PHOENIX CONTACT Ltd Page 1 / 7
http://www.phoenixcontact.co.uk 20-Jan-2012
Extract from the online
catalog
QUINT-PS-100-240AC/24DC/40
Order No.: 2938879
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2938879
DIN rail power supply unit 24 V DC/40 A, primary switched-mode, 1-
phase.
Commercial data
EAN
4 017918 987091
Pack 1
Customs tariff 85044081
Country of Origin CN
Catalog page information Page 563 (IF-2009)
Product notes
WEEE/RoHS-compliant since:
10/07/2006
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation at http://
www.download.phoenixcontact.com.
The General Terms and Conditions
of Use apply to Internet downloads.
Product description
QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high inrush currents
using the POWER BOOST. Thanks to the wide-range input and extensive package of approvals, they can be used in all
sectors of industry the world over. The switching output or floating relay contact are used for remote diagnostics.
Technical data
Input data
Nominal input voltage 110 V AC ... 240 V AC
QUINT-PS-100-240AC/24DC/40 Order No.: 2938879
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2938879
PHOENIX CONTACT Ltd Page 2 / 7
http://www.phoenixcontact.co.uk 20-Jan-2012
AC input voltage range 85 V AC ... 264 V AC (Derating < 100 V DC: 2.5%/V)
DC input voltage range 90 V DC ... 350 V DC (Derating < 110 V DC: 2.5%/V)
AC frequency range 45 Hz ... 65 Hz
DC frequency range 0 Hz
Current consumption Approx. 12.5 A (120 V AC)
Approx. 4.5 A (230 V AC)
Nominal power consumption 960 W
Inrush surge current < 15 A (typical)
Power failure bypass > 20 ms (120 V AC)
> 20 ms (230 V AC)
Input fuse 20 A (fast blow, internal)
Permissible backup fuse B16
B20
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 40 A (-25 °C ... 60 °C)
45 A (with POWER BOOST, -25°C ... 40°C permanent)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Max. capacitive load Unlimited
Current limitation Approx. IBOOST = 45 A (for short-circuit)
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple < 30 mVPP (with nominal values)
Peak switching voltages nominal load < 50 mVPP (20 MHz)
Maximum power dissipation idling 28 W
Power loss nominal load max. 80 W
General data
Width 240 mm
QUINT-PS-100-240AC/24DC/40 Order No.: 2938879
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2938879
PHOENIX CONTACT Ltd Page 3 / 7
http://www.phoenixcontact.co.uk 20-Jan-2012
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
243 mm
Net weight 3.5 kg
Operating voltage display Green LED
Efficiency > 92 % (for 230 V AC and nominal values)
Insulation voltage input/output 3 kV AC (type test)
2 kV AC (routine test)
Degree of protection IP20
Protection class I, with PE connection
MTBF (IEC 61709, SN 29500) > 500000 h
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 50081-2
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers EN 61558-2-17
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
EN 61558-2-17
Shipbuilding approval Germanischer Lloyd (EMC 2), ABS, DNV
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Standard – Protection against electric shock DIN 57100-410
QUINT-PS-100-240AC/24DC/40 Order No.: 2938879
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2938879
PHOENIX CONTACT Ltd Page 4 / 7
http://www.phoenixcontact.co.uk 20-Jan-2012
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Equipment safety GS (tested safety)
Certificate CB Scheme
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
Surge voltage category III
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 10
Stripping length 7 mm
Screw thread M3
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section stranded min. 0.5 mm²
Conductor cross section stranded max. 10 mm²
Conductor cross section AWG/kcmil min. 20
Conductor cross section AWG/kcmil max 6
Stripping length 10 mm
Signaling
Output name DC OK active
Output description UOUT > 0.9 x UN: High signal
Maximum switching voltage ≤ 24 V
Output voltage + 24 V DC (signal)
Maximum inrush current ≤ 20 mA (short-circuit resistant)
QUINT-PS-100-240AC/24DC/40 Order No.: 2938879
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2938879
PHOENIX CONTACT Ltd Page 5 / 7
http://www.phoenixcontact.co.uk 20-Jan-2012
Continuous load current ≤ 20 mA
Status display "DC OK" LED green
Note on status display UOUT < 0.9 x UN: LED flashing
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 10
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Screw thread M3
Output name DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage ≤ 30 V AC/DC
Maximum inrush current ≤ 1 A
Continuous load current ≤ 1 A
Status display "DC OK" LED green
Certificates
Certification CUL, CUL Listed, DNV, GL, GOST, UL, UL Listed
Certification Ex: CUL-EX LIS, UL-EX LIS
Accessories
Item Designation Description
General
2853983 UTA 107 Universal DIN rail adapter, for screwing on switchgear
2938235 UWA 182/52 Universal wall adapter
QUINT-PS-100-240AC/24DC/40 Order No.: 2938879
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2938879
PHOENIX CONTACT Ltd Page 6 / 7
http://www.phoenixcontact.co.uk 20-Jan-2012
Drawings
Block diagram
Circuit diagram
QUINT-PS-100-240AC/24DC/40 Order No.: 2938879
http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2938879
PHOENIX CONTACT Ltd Page 7 / 7
http://www.phoenixcontact.co.uk 20-Jan-2012
Address
PHOENIX CONTACT Ltd
Halesfield 13
Telford / Shropshire / TF7 4PG,England
Phone 01952 681 700
Fax 01952 681 799
http://www.phoenixcontact.co.uk
Phoenix Contact Ltd.
Technical modifications reserved;