PAT450 Portable Appliance Tester PAT450 Portable Appliance Tester DESCRIPTION Operators of electric tools and other electrical equipment must be protected from potentially dangerous flaws in workmanship or wear and tear. The PAT450 is designed to test portable electrical equipment for safe operation. The tests conform to the latest editions of European regulations and standards including VDE0701-0702 and the Code of Practice for the In-Service Inspection and Testing of Electrical Equipment in the UK. The PAT450 has a memory capacity for storing up to 10,000 test results, and also 10 A and 25 A earth bond testing. The unit also includes 1.5 kV and 3 kV flash testing, ideal for tool rental outlets and service workshops where flash testing is routine. It has a high duty cycle, with the design tailored to fast testing, easy operation, and all-day use. The PAT450 features a unique restart, so that when moving the tester from one room to another, it restarts instantly from the same menu where it was unplugged. This is a significant timesaver, allowing more tests per day. USB communication provides convenient download to a standard USB memory stick. An on-board 10,000 record memory provides interruption-free testing for improved efficiency, with a large QWERTY keypad for fast data entry. The instrument is capable of working with standard barcode scanners and a thermal transfer barcode label printer operating directly from the USB port. Thermal transfer labels are highly resistant, stable and easily available. Five soft-keys give direct access to frequently-used functions, accelerating navigation through menus and increasing productivity. Both standard and customer configurable test groups are available for fast, flexible asset testing. n 10,000-record on-board memory n Large 5.7 in. 1/4 VGA backlit full color screen n 200 mA; 10 A and 25 A bond test with high duty cycle n Selectable PASS/FAIL limits n Works with standard barcode scanners Accessories supplied include a combined earth-bond and insulation test lead, an adapter for testing 120 V extension leads, a laptop power supply adapter, and a carry case for convenient product and lead storage. All instruments also include download manager software, to enable data to be converted into a CSV format which can be read directly on a PC using Microsoft(R) Excel. TYPE OF TESTS Earth Bond and Continuity Tests To verify the integrity of exposed metalwork on grounded (Class I) appliances. Test current of 25 A is passed via a remote probe, returning through the Ground pin of the power plug. Test currents of 10 A and 25 A are available for bond testing. Where sensitive electronic equipment may be damaged by high currents, 200 mA is selectable. Insulation Test To check that equipment conductors are isolated from ground - 500 V dc; the live and neutral conductors are linked; and the test voltage is applied between this link and the ground pin. Where an appliance does not have an earth connection (Class II), the remote probe is used to contact anywhere on the external case of the equipment. Where 500 V may damage sensitive equipment, the PAT450 provides alternative methods of verifying insulation integrity. A lower voltage of 250 V dc is selectable, or alternatives such as a touch current test or substitute leakage test can be performed. PAT450 Portable Appliance Tester Touch Current Test This test powers the asset at the supply voltage as if it were in use. The current passing down the earth conductor is displayed. For Class II, the remote probe is used to contact any accessible conductive parts. Differential Leakage Test Similar to the touch current test, during operation the difference in current between the live and neutral conductor is measured. Substitute/Alternative Leakage Test This test is performed in the same method as the insulation test, i.e. between the earth conductor and linked live/ neutral. For Class II, the remote probe is used to contact any accessible conductive parts of the asset. An ac voltage ac voltage (nominal 40 V at supply frequency) is applied and the leakage current measured. As this is at the same frequency as the supply, the impedance of any leakage path is the same as that when the asset is in operation. Functional Load Test Operational test to ensure that the asset works as it should. Supply voltage is applied to the asset when in use. Simultaneously, the VA value is displayed as an additional check that the current drawn by the asset is as expected. Extension and IEC Power Cords Standard insulation and earth-bond tests are performed, with an additional polarity test, to ensure that the lead is wired correctly. Hi-pot/Flash Test Where the application requires a hi-pot/flash test, a high voltage is applied to any exposed conductive parts via a probe. The leakage current between the linked live/neutral conducters and the probe is monitored, and any electrical breakdown indicated. For Class I, the test voltage is 1.5 kV ac; for Class II it is 3 kV ac. FEATURES AND BENEFITS n Large 5.7" 1/4 VGA backlit color screen for clear results n 200mA; 10A and 25A bond test with high duty cycle for repetitive testing n 250V and 500V insulation tests protect sensitive electronics n Selectable PASS/FAIL limits provide instant indication of a faulty asset n 120 V 60 Hz operation for industrial, commercial and residential applications n Simplified menus for easy intuitive operation n Instant restart for faster testing across multiple rooms n Adjustable test times allow faster testing n Tests for standard and anti-surge extension leads n Operational test including VA display for a complete testing range APPLICATIONS While the USA does not have the level of regulation found in the UK, we are far more litigious. Implementing a regular inspection program that includes PAT testing of electrical equipment and appliances will help protect personnel from shock hazards, facilities from electrically induced fires and businesses from litigation. For businesses that manufacture and ship electrical products to the European Union, PAT testing at the factory will ensure that products shipped will pass import testing and not become a costly problem. Ideal for portable appliance testing in locations like service workshops, hotels, schools, hospitals, prisons, long term care facilities, construction sites, offices, restaurants and sport facilities, the PAT450 can store up to 10,000 test results. It features 10 A and 25 A bond tests with high duty-cycle designed for fast testing, easy operation and all-day use. The PAT's 250 V and 500 V insulation tests protect sensitive electronics. PAT450 Portable Appliance Tester SPECIFICATIONS Electrical supply range 120 V 10% Bond test (10 A and 25 A) Open circuit voltage: 9 V a.c. 10% 0.1 V (Supply: 120 V 60 Hz) Earth bond resistance accuracy: 5% 3 digits (0 to 0.49 ) 5% 5 digits 0.5 to .99 ) Earth bond resistance resolution: 10 m (0 to 1.99 ) Display range: 0 to 1.99 Continuity test (200 mA) Continuity test voltage: 4.0 V d.c. -0% +10% Continuity resistance accuracy: 5% 3 digits (0 to 0.49 ) 5% 5 digits (0.5 to .99 ) Continuity resistance resolution: 10 m (1 to 19.99 ) Display range: 0 to 19.99 Insulation resistance test (250 V and 500 V) Accuracy (120 V): 2% 5 digits (0 to 19.99 M) 5% 10 digits (20 to 99.99 M) Resolution: 0.01 M Display range: 0 to 99.99 M Substitute leakage test Test voltage and frequency: Leakage current accuracy: Leakage current resolution: Display range: 40 V ac 10% nominal mains frequency 5% 5 digits 0.01 mA 0 to 19.99 mA Differential leakage current Test voltage and frequency: Nominal mains supply Accuracy: 5% 5 digits Resolution: 0.01 mA Display range: 0 to 19.99 mA Touch current test Test voltage and frequency: Accuracy: Resolution: Display range: Nominal mains supply 5% 5 digits 0.01 mA 0 to 10 mA Operational test Test voltage and frequency: Nominal mains supply VA rating: 110 V 1800 VA VA accuracy:5% 10 digits (0 - 99 VA) 5% 50 digits (100 VA - 999 VA) 5% 100 digits (1000 VA - 1800 VA) Resolution: 1 VA (0 to 1800 VA) Display range:0 to 1800 VA Extension lead test Tests performed: Bond, insulation and polarity Polarity test voltage: 12 V Polarity checks:Lead OK Live neutral S/C Live neutral reversed Live/neutral O/C Hi-pot/Flash test Voltage:1500 V ac. nominal for Class 1 3000 V ac nominal for Class 2 Current:<3.5 mA short circuit @ 253 V primary supply voltage Breakdown current accuracy: 5% 5 digits Breakdown current resolution:0.01 mA Display range:0 to 3.0 mA Fuse test Test voltage:3.3 V Warning:Audible beep if fuse is OK Environmental Operating temperature: Storage temperature: Humidity: Maximum altitude: Ingress protection: -10 to +50 C (+14 F to +122 F) -20 to +60 C (-4 F to +140 F) 90% RH @ -10 to +30 C (14 F to 86 F) 75% RH @ +30 to +50 C (86 F to 122 F) 2000 m IP40 Weight 5.0 kg (11 lb) Dimesions Instrument: 180 (H) x 255 (W) x 320 (L) mm 7 (H) x 10 (W) x 12.5 (L) in. Packaging: 210 (H) x 280 (W) x 390 (L) mm 8.2 (H) x 11 (W) x 15.3 (L) in. Safety IEC 61010-1: CAT II 300 V EMC IEC 61326-1: 2006 IEC 61326-2-2: 2005 PAT450 Portable Appliance Tester ORDERING INFORMATION Item Cat. No. Item PAT450-US 1000-956 Optional Accessories Cat. No. Included Accessories Appliance bar-code labels (1-1000) 6121-483 Printed quick start guide Roll of 1000 FAIL test labels 1001-227 Full user guide on CD Roll of 1000 PASS test labels 1000-971 Calibration Certificate PAT accessory pouch 2001-044 Continuity / earth bond lead + probe (black) 2000-870 PAT test certificate book 1001-299 Extension lead adapter 2001-290 Screen protector (2) 1002-572 Flash lead 3.0 KV 3.5 mA (red) 5310-401 Carry case with lead/document pouch 2000-962 Plug adapter IEC C6 - C13 (3 way 5 A PSU) 2000-551 NOTE: The PAT450 will work with a BrotherTM P-touch(R) printer, 2430PC. Screen protector UK Archcliffe Road, Dover CT17 9EN England T +44 (0) 1 304 502101 F +44 (0) 1 304 207342 UKsales@megger.com United States 2621 Van Buren Avenue Norristown, PA 19403 USA T 1 866-254-0962 (USA only) T +1 610-676-8500 F +1 610-676-8625 VFCustomerSupport@megger.com (case sensitive email address) Other technical sales offices Dallas USA, College Station USA, Sydney AUSTRALIA, Danderyd SWEDEN, Ontario CANADA, Trappes FRANCE, Oberursel GERMANY, Aargau SWITZERLAND, Dubai UAE, Mumbai INDIA, Johannesburg SOUTH AFRICA, and Chonburi THAILAND ISO STATEMENT Registered to ISO 9001:2008 Reg no. Q 09250 Registered to ISO 14001 Reg no. EMS 61597 PAT450_DS_us_V03 www.megger.com Megger is a registered trademark Information contained herein is subject to change without notice