1
CSM_G3J-T-C_DS_E_3_1
Solid State Contactor for 3-phase Motors with Built-in Soft Start/Stop and Monitor Output
G3J-T-C
New Models with AC Power Supply Input and
Monitor Output Equivalent to Non-contact
SPST-NO Join the G3J-T Series
Limiting the starting current saves energy.
Certified for UL and CSA.
Mounts with screws or to DIN Track.
Compact design with heat sinks (3.7-kW models: 100 × 100 ×
130 mm (W × H × D)).
Built-in snubber circuit and thyristor.
Built-in operation indicator.
Refer to Safety Precautions for All Solid State
Relays.
Appearance
Ordering Information
List of Models
Accessories (Order Separately)
Mounting Bracket
Note: Use this Bracket when mounting Thermal Relay GTK-22 (LS Industrial Systems) to a G3J-series.
Output terminals (load side)
Monitor output terminals
Output terminals (power supply side)
Ramp-down time adjuster (default setting: 1 s)
Ramp-up time adjuster (default setting: 1 s)
Operation indicator
Input terminals
Starting torque adjuster (default setting: 200%)
Number of
elements
Isolation
method
Rated power
supply voltage
Input method Applicable monitor capacity
(AC3)
Monitor
output
Model
3 Phototriac
coupler
100 to 240 VAC No-voltage input
(open and short-
circuited input)
3.7 kW (17.4 A) 200 to 220 VAC AC
switching
output
G3J-T217BL-C AC100-240
2.2 kW (11.1 A) G3J-T211BL-C AC100-240
0.75 kW (4.8 A) G3J-T205BL-C AC100-240
12 to 24 VDC 3.7 kW (17.4 A) DC
switching
output
G3J-T217BL-C DC12-24
2.2 kW (11.1 A) G3J-T211BL-C DC12-24
0.75 kW (4.8 A) G3J-T205BL-C DC12-24
Model
R99-14 FOR G3J (See note.)
G3J-T-C
2
Specifications
Certified Standards
UL 508, CSA 22.2 No. 14
Ratings (at an Ambient Temperature of 25°C)
Power Supply
Operating (Input) Circuit
AC Model DC Model
Main Circuit (for Both AC and DC Models)
Note: 1. The rated carry load depends on the ambient temperature. For details, refer to the Load Current vs. Ambient Temperature graph in
Engineering Data.
2. Satisfies switching test conditions of AC3, AC4, and AC53-a. (Refer to Engineering Data on page 5 for the test conditions.)
3. Single-phase loads cannot be used.
Monitor Output
Item Operating input power
supply specifications
AC Model DC Model
Rated power supply voltage 100 to 240 VAC 12 to 24 VDC
Operating voltage range 85 to 264 VAC 10.2 to 26.4 VDC
Current consumption 40 mA max. (at 100 to 240 VAC) 70 mA max. (at 12 to 24 VDC)
Input
method
No-
voltage
input
Short-circuiting/opening terminals 3 and 1 or
terminals 3 and 2
SSR input short-circuited: Maximum
impedance of 1 k,
Maximum residual
voltage of 1 V
SSR input open: Minimum
impedance of
100 k
Relay input: For minute signals
Input current 10 mA max. (at 12 to 24 VDC)
Input
method
No-
voltage
input
Short-circuiting/opening terminals 3 and 1 or
terminals 3 and 2
SSR input turned ON: Maximum residual
voltage of 2 V between
short-circuited
terminals
SSR input turned OFF:Maximum leakage
current of 0.15 mA
Relay input: For minute signals
Item Model G3J-T217BL-C G3J-T211BL-C G3J-T205BL-C
Rated load voltage 200 to 240 VAC
Rated voltage range 180 to 264 VAC
Rated carry current (See note 1.) 17.4 A (at 40°C) 11.1 A (at 40°C) 4.8 A (at 40°C)
Minimum load current 0.5 A
Inrush current resistance (peak value) 500 A (60 Hz, 1 cycle) 350 A (60 Hz, 1 cycle) 150 A (60 Hz, 1 cycle)
Overload resistance Refer to Engineering Data on page 5
Closed current (effective value) AC3 174 A 111 A 48 A
AC4 208.8 A 133.2 A 57.6 A
Breaking current (effective value) AC3 139.2 A 88.8 A 38.4 A
AC4 174 A 111 A 48 A
Applicable
load
3-phase inductive motor (See note 2.)
(AC3, AC4, AC53-a)
200 to 220 VAC
3.7 kW (17.4 A)
200 to 220 VAC
2.2 kW (11.1 A)
200 to 220 VAC
0.75 kW (4.8 A)
Resistive load (AC1) (See note 3.) 200 to 240 VAC
17.4 A
200 to 240 VAC
11.1 A
200 to 240 VAC
4.8 A
Item Operating input power
supply specifications
AC model (See note.) DC model (See note.)
Rated power supply voltage 100 to 240 VAC 12 to 24 VDC
Operating voltage range 85 to 264 VAC 10.2 to 26.4 VDC
Rated carry current 50 mA 0.2 A
Minimum load current 3 mA 3 mA
5
6
5 (+)
6 ()
Note: Internal wiring
AC model DC model
G3J-T-C
3
Characteristics (for Both AC and DC Models)
Note: 1. Provided that the starting torque is 600% In when the motor is started at full voltage.
2. The monitor output will be ON while load current is flowing to the main circuit.
Connections
Connection Examples
Note: Harmonized protection for motor overload is ensured by using a thermal relay. Be sure, however, to install protective devices on the power
supply side, such as fuses and non-fuse breakers, as protection against accidents due to short-circuiting.
Item Model G3J-T217BL-C G3J-T211BL-C G3J-T205BL-C
Ramp-up time Set within a range of approx. 1 to 25 s.
Ramp-down time Set within a range of approx. 1 to 25 s.
Starting torque (See note 1.) Set within a range of 200% to 450% In.
Monitor output operate time (See note 2.) After control signal input: AC model: 300 ms max. (TYP 50 ms), DC model: 50 ms max.
Monitor output release time (See note 2.) After ramp-down time completion (after main circuit current turns OFF): 60 ms max.
Output ON voltage drop (main circuit) 1.6 V (RMS) max.
Output ON voltage drop (monitor output) AC model: 3.5 VAC max., DC model: 2.0 VDC max.
Leakage current (main circuit) 10 mA max. (at 200 VAC)
Leakage current (monitor output) AC model: 1.5 mA max. (at 200 VAC), DC model: 0.15 mA max. (at 24 VDC)
Insulation resistance 100 M min. (at 500 VDC)
Dielectric strength 2,500 VAC, 60 Hz for 1 min
Vibration resistance 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock resistance 294 m/s2
Storage temperature 30 to 70°C (with no icing or condensation)
Ambient operating temperature 20 to 60°C (with no icing or condensation)
Ambient operating humidity 45 to 85 %
Weight Approx. 890 g Approx. 760 g Approx. 760 g
AC Model G3J-T@BL-C DC Model G3J-T@BL-C
(NPN transistor input) (PNP transistor input)
M
L1/R L2/S
Three-phase, 200 to 220 V
G3J
L3/T
100 to
240 VAC
100 to
240 VAC
T1/U T2/V T3/W
1
2
3
4
5
6
7
8
Ry
Thermal Relay
Motor M
L1/R L2/S
Three-phase, 200 to 220 V
G3J
L3/T
12 to
24 VDC
12 to
24 VDC
T1/U T2/V T3/W
1
2
3
4
5
6
7
8
Ry
NPN Tr
Thermal Relay
Motor M
L1/R L2/S
Three-phase, 200 to 220 V
G3J
L3/T
T1/U T2/V T3/W
1
2
3
4
5
6
7
8
Ry
Thermal Relay
Motor
PNP Tr 12 to
24 VDC
12 to
24 VDC
G3J-T-C
4
Example of Forward/Reverse Rotation
Using Monitor Output
G3J-T-C
Note: Be sure to use a fuse or non-fuse breaker to protect the G3J.
Time Chart Example
Note: Switch between forward and reverse rotation only after the
motor rotation has come to a complete stop.
Monitor Output Usage Example (Motor
Stop Hold)
DC Model G3J-T@BL-C
Monitor Output Applications
The monitor output will be ON while current is flowing to the main
circuit. Use the monitor output, e.g., to switch the operation
indicator, or to switch control signals during forward/reverse rotation
or when a mechanical brake is used.
Be sure to use a surge absorber when connecting an inductive load
to the monitor output.
M
21 21
22
135
26
22
135
A2
A1
A2
A1
4
L1/R L2/S
G3J-T-C
L3/T
T1/U T2/V T3/W
1
2
3
4
5
6
7
8
Output to
PLC/relay
sequence
Output from
PLC/relay
sequence
PLC/relay-
sequential
timer circuit
Thermal Relay
Motor
246
Three-phase, 200 to 220 V
Fuse or non-fuse breaker
Forward
rotation
Reverse
rotation
Reversible
contactor
NC NC
T3 L3
T2 L2
T1 L1
NC NC
T3 L3
T2 L2
T1 L1
Reversible contactor
Forward rotation signal input
(output form PLC)
Reversible contactor
Reverse rotation signal input
(output from PLC)
G3J-T-C
Input signal
(output from PLC)
G3J-T-C
Monitor output signal
(input to PLC) Ramp-down
time Ramp-down
time
(See note.)
M
L1/R L2/S
Three-phase, 200 to 220 V
G3J
L3/T
12 to
24 VDC
T1/U T2/V T3/W
1
2
3
4
5
6
7
8
Ry
NPN Tr
Thermal Relay
Motor
Brake
(non-energized)
Do not use two G3J-T or G3J-C Contactors together
for reversible operation.
G3J-T-C
5
Engineering Data
Switching Frequency Conditions (AC3/AC4/AC53-a)
Load Current vs. Ambient Temperature
(at Continuous Power)
Overload Resistance
60 Hz, Ta of 25°C, non-repetitive (1/2 max. for repetitive application)
20
16
12
8
4
0
20020 40 60 80 100
Ambient temperature Ta (°C)
G3J-T217BL-C
G3J-T205BL-C
G3J-T211BL-C
Load current Io (A)
10,000
1,000
100
10
1
0.1
0.01
0 100 200 300 400
Overload current (Arms)
G3J-
T211BL-C
G3J-T217BL-C
G3J-
T205BL-C
Harmonized protection with thermal
overload relays has been provided
conforming to EN 60947-4-1 (Class
10A/10) in this area (dotted line:
for hot start).
ON time (s)
AC3 Class (Immediate Start)
Ie: Rated carry current
Ue: Rated load voltage (200/400 V)
Testing for the soft-start model was performed at
the following conditions:
Ramp-up time = 1 s
Starting torque = 450% In
Testing for the soft start/stop model was
performed at the following conditions:
Ramp-up time = 1 s
Ramp-down time = 1 s
Starting torque = 450% In
AC4 Class (Inching)
Ie: Rated carry current
Ue: Rated load voltage (200/400 V)
Testing for the soft-start model was performed at
the following conditions:
Ramp-up time = 1 s
Starting torque = 450% In
Testing for the soft start/stop model was
performed at the following conditions:
Ramp-up time = 1 s
Ramp-down time = 1 s
Starting torque = 450% In
AC53-2: 6-6: 25-15,
Actual Load Service Life Test
Ie: Rated carry current
Ue: Rated load voltage (200/400 V)
Testing for the soft-start model was performed at
the following conditions:
Ramp-up time = 1 s
Starting torque = 450% In
Testing for the soft start/stop model was
performed at the following conditions:
Ramp-up time = 1 s
Ramp-down time = 1 s
Starting torque = 450% In
0.3 s
Ie
(Ue, cos θ = 0.35)
6Ie
(Ue, cos θ = 0.35)
0.75 s
10 s
0.45 s
6Ie
(Ue, cos θ = 0.35)
10 s
6 s
Ie
(Ue, cos θ = 0.35)
6Ie
(Ue, cos θ = 0.35)
1 min.
4 min.
G3J-T-C
6
Time Chart
Note: 1. The soft-start time and soft-stop time depend on the load characteristics (e.g., inertia and friction factor) in addition to the starting torque,
ramp-up time, and ramp-down time. Therefore, the soft-start time or soft-stop time will not increase beyond a certain point if the ramp-up
time and ramp-down time are increased.
2. Due to the soft-stop control characteristics, the load current continues flowing even after the motor stops. Set to the optimum value
according to the application.
3. The operation indicator will light synchronized with the monitor output.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Ramp-up time Ramp-down time
Monitor output operate time
Monitor output release time
Power supply for
internal drive
Control input signal
Operation indicator lit
Monitor output
Load current
Rated current
15.85
34.9
37.1
54.5
72
107.9
Input terminals
Three, M3 × 8
Monitor
output
Two, M3 × 8
50 max. 4.6 dia. Stating torque adjuster
Ramp-up time adjuster
120 max.
Ramp-down time adjuster
Output
terminals
Six, M4 × 8
5.5
7.6
13.213.2
80 max.
4.6 × 5.6
Oval hole
Operation
indicator
8990100 max. 90±0.2
Two, 4.5-dia. or
M4 holes
50±0.2
G3J-T205BL-C
G3J-T211BL-C
Mounting Hole
Dimensions
G3J-T-C
7
Safety Precautions
Refer to Safety Precautions for All Solid State Relays.
15.85
44.9
37.1
54.5
82
117.8
Input terminals
Three, M3 × 8 50 4.6 dia. Stating torque adjuster
Ramp-up time adjuster
Ramp-down time adjuster
Output
terminals
Six, M4 × 8
5.5 130 max.
7.6
13.213.2
100 max.
4.6 × 5.6
Oval hole
Operation
indicator
8990100 max. 90
±0.2
Two, 4.5-dia. or
M4 holes
50
±0.2
Monitor output
Two, M3 × 8
G3J-T217BL-C
Mounting Hole
Dimensions
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2011.4
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2011 All Right Reserved.