___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
SITOP power supply
Selectivity modules
Manual
SITOP select 4 x 10 A
6EP1961
-2BA00
SITOP PSE200U 4 x 3
A
6EP1961
-2BA11
6EP1961
-2BA31
6EP1961
-2BA51
6EP1961
-2BA61
SITOP PSE200U 4 x 10
A
6EP1961
-2BA21
6EP1961-2BA41
11.2017
C98130
-A7579-A1-3-7629
Overview
Safety notes
1
Description, device design,
dimension drawing
2
Mounting/removal
3
Mounting position, mounting
clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Environmental conditions
8
Environment
9
Service & Support
10
C98130-A7579-A1-3-7629
12/2017 Subject to change
Copyright © Siemens AG 2017.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 3
Overview
Description
Figure 1 View of devices
In conjunction with a 24 V power supply, the selectivity module is used to distribute the load
current across several branches and to monitor the individual currents in these branches.
Faults in the individual branches caused by overload or short-circuit are detected and
selectively switched off, so that the fault does not impact the other load circuits. This means
fast troubleshooting and minimized downtimes.
The key benefits of the product include:
A maximum of 4 load branches are monitored for each module
The response threshold can be continually set for each output using a potentiometer
Overcurrents are reliably switched off, independent of the cable length and cable cross-
section
The 24 V supply for the other loads is maintained
Multi-colored LED for each output for faster troubleshooting on-site
Floating group signal contact for remote diagnostics (for -2BA00, -2BA11, -2BA21,
-2BA51)
Single-channel signal to serially indicate the state of the individual outputs (for -2BA31,
-2BA41, -2BA61)
Overview
Selectivity modules
4 Manual, 11.2017, C98130-A7579-A1-3-7629
Evaluation using free-of-charge SIMATIC S7 function blocks (S7-300/400/1200/1500) for
modules with single channel signal
It can be selected that the load branches are sequentially switched on to reduce the total
inrush current
Versions for limited output power ratings according to NEC Class 2 (maximum, 100 VA).
Ordering data
The following device options are available:
Selectivity modules
Type
Order number
SITOP select
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 2 - 10 A
with group signaling contact
6EP1961-2BA00
SITOP PSE200U
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 0.5 - 3 A
with group signaling contact
6EP1961-2BA11
SITOP PSE200U
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 3 - 10 A
with group signaling contact
6EP1961-2BA21
SITOP PSE200U
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 0.5 - 3 A
with group signaling contact
6EP1961-2BA31
SITOP PSE200U
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 3 - 10 A
with group signaling contact
6EP1961-2BA41
Overview
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 5
Selectivity modules
Type
Order number
SITOP PSE200U
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 0.5 - 3 A
with group signaling contact, NEC Class 2
6EP1961-2BA51
SITOP PSE200U
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 0.5 - 3 A
with single-channel signal, NEC Class 2
6EP1961-2BA61
Accessories
Type
Order number
Flat insertable fuse: Manufacturer, Littelfuse,
series FKS, 19 mm long (for 6EP1961-2BA00)
162.6185.* (FKS-32), 166.7000.* (FKS-80)
Device name plate 20 mm × 7 mm, TI grey
(for 6EP1961-2BA11, -2BA21, -2BA31, -2BA41,
-2BA51, -2BA61)
3RT2900-1SB20
Validity
This manual provides information on the following products:
Selectivity module SITOP select 10 A
Article number: 6EP1961-2BA00
Product State: 4
Selectivity module SITOP PSE200U 3 A
Article number: 6EP1961-2BA11, 6EP1961-2BA31
Product state: 3
changes with respect to the previous version (PS: 2):
temperature range extended to -25 … 60 °C
terminal labeling changed from "NC" to "NF"
Selectivity module SITOP PSE200U 3 A NEC Class 2
Article number: 6EP1961-2BA51, 6EP1961-2BA61
Product state: 2
changes with respect to the previous version (PS: 1):
temperature range extended to -25 … 60 °C
terminal labeling changed from "NC" to "NF"
Selectivity module SITOP PSE200U 10 A
Article number: 6EP1961-2BA21, 6EP1961-2BA41
Product state: 3
changes with respect to the previous version (PS: 2):
temperature range extended to -25 … 60 °C
terminal labeling changed from "NC" to "NF"
Overview
Selectivity modules
6 Manual, 11.2017, C98130-A7579-A1-3-7629
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 7
Table of contents
Overview................................................................................................................................................. 3
1 Safety notes ............................................................................................................................................ 9
1.1 General safety instructions ....................................................................................................... 9
1.2 Safety instructions for hazardous zones ................................................................................... 9
2 Description, device design, dimension drawing...................................................................................... 11
2.1 Device description ................................................................................................................... 11
2.2 Connections and terminal designation.................................................................................... 12
2.3 Potentiometer .......................................................................................................................... 14
2.4 Status displays and signaling ................................................................................................. 15
2.5 Buttons and selector switches ................................................................................................ 19
2.5.1 SITOP select ........................................................................................................................... 19
2.5.2 SITOP PSE200U .................................................................................................................... 20
2.6 Electronic overload shutdown and reset ................................................................................. 21
2.6.1 SITOP select ........................................................................................................................... 21
2.6.2 SITOP PSE200U .................................................................................................................... 23
2.7 Setting the switch-on delay time ............................................................................................. 26
2.7.1 SITOP select ........................................................................................................................... 26
2.7.2 SITOP PSE200U .................................................................................................................... 28
2.8 Block diagram ......................................................................................................................... 29
2.9 Dimensions and weight ........................................................................................................... 31
3 Mounting/removal ................................................................................................................................. 33
4 Mounting position, mounting clearances ................................................................................................ 35
4.1 Standard mounting position .................................................................................................... 35
4.2 Other mounting positions ........................................................................................................ 37
4.2.1 6EP1961-2BA00 ..................................................................................................................... 37
4.2.2 6EP1961-2BA11, 6EP1961-2BA31, 6EP1961-2BA51 and 6EP1961-2BA61 ........................ 39
4.2.3 6EP1961-2BA21 and 6EP1961-2BA41 .................................................................................. 41
5 Installation ............................................................................................................................................ 43
5.1 Input side connection .............................................................................................................. 43
5.2 Output-side connection ........................................................................................................... 45
6 Technical data ...................................................................................................................................... 47
6.1 Input ........................................................................................................................................ 47
6.2 Output ..................................................................................................................................... 47
6.3 Efficiency ................................................................................................................................. 50
Table of contents
Selectivity modules
8 Manual, 11.2017, C98130-A7579-A1-3-7629
6.4 Protection and monitoring ...................................................................................................... 51
6.5 MTBF ..................................................................................................................................... 51
6.6 Mechanical system ................................................................................................................ 52
6.7 Accessories ............................................................................................................................ 53
6.8 Dimension drawing ................................................................................................................ 53
7 Safety, approvals, EMC ........................................................................................................................ 55
7.1 Safety ..................................................................................................................................... 55
7.2 Approvals ............................................................................................................................... 55
7.3 EMC ....................................................................................................................................... 56
8 Environmental conditions ...................................................................................................................... 57
9 Environment ......................................................................................................................................... 59
10 Service & Support ................................................................................................................................. 61
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 9
Safety notes
1
1.1
General safety instructions
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
1.2
Safety instructions for hazardous zones
WARNING
OPERATE POTENTIOMETERS OR SWITCHES IN NON-HAZARDOUS AREAS ONLY!
Safety notes
1.2 Safety instructions for hazardous zones
Selectivity modules
10 Manual, 11.2017, C98130-A7579-A1-3-7629
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 11
Description, device design, dimension drawing
2
2.1
Device description
Using the selectivity module, a 24 V DC output voltage from a regulated power supply can
be distributed across four load circuits. The response threshold of the output current can be
individually set for each output using a potentiometer. When the set response threshold is
exceeded, the output is automatically switched off according to a defined switch off
characteristic, and can be switched on again after a wait time using a pushbutton or remote
reset (SITOP PSE200U). The status of the output is displayed using a multi-color LED for
each output. The status of the outputs can be processed via a group signaling contact or via
a serial single-channel signal.
+24 V input
0 V connection for the internal supply
+24 V outputs
Group signal contact/status output/remote reset input
Potentiometer for each output
Button
Measuring point
Indicator light for each output
Natural convection
Clearance above/below
Selector switch for switch-on delay
Figure 2-1 Design
Description, device design, dimension drawing
2.2 Connections and terminal designation
Selectivity modules
12 Manual, 11.2017, C98130-A7579-A1-3-7629
2.2
Connections and terminal designation
The input terminals can be used to establish the connection to the supply voltage. The
0 V connection is used to supply the internal electronics. Output terminals are used to
connect to the loads to be supplied (also see Chapter Installation (Page 43)).
Using the group signal contact or status output , the operating state of the device can be
processed (function and contact rating, see Chapter Figure 2-4 Operating displays and
signaling (SITOP select and SITOP PSE200U) (Page 15)).
The remote reset input is used to reset outputs that have been automatically shut down
(function, see Chapter Status displays and signaling (Page 15)).
Connections and terminal designations for 6EP1961-2BA00
+ 24 V input 2 screw terminals
0 V connection 2 screw terminals
+ 24 V output: 1, 2, 3, 4 One screw terminal each
group signal contact (13, 14) One screw terminal each
Connections and terminal designations for 6EP1961-2BA11, 6EP1961-2BA21 and 6EP1961-2BA51
+ 24 V input 2 screw terminals
0 V connection 2 screw terminals
+ 24 V output: 1, 2, 3, 4 One screw terminal each
group signal contact (11, 12, 14);
remote reset (RST)
One screw terminal each
Connections and terminal designations for 6EP1961-2BA31, 6EP1961-2BA41 and 6EP1961-2BA61
+ 24 V input 2 screw terminals
0 V connection 2 screw terminals
+ 24 V output: 1, 2, 3, 4 One screw terminal each
not assigned (NF) 2 screw terminals
status output (S); remote reset (RST) One screw terminal each
Description, device design, dimension drawing
2.2 Connections and terminal designation
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 13
*1)
Do not subject the end stop to higher loads
Figure 2-2 Terminal data
NOTICE
Overload of the wiring
The "0 V" connection is only used to supply the internal electronics of the selectivity
module. The 0 V of the connected loads must be routed directly to the power supply using
separate cables!
Description, device design, dimension drawing
2.3 Potentiometer
Selectivity modules
14 Manual, 11.2017, C98130-A7579-A1-3-7629
2.3
Potentiometer
The potentiometer on the front of the device is used to set the response threshold of the
output current. When delivered, the maximum possible response threshold is set.
Figure 2-3 Potentiometer (SITOP select and SITOP PSE200U)
Note
It is only permissible to use an insulated screwdriver when actuating the potentiometer.
For information on actuating the potentiometer (screwdriver, torque), see Figure 2-2
Terminal data (Page 13).
Note
For SITOP PSE200U, the actual output current of a branch can be determined by measuring
the voltage at measuring point "MP"
with respect to the "0 V" terminal. A measured
voltage of 1
V corresponds to an output current of 1 A.
Description, device design, dimension drawing
2.4 Status displays and signaling
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 15
2.4
Status displays and signaling
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA51
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA61
Operating display
Two-color LED Three-color LED Three-color LED
Group signal contact
(13, 14 or 11, 12, 14)
floating relay contact (NO
contact),
contact rating:
24 V/0.5 A
floating relay contact
(changeover contact),
contact rating:
24 V/0.1 A
-
Status output (S)
- - non-isolated 24 V DC output,
max. 30 mA
Remote reset input (RST)
- non-isolated
24 V DC input
Signal level "High" for > 15 V
non-isolated
24 V DC input
Signal level "High" for > 15 V
Figure 2-4 Operating displays and signaling (SITOP select and SITOP PSE200U)
The operating state of the outputs is displayed using multi-color LEDs at the front of the
device. Symbols indicate the significance of each LED, which are listed in the following table.
LED off
LED is continuously lit
LED flashes
Description, device design, dimension drawing
2.4 Status displays and signaling
Selectivity modules
16 Manual, 11.2017, C98130-A7579-A1-3-7629
SITOP select
LED and group signaling contact
Signaling
6EP1961-2BA00
Off All LEDs:
No supply voltage
Device powering up: After the device has powered up, the outputs
are switched on, taking into consideration the switch-on delay that
has been set.
Lights up
green
Normal operation, output is switched on
Lights up red
Output switched off automatically to due overload
Flashes red
Outputs ready to be reset after an automatic switch off by pressing the
button
Light up red All LEDs are red (after actuating the reset button for a minimum of
8 s):
programming mode for the switch-on delay
Flashes red All LEDs flash red (in the programming mode):
signals the programmed switch-on delay time:
all LEDs flash 1x simultaneously red, followed by a 2 s pause:
0 ms
all LEDs flash 2x simultaneously red, followed by a 2 s pause:
24 ms
all LEDs flash 3x simultaneously red, followed by a 2 s pause:
100 ms
Group signaling contact (NO
contact)
Signal contact (13-14) opens (=quiescent position) when one/several
outputs are switched off as a result of overload or when a fuse rup-
tures.
Description, device design, dimension drawing
2.4 Status displays and signaling
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 17
SITOP PSE200U
LED and group signaling contact or status output
Signaling
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA51
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA61
Off All LEDs:
No supply voltage
Device powering up: After the device has powered up, the outputs are
switched on, taking into consideration the switch-on delay that has been
set.
Group signal: Inactive Status output1*: -
LED, individual output:
Output defective (internal fuse has ruptured)
Group signal: Inactive Status output1*: Ci = '0'
Lights
up
green
Normal operation, output is switched on
Group signal: Active Status output1*: Ci = '1'
Flash-
es
green
The output current is in the overload range according to the shutdown char-
acteristic (see Chapter SITOP PSE200U (Page 23))
-2BA11, -2BA21, -2BA31, -2BA41:
overload at the output: Output current 101 - 150 % of the response threshold
(for 5 s)
-2BA51, -2BA61:
overload at the output: Output current 101 - 110 % of the response threshold
(for 5 s)
Group signal: Active
Status output
1*
: Ci = '1'
Lights
up red
Output automatically shut down due to overload or external overvoltage > typ.
30 V/100 ms. The output can be switched on again after a typical wait time of
20 s. The wait time still to elapse is saved when switching off the device
and is reactivated after the device has been switched on again.
Group signal: Inactive
Status output
1*
: Ci = '0'
Flash-
es red
Output ready to be reset after an automatic switch off by actuating the button
or remote reset (effective for all outputs that have been automatically
switched off)
Group signal: Inactive Status output1*: Ci = '0'
Flash-
es
orange
Output manually switched off using the button: The state is saved when the
device is switched off, and can only be reset again by pressing the up button
again.
Group signal: Active
Status output
1*
: Ci = '0'
Red
running
light
Device overtemperature: The outputs can be switched-on again once the
temperature is in the normal range.
Group signal: Inactive
Status output
1*
: Ci = '0'
Group signaling con-
tact (changeover
contact)
In the "inactive" state, 11-12 are
connected and 11-14 open
-
Description, device design, dimension drawing
2.4 Status displays and signaling
Selectivity modules
18 Manual, 11.2017, C98130-A7579-A1-3-7629
Signaling
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA51
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA61
Status output - Serial signaling (see Figure 2-5 Status
signaling (Page 18)),
’1’ = 24 V DC / ’0’ = 0 V (pull down)
1* The status of all four outputs is serially signaled using status output (see Figure 2-5
Status signaling (Page 18)). A frame comprises a start bit START and four status bits Ci
(i=1 4), which are each separated by a pause bit P. While the device powers up, or if the
supply voltage is missing, nothing is signaled, the status remains continuously at ’0’. For
SIMATIC-S7 controllers (S7-300/400/1200/1500), a function block for evaluation is available
under (http://www.siemens.com/sitop) or the direct link
(https://support.industry.siemens.com/cs/us/en/view/61450284).
Figure 2-5 Status signaling
Description, device design, dimension drawing
2.5 Buttons and selector switches
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 19
2.5
Buttons and selector switches
2.5.1
SITOP select
Figure 2-6 Reset button SITOP select
The reset button for the SITOP select selectivity module has the following two functions:
1. resets all outputs automatically switched off due to an overload condition (see Chapter
Electronic overload shutdown and reset (Page 21)).
2. is used to program the sequential switch-on delay (see Chapter Setting the switch-on
delay time (Page 26).
Note
Switching off and switching on an output while commissioning the device
For selectivity module SITOP select, an output can be manually switched off and switched
on, e.g. during commissioning, by removing and inserting the flat f
use of the corresponding
output.
Description, device design, dimension drawing
2.5 Buttons and selector switches
Selectivity modules
20 Manual, 11.2017, C98130-A7579-A1-3-7629
2.5.2
SITOP PSE200U
Figure 2-7 Buttons and selector switches, SITOP PSE200U
The button for the SITOP PSE200U selectivity module has the following two functions:
1. manually switching an output off and on (see the following).
2. resetting an output automatically switched off due to an overload condition (see Chapter
Electronic overload shutdown and reset (Page 21)).
The selector switch can be used to select the delay time when switching on the individual
outputs (see Chapter Setting the switch-on delay time (Page 26)).
Manually switching an output on and off
An individual output can be switched on and switched off using the button. When the device
is delivered, the outputs are manually switched off.
Switching off an output:
For outputs that are switched on, LED of the particular output is lit green. You can switch
off the output by pressing the assigned button . The LED then flashes orange (output has
been manually switched off).
Switching on an output:
For outputs that have been manually switched off, LED of the particular output is lit
orange. You can switch on the output by pressing the assigned button . The LED is then
lit green (output is switched on).
Note
An output that has been manually switched
-off can only be manually switched-on again by
manual
ly pressing the button again. It is not possible to switch on an output that has been
manually switched off using the remote reset signal.
An output that has been manually switched off remains saved (latch) even when the supply
voltage is no longer availab
le, and is a manually switched off when the supply voltage
returns.
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 21
2.6
Electronic overload shutdown and reset
An overload is permitted for a defined period of time for each selectivity module output. The
output is electronically shut down according to the "Shutdown characteristic" diagram after
the limit value has been exceeded.
2.6.1
SITOP select
Figure 2-8 Shutdown characteristic SITOP select
An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
In the range 101 - 129 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down (LED of
the output is lit red).
In the range > 130 % of the selected current response threshold, the current is limited to
130 %, after approx. 50 - 100 ms the output is electronically shut down (LED of the output
is lit red).
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically shutdown
(the LED of the output is lit red).
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
Selectivity modules
22 Manual, 11.2017, C98130-A7579-A1-3-7629
Reset of an electronic overload shutdown using the reset button
Figure 2-9 Reset button SITOP select
Using the reset button , after a delay time has elapsed, outputs that have been shut down
due to an overload can be reset, i.e. the electronic shutdown can be reset.
The initial situation is an electronic shutdown of individual outputs as a result of an overload
condition. This is signaled using the LED of the particular output.
LED
Meaning/handling
Lit red
Electronic shutdown as a result of an overload; wait time until a reset is possible:
approx. 20 seconds.
Flashes red
Output ready for a reset; press the button to switch-on the output again.
Lit green
The reset was carried out, the output was switched-on again.
Procedure to reset an electronic shutdown:
1. After an electronic shutdown (LED of the output is lit red), allow a wait time of 20 seconds
to elapse.
2. Press the reset button
Electronic shutdown was reset, and the output has been switched-on again (LED of the
output is lit green).
Note
When pressing the button, all of the outputs shut down due to an overload, which are ready
for reset (LED flashes red), are switched
-in again together.
Note
If, after a reset, the cause of the overload is still present, then the output is again
automatically shut down. Before carrying out a reset, remove the cause of the overload to
prevent a new shutdown.
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 23
2.6.2
SITOP PSE200U
Shutdown characteristics SITOP PSE200U (with the exception of -2BA51, -2BA61) product
version 1:
Figure 2-10 Shutdown characteristics SITOP PSE200U (product version 1)
An output current is continuously permissible up to the selected current response
threshold.
In the range 101 - 129 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down.
In the range > 130 % of the selected current response threshold, the current is limited to
130 %; typically after 100 ms the output is electronically shut down.
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically
shutdown.
Shutdown characteristic SITOP PSE200U (with the exception of -2BA51, -2BA61) from
product version 2 and higher:
Figure 2-11 Shutdown characteristics SITOP PSE200U (from product version 2 and higher)
An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
An overload current for 5 seconds is permissible in the range 101 - 149 % of the set
current response threshold value (the LED of the output flashes green) - and then the
output is electronically shut down (LED of the output is red).
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
Selectivity modules
24 Manual, 11.2017, C98130-A7579-A1-3-7629
In the range > 150 % of the selected current response threshold, the current is limited to
150 %, typically after 100 ms, the output is electronically shut down (LED of the output is
lit red).
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically shutdown
(the LED of the output is lit red).
Shutdown characteristic 6EP1961-2BA51, -2BA61:
Figure 2-12 Shutdown characteristic 6EP1961-2BA51, -2BA61
An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
An overload current for 5 seconds is permissible in the range 101 - 109 % of the set
current response threshold value (the LED of the output flashes green) - and then the
output is electronically shut down (LED of the output is red).
In the range > 110 % of the selected current response threshold, the current is limited to
110 %, typically after 100 ms, the output is electronically shut down (LED of the output is
lit red).
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically shutdown
(the LED of the output is lit red).
Reset of an electronic overload shutdown using the reset button and remote reset
Figure 2-13 SITOP PSE200U button
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 25
An individual output can be reset using the button. This resets the electronic shutdown of the
output, caused by an overload condition.
The initial situation is an electronic shutdown of individual outputs as a result of an overload
condition. This is signaled using the LED of the particular output.
LED
Meaning/handling
Lit red
Electronic shutdown as a result of an overload; wait time until a reset is possible:
approx. 20 seconds.
Flashes red Output ready for a reset; press the button to switch-on the output again.
Lit green
The reset was carried out, the output was switched-on again.
Procedure to reset an electronic shutdown:
1. After an electronic shutdown (LED of the output is lit red), allow a wait time of 20 seconds
to elapse.
2. Press the reset button of the particular output
Electronic shutdown was reset, and the output has been switched-on again (LED of the
output is lit green).
Remote reset:
Alternatively, a remote reset signal can be used. The non-isolated 24 V input (referred to the
"0 V" terminal of the module) can be used at terminal "RST". A reset is executed for an input
level of > 15 V.
Note
The rising edge of the remote reset signal is evaluated, i.e. for an additional remote reset
signal, initially a voltage level of 13
V must be fallen below.
Using a remote reset signal at terminal "RST" all outputs that were shut down electronically
due to an overload are reset at this time. Prerequisite: The output is ready to be reset, i.e.
the electronic overload shutdown occurred longer than 20 s ago (LED of the output flashes
red).
Note
If, after a reset, the cause of the overload is still present, then the output is again
automatically shut down. Before carrying out a reset, remove the cause of the overload to
prevent a new shutdown.
Description, device design, dimension drawing
2.7 Setting the switch-on delay time
Selectivity modules
26 Manual, 11.2017, C98130-A7579-A1-3-7629
2.7
Setting the switch-on delay time
For specific loads, it can make sense to sequentially switch-on the outputs in order to reduce
the peak inrush currents, and therefore the load on the power supply. To achieve this, the
individual outputs of the selectivity module can be switched-in with a time delay between one
another in a fixed sequence (output 1 ⇒ 2 ⇒ 3 ⇒ 4). The delay time set between the
individual outputs is the same for all of the outputs. When supplied, the delay time is set to
0 ms (all outputs switch on simultaneously).
2.7.1
SITOP select
Figure 2-14 Reset button SITOP select
Programming the sequential switch-on delay
For specific loads, it can make sense to sequentially switch-on the outputs in order to reduce
the peak inrush currents, and therefore the load on the power supply. To achieve this, the
individual outputs of the selectivity module can be switched-in with a time delay between one
another in a fixed sequence (output 1 ⇒ 2 ⇒ 3 ⇒ 4). The delay time between the individual
outputs is the same for all outputs, and can be set to 0 ms, 24 ms or 100 ms. The selected
setting is also kept for an unlimited time even when the power fails, and can be changed as
often as required. When supplied, the delay time is set to 0 ms (all outputs switch on
simultaneously).
Description, device design, dimension drawing
2.7 Setting the switch-on delay time
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 27
Procedure when setting the delay time:
1. Keep the reset button pressed for approximately 8 seconds. The selectivity module
changes into the programming mode, all LEDs are lit red and the outputs are shut down.
2. Release the reset button. The LEDs signal the selected delay time using a specific flash
rhythm. The meaning is as follows:
LED
Meaning
flash 1x simultaneously red, followed by a 2 s pause
Delay time of 0 ms selected
flash 2x simultaneously red, followed by a 2 s pause
Delay time of 24 ms selected
flash 3x simultaneously red, followed by a 2 s pause
Delay time of 100 ms selected
The flashing rhythm is repeated after a pause of approx. 2 s.
3. Briefly press the reset button; this causes the actual setting to be moved forward by one
stage (0 ms ⇒ 24 ms ⇒ 100 ms ⇒0 ms). Press the reset button several times until the
required setting is signaled.
4. Then keep the reset button pressed for approximately 8 seconds. All LEDs light up red.
5. Release the reset button. The selectivity module saves the delay time that has been set
and sequentially switches on the outputs.
The LEDs of the outputs are lit green, and the selectivity module is again in its normal
operating mode.
Note
In the programming mode, if the reset button is not pressed within 30
s, then the selectivity
module automatically returns to the normal operating state without saving any change made
to the delay time. The setting is also not saved if, while program
ming, the supply voltage
fails.
Note
The selectivity module outputs are shut down while programming, and are automatically
switched
-on again after the programming mode is either manually or automatically exited.
They are also automatically switched on
again after the voltage returns after a power failure!
Description, device design, dimension drawing
2.7 Setting the switch-on delay time
Selectivity modules
28 Manual, 11.2017, C98130-A7579-A1-3-7629
2.7.2
SITOP PSE200U
Figure 2-15 SITOP PSE200U selector switch
Setting the sequential switch-on delay
The switch-on delay is set at selector switch . When delivered, DIP switches "A" and "B"
are in position "0" (no switch-on delay).
Procedure when setting the delay time:
With the selectivity module in a no-voltage condition, set DIP switches "A" and "B" to the
required delay time.
No delay, all four outputs are simultaneously switched-on (condition when delivered).
25 ms delay between the outputs being switched on.
100 ms delay between the outputs being switched on.
Outputs switched on depending on the load: The next output is switched on as soon as the
current of the previous output lies below the selected response threshold.
The next time that the selectivity module powers up, the outputs are sequentially switched on
corresponding to the selected delay time.
Description, device design, dimension drawing
2.8 Block diagram
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 29
2.8
Block diagram
Figure 2-16 Block diagram of the 6EP1961-2BA00
Figure 2-17 Block diagram for 6EP1961-2BA11, 6EP1961-2BA21 and 6EP1961-2BA51
Description, device design, dimension drawing
2.8 Block diagram
Selectivity modules
30 Manual, 11.2017, C98130-A7579-A1-3-7629
Figure 2-18 Block diagram 6EP1961-2BA31, 6EP1961-2BA41 and 6EP1961-2BA61
Description, device design, dimension drawing
2.9 Dimensions and weight
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 31
2.9
Dimensions and weight
Figure 2-19 Dimension drawing 6EP1961-2BA00
Figure 2-20 Dimension drawing 6EP1961-2BA*1
Description, device design, dimension drawing
2.9 Dimensions and weight
Selectivity modules
32 Manual, 11.2017, C98130-A7579-A1-3-7629
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA21
6EP1961-2BA41
6EP1961-2BA51
6EP1961-2BA61
Dimensions (W × H × D) in mm
72 × 90 × 88.7
72 × 80 × 65
Weight
Approx. 0.4 kg
Approx. 0.2 kg
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 33
Mounting/removal
3
WARNING
Installing the device in a housing or a control cabinet
The SITOP select and SITOP PSE200U selectivity modules are built-in units. They must be
installed in a housing or control cabinet where only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails (see Chapter
Mechanical system (Page 52))
Mounting
To mount the device, position it with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place. If it is too difficult to snap them
into place, press slider at the same time, as described under "Removal".
Removal
To remove the device, pull slider using a screwdriver (see Figure 3-1
Mounting/removal (example): 6EP1961-2BA11) (Page 33)) and detach it at the lower edge of
the standard mounting rail. Then you can remove the device from the upper edge of the
standard mounting rail.
Figure 3-1 Mounting/removal (example): 6EP1961-2BA11)
Mounting/removal
Selectivity modules
34 Manual, 11.2017, C98130-A7579-A1-3-7629
WARNING
Use in hazardous zones
If the device is installed in a hazardous zone (II 3G Ex nA nC IIC T4 Gc (-2BA11, -2BA21,
-2BA51) / II 3G Ex nA IIC T4 Gc (-2BA31, -2BA41, -2BA61)), then it must be installed in a
distribution box with degree of protection IP54 or higher.
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 35
Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails. The device must be mounted vertically in
such a way that the input terminals are at the bottom.
A clearance of at least 50 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.
Individual output current as a function of the ambient temperature and installation altitude
Figure 4-1 6EP1961-2BA00: Output current in the standard mounting position
Figure 4-2 6EP1961-2BA11, 6EP1961-2BA31, 6EP1961-2BA51 and 6EP1961-2BA61 output
current in the standard mounting position
Mounting position, mounting clearances
4.1 Standard mounting position
Selectivity modules
36 Manual, 11.2017, C98130-A7579-A1-3-7629
Figure 4-3 6EP1961-2BA21 and 6EP1961-2BA41: Output current in the standard mounting position
Figure 4-4 Mounting height derating
Mounting position, mounting clearances
4.2 Other mounting positions
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 37
4.2
Other mounting positions
For mounting positions that deviate from the standard mounting position, derating factors
(reduction of the output power or the permissible ambient temperature) must be observed in
accordance with the following diagrams.
Note
In the case of mounting positions that deviate from the standard mounting position, reduced
mechanical resistance of the devices against vibration and shock
must be expected.
Particularly when installing on a vertically fastened standard mounting rail, additional
measures may be required, e.g. to prevent the device from slipping on the standard
mounting rail.
4.2.1
6EP1961-2BA00
Figure 4-5 Mounting position (1)
Figure 4-6 Mounting position (2)
Mounting position, mounting clearances
4.2 Other mounting positions
Selectivity modules
38 Manual, 11.2017, C98130-A7579-A1-3-7629
Figure 4-7 Mounting position (3)
Figure 4-8 Mounting position (4)
Figure 4-9 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 39
4.2.2
6EP1961-2BA11, 6EP1961-2BA31, 6EP1961-2BA51 and 6EP1961-2BA61
Figure 4-10 Mounting position (1)
Figure 4-11 Mounting position (2)
Figure 4-12 Mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
Selectivity modules
40 Manual, 11.2017, C98130-A7579-A1-3-7629
Figure 4-13 Mounting position (4)
Figure 4-14 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 41
4.2.3
6EP1961-2BA21 and 6EP1961-2BA41
Figure 4-15 Mounting position (1)
Figure 4-16 Mounting position (2)
Figure 4-17 Mounting position (3)
Mounting position, mounting clearances
4.2 Other mounting positions
Selectivity modules
42 Manual, 11.2017, C98130-A7579-A1-3-7629
Figure 4-18 Mounting position (4)
Figure 4-19 Mounting position (5)
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 43
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Input side connection
WARNING
The device is only suitable for operation with
24 V DC voltages
(safety extra low voltage). If
this device is connected to line supplies with higher voltage levels this can result in death or
serious injury as well as extensive material damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Figure 5-1 Input connection
Installation
5.1 Input side connection
Selectivity modules
44 Manual, 11.2017, C98130-A7579-A1-3-7629
The supply is connected via input terminal , designated "24 V" and the 0 V terminal ,
designated "0 V"; the "0 V" connection is not used for the load supply, but only to supply the
internal electronics of the selectivity module (terminal cross-sections, see Figure 2-2
Terminal data (Page 13)).
NOTICE
Overload of the wiring
The "0 V" connection is only used to supply the internal electronics of the selectivity
module. The 0 V of the connected loads must be routed directly to the power supply using
separate cables!
NOTICE
Overload of the wiring
The input terminals of the selectivity module are designed for a maximum input current of
40 A. This must be taken into account when connecting several selectivity modules in
parallel using "loop through". If the total current demand of all selectivity modules
connected in parallel is more than 40 A, then the maximum current should be reduced to
40 A per branch by using additional feeder cables directly from the power supply to the
selectivity modules connected in parallel.
Installation
5.2 Output-side connection
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 45
5.2
Output-side connection
(see Chapter Technical data (Page 47))
Figure 5-2 Output connection
The load to be supplied is connected through output terminals labeled OUT 1, 2, 3, 4.
(terminal cross-sections, see Figure Terminal data (Page 13)).
Note
The 0
V of the loads must be routed directly to the power supply using separate cables!
Installation
5.2 Output-side connection
Selectivity modules
46 Manual, 11.2017, C98130-A7579-A1-3-7629
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 47
Technical data
6
Note
Technical data apply for a rated input voltage, rated load and 25
°C ambient temperature if
nothing else i
s specified.
6.1
Input
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA51
6EP1961-2BA61
6EP1961-2BA21
6EP1961-2BA41
Input
Regulated DC voltage
1*)
Regulated DC voltage
Regulated DC voltage
Rated voltage U
in rated
24 V
24 V
24 V
Voltage range
22 - 30 V
22 - 30 V
22 - 30 V
Overvoltage strength 35 V; 100 ms 35 V 35 V
Input current at Uin rated 40 A 12 A 40 A
1*) SITOP select (6EP1961-2BA00) cannot be operated with the DC-UPS module 40 A
(6EP1931-2FC21/-2FC42).
6.2
Output
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA51
6EP1961-2BA61
6EP1961-2BA21
6EP1961-2BA41
Output
Regulated DC voltage
Regulated DC voltage
Regulated DC voltage
Output voltage
Uin - approx. 0.3 V
Uin - approx. 0.2 V
Uin - approx. 0.2 V
Total tolerance Corresponding to the supply-
ing input voltage
Corresponding to the supply-
ing input voltage
Corresponding to the supply-
ing input voltage
Number of outputs
4
4
4
Output current up to 60 °C
for each output (rated value)
10 A 3 A 10 A
Technical data
6.2 Output
Selectivity modules
48 Manual, 11.2017, C98130-A7579-A1-3-7629
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA51
6EP1961-2BA61
6EP1961-2BA21
6EP1961-2BA41
Adjustable response thresh-
old
2 - 10 A
0.5 - 3 A 3 - 10 A
Connecting outputs in paral-
lel
No
No No
Switching on outputs All outputs are simultaneous-
ly switch on after the supply
voltage has ramped up,
delay time of 24 ms or
100 ms can be programmed
for outputs to be sequentially
switched on.
All outputs are simultaneously switched-on after the supply
voltage ramps up > 20 V, delay time of 25 ms, 100 ms – or
"load optimized" where the outputs are sequentially
switched-on, selected using the DIP switch.
Shutdown characteristics SITOP select:
Figure 6-1 Shutdown characteristic SITOP select
An output current is continuously permissible up to the selected current response
threshold.
In the range 101 - 129 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down.
In the range > 130 % of the selected current response threshold, the current is limited to
130 %; after approximately 50 - 100 ms, the output is electronically shut down.
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically
shutdown.
Technical data
6.2 Output
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 49
Shutdown characteristics SITOP PSE200U (with the exception of -2BA51, -2BA61) product
version 1:
Figure 6-2 Shutdown characteristics SITOP PSE200U (product version 1)
An output current is continuously permissible up to the selected current response
threshold.
In the range 101 - 129 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down.
In the range > 130 % of the selected current response threshold, the current is limited to
130 %; typically after 100 ms the output is electronically shut down.
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically
shutdown.
Shutdown characteristics SITOP PSE200U (with the exception of -2BA51, -2BA61) from
product version 2 and higher:
Figure 6-3 Shutdown characteristics SITOP PSE200U (from product version 2 and higher)
An output current is continuously permissible up to the selected current response
threshold.
In the range 101 - 149 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down.
Technical data
6.3 Efficiency
Selectivity modules
50 Manual, 11.2017, C98130-A7579-A1-3-7629
In the range > 150 % of the selected current response threshold, the current is limited to
150 %; typically after 100 ms the output is electronically shut down.
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically
shutdown.
Shutdown characteristic 6EP1961-2BA51, -2BA61:
Figure 6-4 Shutdown characteristic 6EP1961-2BA51, -2BA61
An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
In the range 101 - 109 % of the selected current response threshold, an overload current
is permissible for 5 seconds (LED of the output flashes green), then the output is
electronically shut down (LED of the output is lit red).
In the range > 110 % of the selected current response threshold, the current is limited to
110 %, typically after 100 ms, the output is electronically shut down (LED of the output is
lit red).
When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically shutdown
(the LED of the output is lit red).
6.3
Efficiency
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA51
6EP1961-2BA61
6EP1961-2BA21
6EP1961-2BA41
Efficiency at U
out rated
, I
out rated
, approx.
97 %
97 %
99 %
Power loss at U
out rated
, I
out rated
, approx.
30 W
9 W
10 W
Technical data
6.4 Protection and monitoring
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 51
6.4
Protection and monitoring
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA51
6EP1961-2BA21
6EP1961-2BA31
6EP1961-2BA61
6EP1961-2BA41
Device protection Flat fuse for each
output (a 15 A
fuse is inserted
when the device is
shipped)
1*)
Internal fuse 5 A
for each output
(not accessible)
Internal fuse 15 A
for each output
(not accessible)
Internal fuse 5 A
for each output
(not accessible)
Internal fuse 15 A
for each output
(not accessible)
Operating display One LED per
output: Green LED
for "Output
switched through",
red LED for "Out-
put shutdown due
to overcurrent"
One LED per output: Green LED for "Output switched through", orange LED for
"Output manually switched off", red LED for "Output shutdown due to overcur-
rent".
Signaling Group signaling
contact (NO con-
tact, contact rating
0.5 A/24 V)
Group signaling contact (changeover
contact, contact rating 0.1 A/24 V)
Status signal output (pulse position
signal that can be evaluated using a
Simatic function block)
1*)
Note for 6EP1961-2BA00:
When required, depending on the potentiometer setting, lower fuse values can be selected.
Setting to → fuse from
2 A → 3 A
3 A → 4 A
4 A → 5 A
6 A → 7.5 A
8 A → 10 A
10 A → 15 A
6.5
MTBF
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA51
6EP1961-2BA61
Mean Time Between Failures
> 500,000 hours at 40 °C, rated load, 24 hour operation
Technical data
6.6 Mechanical system
Selectivity modules
52 Manual, 11.2017, C98130-A7579-A1-3-7629
6.6
Mechanical system
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA51
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA61
Connection system
Screw connection
Screw connection
Screw connection
+24 V input 2 screw terminals for
0.5 - 16 mm²
2 screw terminals for
0.5 - 16 mm²
2 screw terminals for
0.5 - 16 mm²
0 V connection 2 screw terminals for
0.2 - 6 (4) mm² solid (finely
stranded)
2 screw terminals for
0.2 - 6 (4) mm² solid (finely
stranded)
2 screw terminals for
0.2 - 6 (4) mm² solid (finely
stranded)
Output 1, 2, 3, 4
One screw-type terminal for
each output for 0.2 - 6 (4)
mm² solid (finely stranded)
One screw-type terminal for
each output for 0.2 - 6 (4)
mm² solid (finely stranded)
One screw-type terminal for
each output for 0.2 - 6 (4)
mm² solid (finely stranded)
Group signal contact 2 screw terminals for
0.2 - 6 (4) mm² solid (finely
stranded)
3 screw terminals for
0.2 - 6 (4) mm² solid (finely
stranded)
-
Status output - - One screw terminal for
0.2 - 6 (4) mm² solid (finely
stranded)
Remote reset - One screw terminal for
0.2 - 6 (4) mm² solid (finely
stranded)
One screw terminal for
0.2 - 6 (4) mm² solid (finely
stranded)
Width of the housing
72 mm
72 mm
72 mm
Height of the housing
90 mm
80 mm
80 mm
Depth of the housing approx. 90 mm 72 mm 72 mm
Installation width 72 mm 72 mm 72 mm
Mounting height 190 mm 180 mm 180 mm
Weight, approx. 0.4 kg 0.2 kg 0.2 kg
Mounting
Can be snapped onto standard TH35-15/7,5 mounting rails (EN 60715)
Technical data
6.7 Accessories
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 53
6.7
Accessories
Accessories
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA51
6EP1961-2BA61
Electrical accessories Flat insertable fuse: Manufacturer,
Littelfuse, FKS series, 19 mm long
-
Mechanical accessories - Device name plate 20 mm x 7 mm
TI grey 3RT2900-1SB20
6.8
Dimension drawing
See chapter Dimensions and weight (Page 31)
CAD data that can be downloaded from the Internet:
6EP1961-2BA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00575)
6EP1961-2BA11
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00423)
6EP1961-2BA21
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00427)
6EP1961-2BA31
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00742)
6EP1961-2BA41
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00745)
6EP1961-2BA51
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01240)
6EP1961-2BA61
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01241)
Technical data
6.8 Dimension drawing
Selectivity modules
54 Manual, 11.2017, C98130-A7579-A1-3-7629
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 55
Safety, approvals, EMC
7
7.1
Safety
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA51
6EP1961-2BA61
Standard for safety
acc. to EN 60950-1 and EN 50178
Protection class Class III
7.2
Approvals
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA51
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA61
CE marking Yes Yes Yes
Degree of protection (EN
60529)
IP20 IP20 IP20
UL/cUL (CSA) approval
Remark:
UL-Recognized (UL 2367)
File E328600; cULus (UL
508, CSA C22.2 No. 107.1)
File E197259; cURus (UL
60950, CSA C22.2 No.
60950) File E151273
UL-Recognized (UL 2367) File E328600; cULus (UL 508,
CSA C22.2 No. 107.1) File E197259
The combination of the listed Siemens AG power supply
and solid-state overcurrent protector models 6EP1961,
followed by -2BA51 or -2BA61 additionally create a limited
voltage/current circuit.
Devices 6EP1961-2BA51 and -2BA61 additionally fulfill the
conditions for "Class 2 output" according to UL 1310 (maxi-
mum 100 VA)
Explosion protection
ATEX (EX) II 3G Ex nA nC
IIC T4 Gc
cCSAus Class I, Div. 2,
Group A,B,C,D, T4
ATEX (EX) II 3G Ex nA nC
IIC T4 Gc
cCSAus Class I, Div. 2,
Group A,B,C,D, T4
ATEX (EX) II 3G Ex nA IIC
T4 Gc
cCSAus Class I, Div. 2,
Group A,B,C,D, T4
Marine approvals
-
DNV-GL, ABS
DNV-GL, ABS
Safety, approvals, EMC
7.3 EMC
Selectivity modules
56 Manual, 11.2017, C98130-A7579-A1-3-7629
7.3
EMC
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA51
6EP1961-2BA61
Emitted interference
EN 55022 Class B
Noise immunity
EN 61000-6-2
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 57
Environmental conditions
8
6EP1961-2BA00
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA51
6EP1961-2BA61
Ambient temperature
-25 … 60 °C for natural convection
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Transport and storage temperature -40 … 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
Degree of pollution
2
Mechanical stressing in operation Tested according to EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 8.4 Hz
2 g acceleration in the range 8.4 - 150 Hz
Tested according to EN 60068-2-27 shock, test Ea:
acceleration 150 m/s2, test duration 11 ms
Damaging gases Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
1080 - 795 hPa (-1000 - 2000 m)
For operation at altitudes of 2000 - 6000 m above sea level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
(see Figure 4-4 Mounting height derating (Page 36))
Storage:
1080 - 660 hPa (-1000 - 3500 m)
Environmental conditions
Selectivity modules
58 Manual, 11.2017, C98130-A7579-A1-3-7629
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 59
Environment
9
The devices are in conformance with RoHS.
As a rule, only non-silicon precipitating materials are used.
Disposal guidelines
Packaging and packaging aids can and should always be recycled. The product itself may
not be disposed of as domestic refuse.
Environment
Selectivity modules
60 Manual, 11.2017, C98130-A7579-A1-3-7629
Selectivity modules
Manual, 11.2017, C98130-A7579-A1-3-7629 61
Service & Support
10
Technical support
Technical support for all IA/DT products can be accessed through the following
communication channels:
Telephone: + 49 (0) 911 895 7222
Internet:
Web form for support request (http://www.siemens.de/automation/support-request)
Technical documentation on the Internet
Operating instructions and manuals for SITOP are available in the Internet:
Operating instructions/manuals (http://www.siemens.com/sitop/manuals)
SITOP power supply homepage
General news about our power supplies is available in the Internet at the SITOP home page:
SITOP (http://www.siemens.com/sitop)
Information material
SITOP information can be downloaded from the Internet:
Information and download center (http://www.siemens.com/sitop-infomaterial)
CAx data
2D/3D data and circuit diagram macros can be downloaded from the Internet:
Siemens image database (http://www.siemens.com/sitop-cax)
Request all CAx data via the CAx download manager:
CAx shopping cart (http://www.siemens.com/cax)
SITOP Selection Tool
Simply and quickly select the optimum the power supply or DC-UPS:
SITOP Selection Tool (http://www.siemens.com/sitop-selection-tool)
Online catalog and ordering system
The online catalog and the online ordering system are available through the Industry Mall
homepage:
Industry Mall (http://www.siemens.com/industrymall/de)
Service & Support
Selectivity modules
62 Manual, 11.2017, C98130-A7579-A1-3-7629
Contact persons
If you have any questions regarding the use of our products, then contact the Siemens
contact person in your regional Siemens sales office.
You can find these addresses as follows:
On the Internet (http://www.automation.siemens.com/partner)
Industry Mall (http://www.siemens.com/industrymall/de)