© 2015 Bel Power Solutions, Inc.
North America
+1-866.513.2839
Asia-Pacific
+86.755.29885888
Europe, Middle East
+353 61 225 977
tech.support@psbel.com
BCD.00287_AB
60 W Convection Cooled
90-264 VAC Input
-20 to 50°C Full Load Operation
2 x MOPP
4.0 x 2.0 x 1.2 inch (101.6 x 50.8 x 30.48 mm)
No Minimum Load Required - Single Output Models
No Load Power < 0.3 W
IEC Protection Class Options:
o Class I: Earthing Tab J4 (no suffix)
o Class II: No Earthing Tab (-2 suffix)
Conducted EMI EN 55022-B, FCC Part 15 Level B
Medical Safety Agency Approvals
CE marked
The MBC60 Series of open-frame medical
power supplies, with its wide universal 90-264
VAC input range, is available at 60 W of output
power and a variety of single and multiple output
voltages. The MBC series was designed to 3rd
edition medical approvals and provides 2x
MOPP (Means of Patient Protection) isolation for
class 1 and class 2 installations.
These medical power supplies are ideal for,
monitoring, home health equipment as well as
surgical devices.
Dialysis
Monitoring
Pumps
Surgical Devices
Home Health
Ultrasound
MBC60 Series
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD.00287_AB
MODEL
OUTPUT VOLTAGE
(VDC) 1
MAX (A)
MINIMUM
LOAD (A) 3
RIPPLE & NOISE 2
TOTAL
REGULATION
OVP THRESHOLD
MBC60-1005G
5.1
10.0
0.0
1%
± 0.8%
130% Typical
MBC60-1012G
12
5.4
0.0
1%
± 0.8%
130% Typical
MBC60-1015G
15
4.33
0.0
1%
± 0.8%
130% Typical
MBC60-1024G
24
2.7
0.0
1%
± 0.8%
130% Typical
MBC60-1048G
48
1.35
0.0
1%
± 0.8%
130% Typical
MBC60-3000G
5.2
8.0
0.5
1%
± 0.8%
130% Typical
12.5
3.0
0.1
1%
± 5.3%
-12.8
0.5
0.0
1%
± 5.3%
MBC60-3001G
5.2
8.0
0.5
1%
± 0.8%
130% Typical
24.0
1.5
0.1
1%
± 5.3%
-12.8
0.5
0.0
1%
± 5.3%
MBC60-3002G
5.2
8.0
0.5
1%
± 0.8%
130% Typical
14.6
2.5
0.1
1%
± 5.3%
-14.8
0.5
0.0
1%
± 5.3%
MBC60-3003G
3.3
6.0
1.0
1.5%
± 0.8%
130% Typical
5.2
3.0
0.1
1%
± 5.3%
-12.8
0.5
0.0
1%
± 5.3%
Warranty 2 years.
NOTES:
1 Maximum outputs for each output. Max power rating should not be exceeded.
2 Output noise measurement is made with a 20 MHz bandwidth using a 6” twisted pair, terminated with a 10 uF tantalum
capacitor in parallel with a 0.1 uF ceramic capacitor.
3 Minimum load specified to meet cross regulation.
MBC60 Series
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD.00287_AB
Specifications are for nominal input voltage, 25°C and max load unless otherwise stated.
PARAMETER
DESCRIPTION / CONDITION
CRITERION
Input Voltage
Universal Input
90 - 264 VAC
Input Frequency 4
47 to 400 Hz
Input Current
120 VAC:
230 VAC:
1.5 A max.
0.75 A max.
No Load Power
Single output models
Multi output models
< 0.3 W
< 0.5 W
Inrush Current
120 VAC:
230 VAC:
30 A max.
60 A max.
Leakage Current
120 VAC:
230 VAC:
< 140 μA
< 250 μA
4 Safety Approved: 47 to 63 Hz.
PARAMETER
DESCRIPTION / CONDITION
CRITERION
Efficiency
Typical
85%
Hold Up Time
120 / 230 VAC
6 ms
Output Power
50 to 65 W
Line Regulation
+/-0.3%
Load Regulation
V1:
V2 & V3:
+/-0.5%
+/-5%
Transient Response
Main output 50 to 100% load change,
50/60 Hz, 50% duty cycle, 0.1A / us
< 10%,
recovery time < 5 ms
Rise Time
< 100 ms
Set Point Tolerance
V1:
V2 & V3:
± 3%
± 5%
Voltage Adjustment
V1
± 10%
Remote Sense
V1
0.5 VDC compensation
Over Current Protection
Typical above rating
130%
Over Voltage Protection
Typical for V1 only
130%
Short Circuit Protection
Short term, auto recovery
PARAMETER
DESCRIPTION / CONDITION
CRITERION
Isolation Voltage
Input to Output, 2M0PP
Input to Ground, 1M0PP
Output to Ground
Min. 5700 VDC
1500 VAC
500 VAC
Switching Frequency
Typical
67 kHz
Reliability
MTBF according to Telcordia -SR332-Issue 3
1.87 million hours
Operating Temperature
Refer to derating curve
Start-up is guaranteed
-20 to 70°C
-20 to 0°C
Storage Temperature
-40 to 85°C
MBC60 Series
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD.00287_AB
PARAMETER
DESCRIPTION / CONDITION
CRITERION
Conducted Emissions
EN55022-B, CISPR22-B, FCC PART15-B
Radiated Emissions
EN55022-B, CISPR22-B, FCC PART15-B
To be controlled in end system
Harmonic Current
EN61000-3-2
Class A
Static Discharge
EN61000-4-2
Level 3
RF Field Susceptibility
EN61000-4-3
Level-3
Fast Transients/Bursts
EN61000-4-4
Level-3
Surge Susceptibility
EN61000-4-5
Level-3
Humidity
Non Condensing
95%
Altitude
Operating:
Non-Operating:
10,000 ft.
40,000 ft.
PARAMETER
DESCRIPTION/CONDITION
Agency Approvals
Approved to the latest edition of the following standards:
CSA/UL60601-1, EN60601-1 and IEC60601-1
CE mark
Complies with LVD Directive
Figure 1 - Output Power Vs. Temperature
CONNECTOR
PIN
DESCRIPTION/CONDITION
MANUFACTURER / PN
AC Input Connector
J1
Pin 1
Pin 2
AC Neutral
AC Line
Molex: 26-60-4030 or equivalent
Mating: 09-50-3031; Pins: 08-50-0106
DC Output Connector
J2
Pin 1,2
Pin 3,4
Pin 5
Pin 6
V1
RTN
V3
V2
Tyco: 640445-6 or equivalent
Mating: 647402-6; Pins: 3-647409-1
Remote Sense
J3
Pin 1
Pin 2
+V1 Sense
-V1 Sense
Molex: 22-23-2021 or equivalent
Mating: 22-01-2021
Earthing Tab
J4
Molex: 19705-4301
Mating: 190030001
MBC60 Series
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD.00287_AB
PARAMETER
DESCRIPTION/CONDITION
Weight
150 g (0.33 lbs.)
Dimensions
101.6 x 50.8 x 30.48 mm (4 x 2 x 1.2 inch)
Figure 2 - Mechanical Drawing MBC60-1xxxG
Figure 3 - Mechanical Drawing MBC60-3xxxG
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems, equipment used in
hazardous environments, or nuclear control systems.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date
manufactured. Specifications are subject to change without notice.