SP-750 750W Single Output Power Supply series Features : Universal AC input / Full range AC input active surge current limiting Built-in active PFC function,PF>0.96 Protections: Short circuit / Overload / Over voltage / Over temperature Forced air cooling by built-in DC ball bearing fan High power density 5.48/inch3 Built-in constant current limiting circuit With power good and fail signal output Built-in remote ON-OFF control Built-in remote sense function 3 years warranty SPECIFICATION MODEL OUTPUT SP-750-5 SP-750-12 SP-750-15 SP-750-24 SP-750-27 SP-750-48 DC VOLTAGE 5V 12V 15V 24V 27V 48V RATED CURRENT 120A 62.5A 50A 31.3A 27.8A 15.7A CURRENT RANGE 0 ~ 120A 0 ~ 62.5A 0 ~ 50A 0 ~ 31.3A 0 ~ 27.8A 0 ~ 15.7A RATED POWER 600W 750W 750W 751.2W 750.6W 753.6W RIPPLE & NOISE (max.) Note.2 120mVp-p 120mVp-p 120mVp-p 120mVp-p 120mVp-p 120mVp-p VOLTAGE ADJ. RANGE 10 ~ 13.5V 13.5 ~ 16.5V 22 ~ 26.4V VOLTAGE TOLERANCE Note.3 INPUT 4.75 ~ 5.5V 2.0% 43 ~ 56V 1.0% 1.0% 1.0% 1.0% LINE REGULATION 0.5% 0.3% 0.3% 0.2% 0.2% 0.2% LOAD REGULATION 2.0% 0.5% 0.5% 0.5% 0.5% 0.5% SETUP, RISE TIME 1500ms, 50ms/230VAC HOLD UP TIME (Typ.) 16ms/230VAC VOLTAGE RANGE 90 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) PF>0.96/230VAC EFFICIENCY (Typ.) AC CURRENT (Typ.) 80% INRUSH CURRENT (Typ.) LEAKAGE CURRENT <2.0mA / 240VAC 85 OVER TEMPERATURE 87% 89% 5 89% 90% 31 ~ 36.5V 57.6 ~ 67.2V 4.2A/230VAC 45A/230VAC (TSW1 ) detect on heatsink of power transistor 85 5 (TSW2 ) detect on heatsink of power diode 50ms/1ms Note.5 RC+/RC- short power on, open power off WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY SAFETY STANDARDS WITHSTAND VOLTAGE PF>0.99/115VAC at full load Protection type : Shut down o/p voltage, recovers automatically after temperature goes down POWER GOOD/FAIL TEMP. COEFFICIENT VIBRATION 16ms/115VAC at full load 127 ~ 370VDC 105 ~ 125% rated output power Protection type : Constant current limiting, unit will Hiccup after 3 sec. 5.75 ~ 6.75V 13.8 ~ 16.2V 18 ~ 21V 27.6 ~ 32.4V Protection type : Shut down o/p voltage, re-power on to recover PROTECTION OVER VOLTAGE REMOTE CONTROL 1500ms, 50ms/115VAC at full load 85% 8.8A/115VAC 27A/115VAC OVERLOAD FUNCTION 24 ~ 30V 1.0% -20 ~ +60 (Refer to output load derating curve) 20~90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH 0.05%/ (0 ~ 50 ) 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes UL60950-1, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC SAFETY & ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC EMC EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), EN55022 (CISPR22) Class B (Note 4) HARMONIC CURRENT EMS IMMUNITY MTBF OTHERS DIMENSION PACKING NOTE Compliance to EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A 124K hrs min. MIL-HDBK-217F (25 278*127*63.5mm (L*W*H) 2.9Kg; 6pcs / 18.4Kg / 0.98CUFT ) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. The power supply unit will have no output if the shorting connector is not assembled between RC+ & RC-. File Name:SP-750-SPEC 2008-07-21 SP-750 750W Single Output Power Supply Mechanical Specification Case No.919A 220 series Unit:mm 113 16 5 30 20 4-M3 7 6-M3 L=6 149 4-M3 Air flow direction O/P 5 CONTROL 33 11 72 24.5 91 240 251 278 2 1 2 3 4 40.5 5 6 7 8 +V ADJ. 1 2 3 7 7 10 39 113 127 1 I/P 19 max. 4-M3 28 max. 220 34.5 20 63.5 20 max. 2-M6 15 BOTTOM VIEW TOP VIEW AC Input Terminal Pin No. Assignment Pin No. 1 2 3 Assignment AC/L AC/N FG DC Output Terminal Pin No. Assignment Pin No. 1 2 Assignment DC OUTPUT +V DC OUTPUT -V Control Pin No. Assignment : MOLEX 5559-NP uses 5558male crimp terminal Pin No. 1 2 3 4 Assignment NC -S G RC- Pin No. Assignment Mating connector Terminal NC 5 MOLEX 5556 6 PF(Power fail signal) MOLEX 5557-NR Female crimp Terminal +S 7 receptacle RC+ 8 Block Diagram PFC fosc : 100KHz PWM fosc : 140KHz +S I/P EMI FILTER ACTIVE INRUSH CURRENT LIMITING RECTIFIERS PWM POWER SWITCHING PFC POWER SWITCHING DETECTION CIRCUIT PFC CONTROL RECTIFIERS & FILTER O.T.P. CURRENT LIMIT +V -V -S O.L.P. DETECTION CIRCUIT PWM CONTROL PF O.V.P. O.T.P. REMOTE CONTROL AUX POWER FAN RC FAN LOCK PROTECTION File Name:SP-750-SPEC 2008-07-21 SP-750 750W Single Output Power Supply Derating Curve series Static Characteristics 100 100 90 80 85 70 LOAD (%) LOAD (%) 60 40 20 -20 60 50 40 0 10 20 30 40 50 60 70 (HORIZONTAL) 90 95 100 115 260 INPUT VOLTAGE (VAC) 60Hz AMBIENT TEMPERATURE ( ) Control Terminal Instruction Manual Remote Sensing Power Fail Signal PF Signal is the voltage difference between "G" and "PF" pin output G PF RC+ +S PF NC RC+ +S PF NC RC- G RC- G -S NC -V -S NC +V LOAD + +V -V -S LOAD + +S Remote Control Power ON: RC+/RC- Short Power OFF: RC+/RC- open RC- RC+ RC+ +S PF NC RC- G -S NC +V -V LOAD + File Name:SP-750-SPEC 2008-07-21