80,000 50,000 1,430
JCK-24R 450 24R 2540V 11.24 3.0 3.0 Double 80,000 50,000 1,880
2400V; R-Rated; Indoor/Enclosure;With Westinghouse Ampguard Hookeye (See Figure 1)
JCK-A-2R 70 2R 2540V 11.24 3.0 3.0 Single 80,000 50,000 165
JCK-A-3R 100 3R 2540V 11.24 3.0 3.0 Single 80,000 50,000 220
JCK-A-4R 130 4R 2540V 11.24 3.0 3.0 Single 80,000 50,000 320
JCK-A-5R 150 5R 27540V 11.24 3.0 3.0 Single 80,000 50,000 410
JCK-A-6R 170 6R 2540V 11.24 3.0 3.0 Single 80,000 50,000 480
JCK-A-9R 200 9R 2540V 11.24 3.0 3.0 Single 80,000 50,000 720
JCK-A-12R 230 12R 2540V 11.24 3.0 3.0 Single 80,000 50,000 970
JCK-A-18R 390 18R 2540V 11.24 3.0 3.0 Double 80,000 50,000 1,430
JCK-A-24R 450 24R 2540V 11.24 3.0 3.0 Double 80,000 50,000 1,880
2400V; R-Rated; Indoor/Enclosure; Bolt-On (See Figure 2)
JCK-B-30 25 2540V 14.18 12.81 - Single 80,000 50,000 90
JCK-B-2R 70 2R 2540V 14.18 12.81 - Single 80,000 50,000 170
JCK-B-3R 100 3R 2540V 14.18 12.81 - Single 80,000 50,000 245
JCK-B-4R 130 4R 2540V 14.18 12.81 - Single 80,000 50,000 340
JCK-B-5R 150 5R 2540V 14.18 12.81 - Single 80,000 50,000 430
JCK-B-6R 170 6R 2540V 14.18 12.81 - Single 80,000 50,000 500
JCK-B-9R 200 9R 2540V 14.18 12.81 - Single 80,000 50,000 1,000
JCK-B-12R 230 12R 2540V 14.18 12.81 - Single 80,000 50,000 1,250
JCK-B-18R 390 18R 2540V 14.18 12.81 3.56 Double 80,000 50,000 1,700
JCK-B-24R 450 24R 2540V 14.18 12.81 3.56 Double 80,000 50,000 1,210
2400V; R-Rated; Indoor; Hermetically Sealed, Class 1, Group D, Div. 2, Hazardous Locations; For Use with Ampgard Motor Starters (See Figure 1)
JCH-30 25 2540V 10.81 3.0 3.0 Single 80,000 50,000 90
JCH-2R 70 2R 2540V 10.81 3.0 3.0 Single 80,000 50,000 170
JCH-3R 100 3R 2540V 10.81 3.0 3.0 Single 80,000 50,000 245
JCH-4R 130 4R 2540V 10.81 3.0 3.0 Single 80,000 50,000 340
JCH-5R 150 5R 2540V 10.81 3.0 3.0 Single 80,000 50,000 430
JCH-6R 170 6R 2540V 10.81 3.0 3.0 Single 80,000 50,000 500
JCH-9R 200 9R 2540V 10.81 3.0 3.0 Single 80,000 50,000 1,000
JCH-12R 230 12R 2540V 10.81 3.0 3.0 Single 80,000 50,000 1,250
JCH-18R 390 18R 2540V 10.81 3.0 3.0 Double 80,000 50,000 1,700
JCH-24R 450 24R 2540V 10.81 3.0 3.0 Double 80,000 50,000 2,100
4800V; R-Rated; Indoor/Enclosure (See Figure 1)
JCL-2R 70 2R 5080V 15.76 3.0 3.0 Single 80,000 50,000 165
JCL-3R 100 3R 5080V 15.76 3.0 3.0 Single 80,000 50,000 220
JCL-4R 130 4R 5080V 15.76 3.0 3.0 Single 80,000 50,000 320
JCL-5R 150 5R 5080V 15.76 3.0 3.0 Single 80,000 50,000 410
JCL-6R 170 6R 5080V 15.76 3.0 3.0 Single 80,000 50,000 480
JCL-9R 200 9R 5080V 15.76 3.0 3.0 Single 80,000 50,000 720
JCL-12R 230 12R 5080V 15.76 3.0 3.0 Single 80,000 50,000 970
JCL-18R 390 18R 5080V 15.76 3.0 3.0 Double 80,000 50,000 1,430
JCL-24R 450 24R 5080V 15.76 3.0 3.0 Double 80,000 50,000 1,880
10-10-01 SB01396
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR, & JCR-B
Page 2 of 8
BIF Doc #6001
Specifications
Buss Maximum Dimensions (Inches) Max. Int. Cap. Min. Int. Cap.
Catalog No. Amperage Design Voltage A B C Construction Amps (Asym.) Amps (Sym.) Amps (Sym.)
4800V; R-Rated; Indoor/Enclosure;With Westinghouse Ampguard Hookeye (See Figure 1)
JCL-A-2R 70 2R 5080V 15.76 3.0 3.0 Single 80,000 50,000 165
JCL-A-3R 100 3R 5080V 15.76 3.0 3.0 Single 80,000 50,000 220
JCL-A-4R 130 4R 5080V 15.76 3.0 3.0 Single 80,000 50,000 320
JCL-A-5R 150 5R 5080V 15.76 3.0 3.0 Single 80,000 50,000 410
JCL-A-6R 170 6R 5080V 15.76 3.0 3.0 Single 80,000 50,000 480
JCL-A-9R 200 9R 5080V 15.76 3.0 3.0 Single 80,000 50,000 720
JCL-A-12R 230 12R 5080V 15.76 3.0 3.0 Single 80,000 50,000 970
JCL-A-18R 390 18R 5080V 15.76 3.0 3.0 Double 80,000 50,000 1,430
JCL-A-24R 450 24R 5080V 15.76 3.0 3.0 Double 80,000 50,000 1,880
4800V; R-Rated; Indoor/Enclosure; Bolt-On (See Figure 2)
JCL-B-30 30 5080V 19.25 17.88 - Single 80,000 50,000 95
JCL-B-2R 70 2R 5080V 19.25 17.88 - Single 80,000 50,000 180
JCL-B-3R 100 3R 5080V 19.25 17.88 - Single 80,000 50,000 270
JCL-B-4R 130 4R 5080V 19.25 17.88 - Single 80,000 50,000 350
JCL-B-5R 150 5R 5080V 19.25 17.88 - Single 80,000 50,000 450
JCL-B-6R 170 6R 5080V 19.25 17.88 - Single 80,000 50,000 540
JCL-B-9R 200 9R 5080V 19.25 17.88 - Single 80,000 50,000 700
JCL-B-12R 230 12R 5080V 19.25 17.88 - Single 80,000 50,000 1,000
JCL-B-18R 390 18R 5080V 19.25 17.88 3.31 Double 80,000 50,000 1,450
JCL-B-24R 450 24R 5080V 19.25 17.88 3.31 Double 80,000 50,000 2,000
4800V; R-Rated; Indoor; Hermetically Sealed, Class 1, Group D, Div. 2, Hazardous Locations; For Use with Ampgard Motor Starters (See Figure 1)
JCG-30 30 5080V 15.91 3.0 3.0 Single 80,000 50,000 95
JCG-2R 70 2R 5080V 15.91 3.0 3.0 Single 80,000 50,000 180
JCG-3R 100 3R 5080V 15.91 3.0 3.0 Single 80,000 50,000 270
JCG-4R 130 4R 5080V 15.91 3.0 3.0 Single 80,000 50,000 350
JCG-5R 150 5R 5080V 15.91 3.0 3.0 Single 80,000 50,000 450
JCG-6R 170 6R 5080V 15.91 3.0 3.0 Single 80,000 50,000 540
JCG-9R 200 9R 5080V 15.91 3.0 3.0 Single 80,000 50,000 700
JCG-12R 230 12R 5080V 15.91 3.0 3.0 Single 80,000 50,000 1,000
JCG-A-18R 390 18R 5080V 15.91 3.0 3.0 Double 80,000 50,000 1,450
JCG-A-24R 450 24R 5080V 15.91 3.0 3.0 Double 80,000 50,000 2,000
7200V; R-Rated; Indoor/Enclosure;With Ampgard Hookeye (See Figure 1)
JCR-2R 70 2R 8300V 15.85 3.0 3.0 Single 80,000 50,000 160
JCR-3R 100 3R 8300V 15.85 3.0 3.0 Single 80,000 50,000 250
JCR-4R 130 4R 8300V 15.85 3.0 3.0 Single 80,000 50,000 325
JCR-5R 150 5R 8300V 15.85 3.0 3.0 Single 80,000 50,000 390
JCR-6R 170 6R 8300V 15.85 3.0 3.0 Single 80,000 50,000 500
JCR-9R 200 9R 7200V 15.85 3.0 3.0 Single 80,000 50,000 750
JCR-12R 230 12R 7200V 15.85 3.0 3.0 Single 80,000 50,000 1,000
JCR-18R 390 18R 7200V 15.85 3.0 3.0 Double 80,000 50,000 1,450
JCR-24R 450 24R 7200V 15.85 3.0 3.0 Double 80,000 50,000 2,500
7200V; R-Rated; Indoor/Enclosure; Bolt-On (See Figure 2)
JCR-B-2R 70 2R 8300V 19.25 17.88 - Single 80,000 50,000 160
JCR-B-3R 100 3R 8300V 19.25 17.88 - Single 80,000 50,000 250
JCR-B-4R 130 4R 8300V 19.25 17.88 - Single 80,000 50,000 325
JCR-B-5R 150 5R 8300V 19.25 17.88 - Single 80,000 50,000 390
JCR-B-6R 170 6R 8300V 19.25 17.88 - Single 80,000 50,000 500
JCR-B-9R 200 9R 7200V 19.25 17.88 - Single 80,000 50,000 750
JCR-B-12R 230 12R 7200V 19.25 17.88 - Single 80,000 50,000 1,000
JCR-B-18R 390 18R 7200V 19.25 17.88 3.31 Double 80,000 50,000 1,450
JCR-B-24R 450 24R 7200V 19.25 17.88 3.31 Double 80,000 50,000 2,500
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
10-10-01 SB01396
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR, & JCR-B
Page 3 of 8
BIF Doc #6001
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
10-10-01 SB01396
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR, & JCR-B
Page 4 of 8
BIF Doc #6001
0.38"
(9.5mm)
B
INDICATOR
Showing Fuse is Open
INDICATOR
Showing Fuse
is Open
A
C
Dimensional Data
Figure 1
Figure 2
Form No. (helv reg. 7pt)
Page 5 of 8
BIF Doc #XXXX
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
CURRENT IN AMPERES
TIME IN SECONDS
20
100
1,000
10,000
20,000
300
100
10
1
.1
.01
2
3
AMPERE
RATING
4
6
9
12
18
24
Current Limitation Curves Time-Current Characteristic Curves–Average Melt
INSTANTANEOUS PEAK LET THRU
CURRENT AMPERES
PROSPECTIVE SHORT CIRCUIT CURRENT
ASYMMETRICAL RMS AMPERES
3
24
18
12
9
6
4
2
B
A
R
RATING
400,000
100,000
10,000
1,000
1,000
10,000
80,000
200,000
JCK
JCL
JCK, JCK-A, JCL, JCL-A
10-10-01 SB01396
Bussmann®
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
10-10-01 SB01396
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR, & JCR-B
Page 6 of 8
BIF Doc #6001
Time-Current Curve: Minimum Melt Time-Current Curve:Total Clearing
JCK-B, JCH
50999-1
Peak Let-Through Curves
50999-3
50999-2
Bussmann®
10-10-01 SB01396
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR, & JCR-B
Page 7 of 8
BIF Doc #6001
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
Time-Current Curve: Minimum Melt Time-Current Curve:Total Clearing
JCL-B, JCG
51000-1
Peak Let-Through Curves
51000-3
51000-2
Bussmann®
10-10-01 SB01396
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR, & JCR-B
Page 8 of 8
BIF Doc #6001
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
JCK, JCK-A, JCK-B, JCH,
JCL, JCL-A, JCL-B,
JCG, JCR, & JCR-B
Time-Current Curve: Minimum Melt Time-Current Curve:Total Clearing
JCR, JCR-B
Peak Let-Through Curves
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to
clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any
products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been select-
ed, it should be tested by the user in all possible applications.
51001-1 51001-2
51001-3