Product data sheet
Characteristics
TVS4HWA50X
Surge Protect - HWA - 50kA - 480Y/277VAC -
3P4W - T4X
Product availability : Stock - Normally stocked in distribution facility
Price* : 2,640.00 USD
Main
Product Surge protection device
Range Surgelogic
Device Short Name HWA
Complementary
Surge Current 50 kA per phase
System Voltage 480Y/277 V AC
Phase 3 phases
Wiring Configuration 4-wire
Connection Wire phase and neutral AWG 10 copper
Wire ground AWG 10 copper
Wire dry contacts AWG 22 copper
MCOV 320 V
Nominal Discharge Current 20 kA
SCCR 200 kA
Local Signalling Status LED, green = normal operation per phase
Status LED, red = fault per phase
Alarm = fault
Mounting Location Bottom of enclosure
Device Mounting Surface
Flush with fixing kit
Height 4.8 in (122 mm)
Width 8.62 in (219 mm)
Depth 3.11 in (79 mm)
Environment
Enclosure Rating NEMA 4X
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Jul 13, 2019
1
Enclosure Material Plastic, colour : black
Standards CSA C22.2 No 8 1986
UL 1283 ed. 5
UL 1449 ed. 4
Ambient Operating 149 °F (65 °C)
Ordering and shipping details
Category 08466 - SURGE PROTECTION HWA
Discount Schedule DE1B
GTIN 00785901406242
Nbr. of units in pkg. 1
Package weight(Lbs) 5.1500000000000004
Returnability Y
Country of origin US
Offer Sustainability
RoHS (date code: YYWW) Compliant - since 1743 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP which is known to the State of California to cause cancer and
- - - - - - - Substance 2 DIDP which is known to the State of California to cause birth defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
2