3
Starters
Low Voltage Products & Systems 3.11
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
Across the line starters
Open & enclosed
A9 – AF750
Enclosure types
• NEMA 1 (Indoor metal)
NEMA 3R (Outdoor metal)
• NEMA 12 (Metal dusttight)
• NEMA 4X (Stainless steel)
• NEMA 4 (Water tight)
• NEMA 1, 3R, 4, 4X, & 12 (Plastic)
• IP 65 plastic A9 – A16 starters
• NEMA 7 & 9
Class I, Group C, D, Div 1 & 2
Class II, Groups E, F, & G, D iv 1 & 2
Class III, 4X
Overload relay protection
Starters, sizes A9 A300, have Class 10
adjustable thermal bimetallic overload relay
protection as standard.
Sizes AF400 – AF750, have selectable Class
10, 20, 30 adjustable electronic overload relay
protection as standard.
Electronic overload relay protection is available
for other starter sizes.
Across the line
Starters
Description
A9 – AF750
Maximum UL horsepower ratings
UL508A Panel Program, #E105450
NEMA sizes (00 – 7) available
Compact space-saving design
Standard auxiliary contact congurations:
A9 – A40 1 NO
A50 – AF750 1 NO & 1 NC
Additional auxiliary contact blocks are
available
Consult factory for DC ratings & DC control
operation
Fast, snap-on DIN rail mounting (A9 - A110)
Double break contact design
Snap-on front and side mounted
accessories include mechanical latch,
pneumatic timer and 1 & 4 pole auxiliary
contact blocks (A9 – A110)
Easy coil change
Captive terminal screws
NEMA, UL, CSA, and most other
international standards
cUL marked
• Operates over an extended voltage range
of 85% to 110% of rated control voltage
Screwdriver guide holes
For reduced voltage starters, consult
factory.
3
Starters
3.12 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Starter selection by motor horsepower & voltage
Maximum UL/CSA ratings, three phase
NOTE: For motors with RPM greater or less than 1800 RPM, check full load amp rating on motor nameplate to ensure proper overload protection.
For AF50 – AF 300 starters, consult factory.
1 For AF400 - AF750 only.
CAUTION: The above ratings are based on average motor FLA. Actual FLA
on the motor nameplate should be used for overload relay setting.
Motor horsepower Open
Complete starter
Starter components
3-phase, 1800 RPM 1Contactors Overload relays
200V 230V 460V 575V Catalog number List
price Catalog number List
price Catalog number List
price
———1/4 11-2C A9-30-10-84 TA25DU0.4 (0.25 – .4)
$ 63
1/4, 1/3 1/3 11-2D A9-30-10-84 TA25DU0.63 (0.4 – .63)
———1/2 11-2E A9-30-10-84 TA25DU1.0 (0.63 – 1.0)
1/2 3/4 11-2F A9-30-10-84 TA25DU1.4 (1.0 – 1.4)
3/4 11-2G A9-30-10-84 TA25DU1.8 (1.3 – 1.8)
1/2 11.5 11-2H $ 165 A9-30-10-84 $ 78 TA25DU2.4 (1.7 – 2.4)
1/2 1.5 2 11-2J A9-30-10-84 TA25DU3.1 (2.2 – 3.1)
3/4 3/4 2 11-2K A9-30-10-84 TA25DU4.0 (2.8 – 4.0)
—1—311-2L A9-30-10-84 TA25DU5.0 (3.5 – 5.0)
11.5 35 11-2M A9-30-10-84 TA25DU6.5 (4.5 – 6.5)
22511-2N A9-30-10-84 TA25DU8.5 (6.0 – 8.5)
———7.5 11-2P A9-30-10-84 TA25DU11 (7.5 – 11)
3 3 7.5 10 21-2Q 171 A12-30-10-84 84 TA25DU14 (10 – 14)
5 5 10 15 31-2R 200 A16-30-10-84 102 TA25DU19 (13 – 19)
7.5 15 20 41-2S 294 A26-30-10-84 183 TA25DU25 (18 – 25)
7.5 10 20 25 41-2T A26-30-10-84 TA25DU32 (24 – 32)
10 10 51-2B 365 A30-30-10-84 252 TA42DU32 (22 – 32)
TA42DU42 (29 – 42) 78 25 30 51-2C
10 15 30 40 61-2C 423 A40-30-10-84 297 TA42DU42 (29 – 42)
15 40 50 71-2D 458 A50-30-11-84 330 TA75DU52 (36 – 52)
102
20 71-2E A50-30-11-84 TA75DU63 (45 – 63)
20 ———81-2F 522 A63-30-11-84 372
50 60 81-2F A63-30-11-84 TA75DU80 (60 – 80)
25 30 60 75 91-2F 563 A75-30-11-84 413
30 40 75 100 A1-2B 765 A110-30-11-84 480 TA110DU110 (80 – 110) 165
40 ———B1-2C 1,315 A145-30-11-84 825 TA200DU135 (100 – 135)
22550 100 125 B1-2D TA200DU150 (110 – 150)
50 60 125 150 C1-2E 1,730 A185-30-11-84 1,290 TA200DU175 (130 – 175)
60 75 150 200 D1-2E3 2,422 A210-30-11-84 1,635
E320DU320 (105-320) 77575 100 200 250 E1-2E3 3,027 A260-30-11-84 1,815
100 250 300 F1-2E3 3,177 A300-30-11-84 1,875
125 125, 150 350 400 G1-70E5 4,125 AF400-30-11-70 3,120 E500DU500 (170 – 500) 865
150 200 400 500 H1-70E5 9,375 AF460-30-11-70 4,425
200 250 500 600 T1-70E8 12,400 AF580-30-11-70 6,900 E800DU800 (270 – 800) 950
250 300 600 700 U1-70E8 13,350 AF750-30-11-70 7,200
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the two
digits after the last dash in the catalog number.
Ex.: A 240V coil is required for an A75 starter: 91-4F
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
Discount schedule AA [OA] – A9 - A110
AEA [OC] – A145 - AF1650
Coil voltage selection – A9 - A300
Hz Contactor
type
Volts
24 110 120 208 220 240 440 480 500 600
60 A 1 23456 7
50 A 1 2 4 7
Coil voltage selection – AF400 - AF750 1
Hz Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E FG H
3
Starters
Low Voltage Products & Systems 3.13
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
Starter selection by motor horsepower & voltage
NEMA sizes & ratings, three phase
NEMA
size
Motor horsepower Open
Complete starter
Starter components
3-phase, 1800 RPM 1Contactors Overload relays
200V 230V 460V 575V Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
1/4 J1-2C
$ 165
A9N00-30-10-84 TA25DU0.4 (0.25 – .4)
$ 63
1/3 J1-2D A9N00-30-10-84 TA25DU0.63 (0.4 – .63)
1/4 1/2 J1-2E A9N00-30-10-84 TA25DU1.0 (0.63 – 1.0)
1/4 1/3,1/2 J1-2F A9N00-30-10-84 TA25DU1.4 (1.0 – 1.4)
1/3 3/4 3/4 J1-2G A9N00-30-10-84 TA25DU1.6 (1.3 – 1.6)
00 1/3,1/4 1/2 1 1 J1-2H A9N00-30-10-84 $ 78 TA25DU2.4 (1.7 – 2.4)
1/2 1.5, 2 J1-2J A9N00-30-10-84 TA25DU3.1 (2.2 – 3.1)
3/4 3/4 1.5, 2 J1-2K A9N00-30-10-84 TA25DU4.0 (2.8 – 4.0)
1 J1-2L A9N00-30-10-84 TA25DU5.0 (3.5 – 5.0)
11.5 J1-2M A9N00-30-10-84 TA25DU6.5 (4.5 – 6.5)
1.5 ———J1-2N A9N00-30-10-84 TA25DU8.5 (6.0 – 8.5)
3 K1-2L
200
A16N0-30-10-84 TA25DU5.0 (3.5 – 5.0)
0 3 5 K1-2M A16N0-30-10-84 102 TA25DU6.5 (4.5 – 6.5)
2 2 5 K1-2N A16N0-30-10-84 TA25DU8.5 (6.0 – 8.5)
3 3 K1-2P A16N0-30-10-84 TA25DU11 (7.5 – 11)
7.5 L1-2P
294
A26N1-30-10-84 TA25DU11 (7.5 – 11)
1 7.5 10 L1-2Q A26N1-30-10-84 183 TA25DU14 (10 – 14)
5 5 10 L1-2R A26N1-30-10-84 TA25DU19 (13 – 19)
7.5 7.5 L1-2S A26N1-30-10-84 TA25DU25 (18 – 25)
2
15 M1-2R 458 A50N2-30-11-84 330 TA25DU19 (13 – 19) 2
15 20 M1-2A
458
A50N2-30-11-84 TA75DU25 (18 – 25)
102
10 20 25 M1-2B A50N2-30-11-84 330 TA75DU32 (22 – 32)
10 15 25 M1-2C A50N2-30-11-84 TA75DU42 (29 – 42)
3
30 N1-2C
563
A75N3-30-11-84 TA75DU42 (29 – 42)
15 30 40 N1-2D A75N3-30-11-84 413 TA75DU52 (36 – 52)
20 20 40 50 N1-2E A75N3-30-11-84 TA75DU63 (45 – 63)
25 25,30 50 N1-2F A75N3-30-11-84 TA75DU80 (60 – 80)
60 60, 75 P1-2A
1,315
A145N4-30-11-84
825
TA200DU90 (65 – 90)
1654 30 40 75 100 P1-2B A145N4-30-11-84 TA200DU110 (80 – 110)
40 50 100 P1-2C A145N4-30-11-84 TA200DU135 (100 – 135)
550,60,75 60,75,100 125,150,200 200 Q1-2E3 3,027 A260N5-30-11-84 1,815 E320DU320 (105-320) 775
100 200
6 100, 125 125,150 250, 300 250, 300 R1-70E5 5,700 AF460N6-3011-70 4,425 E500DU500 (170 - 500) 865
150 200 400 400
7 250, 300 500, 600 500, 600 S1-70E8 8,646 AF750N7-3011-70 7,200 E800DU800 (270 - 800) 950
NOTE: For motors with RPM greater or less than 1800 RPM, check full load amp rating on motor nameplate to ensure proper overload protection.
For AF50 – AF 300 starters, consult factory.
1 AF400 - AF750 only.
2 Overload to be base mounted.
CAUTION: The above ratings are based on average motor FLA. Actual FLA
on the motor nameplate should be used for overload relay setting.
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the two
digits after the last dash in the catalog number.
Ex.: A 240V coil is required for an A75 starter: N1-4F
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
Coil voltage selection – A9 - A300
Hz Contactor
type
Volts
24 110 120 208 220 240 440 480 500 600
60 A 1 23456 7
50 A 1 2 4 7
Coil voltage selection – AF400 - AF750 1
Hz Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E FG H
Discount schedule AA [OA] – A9 - A110
AEA [OC] – A145 - AF1650
3
Starters
3.14 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Motor horsepower Open
Complete starter
Starter components
3 Phase, 1800 RPM Contactor Overload relay
200V 230V 460V 575V Catalog number List Price Catalog number List Price Catalog number List Price
——— 1/4
11-2B1
$ 198
A9-30-10-84
$ 78
E16DU1.0 (0.3 - 1.0)
$ 96
1/4,1/3 1/3
——— 1/2
1/2 3/4
11-2C1 A9-30-10-84 E16DU2.7 (0.9-2.7) 3/4
1/2 1 1 1/2
1/2 1 1/2 2
11-2D1 A9-30-10-84 E16DU6.3 (2.0-6.3)
3/4 3/4 2
1 3
1 1 1/2 3 5
2 2 5 7 1/2 11-2E1 A9-30-10-84
E16DU18.9 (5.7-18.9) 3 3 7 1/2 10 21-2E1 204 A12-30-10-84 84
5 5 10 15 31-2E1 233 A16-30-10-84 102
7 1/2 15 20 41-2E1 336 A26-30-10-84 183 E45DU30 (9-30)
105
7 1/2 10 20 25
10 10 51-2E2 414 A30-30-10-84 252 E45DU45 (15-45)
25 30
10 15 30 40 61-2E2 472 A40-30-10-84 297 E45DU45 (15-45) 112
15 20 40 50 71-2E1 544 A50-30-11-84 330
E80DU80 (27-80) 18820 50 60 81-2E1 608 A63-30-11-84 372
25 30 60 75 91-2E1 649 A75-30-11-84 413
30 ———A1-2E1 861 A110-30-11-84 480 E140DU140 (50-140) 261
40 75 100
40 50 100 125 B1-2E2 1,415 A145-30-11-84 825 E200DU200 (60-200) 325
50 60 125 150 C1-2E2 1,830 A185-30-11-84 1,290
60 75 150 200 D1-2E3 2,422 A210-30-11-84 1,635
E320DU320 (100-320) 77575 100 200 250 E1-2E3 3,027 A260-30-11-84 1,815
100 250 300 F1-2E3 3,177 A300-30-11-84 1,875
125 5/6 350 400 G1-70E5 4,125 AF400-30-11-70 3,120 E500DU500 (150-500) 865
150 200 400 500 H1-70E5 5,700 AF460-30-11-70 4,425
200 250 500 600 T1-70E8 8,346 AF580-30-11-70 6,900 E800DU800 (250-800) 950
250 300 600 700 U1-70E8 8,646 AF750-30-11-70 7,200
Selection by motor horsepower
UL/CSA Starters with electronic overload
Discount schedule AA [OA] – A9 - A110
AEA [OC] – A145 - AF1650
3
Starters
Low Voltage Products & Systems 3.15
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
NEMA
size
Motor horsepower Open
Complete starter
Starter components
3-phase, 1800 RPM Contactors Overload relays
200V 230V 460V 575V Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
00
———1/4 J1-2A1 A9N00-30-10-84 E16DU0.32 (0.1 - 0.32) $ 96
———1/3 J1-2B1 A9N00-30-10-84 E16DU1.0 (0.3 - 1.0) 96
1/4 1/2 J1-2B1 A9N00-30-10-84
1/4 1/3,1/2 J1-2C1 A9N00-30-10-84
E16DU2.7 (0.9 - 2.7) 961/3 3/4 3/4 J1-2C1 A9N00-30-10-84
1/3,1/4 1/2 1 1 J1-2C1 $ 198 A9N00-30-10-84 $ 78
1/2 1.5, 2 J1-2D1 A9N00-30-10-84
E16DU6.3 (2.0 - 6.3) 96
3/4 3/4 1.5, 2 J1-2D1 A9N00-30-10-84
1 J1-2D1 A9N00-30-10-84
11.5 J1-2D1 A9N00-30-10-84
1.5 ———J1-2E1 A9N00-30-10-84 E16DU18.9 (5.7 - 18.9) 96
0
3 K1-2D1 A16N0-30-10-84 E16DU6.3 (2.0 - 6.3) 96
3 5 K1-2D1 233 A16N0-30-10-84 102
225K1-2E1 A16N0-30-10-84 E16DU18.9 (5.7 - 18.9) 96
3 3 K1-2E1 A16N0-30-10-84
1
———7.5 L1-2E1 A26N1-30-10-84
E45DU30 (9 - 30) 105
7.5 10 L1-2E1 336 A26N1-30-10-84 183
5 5 10 L1-2E1 A26N1-30-10-84
7.5 7.5 L1-2E1 A26N1-30-10-84
2
———15 M1-2E1 544 A50N2-30-11-84 330 E45DU45 (15 - 45) 112
15 20 M1-2E1 A50N2-30-11-84 E45DU45 (15 - 45) 112
10 20 25 M1-2E1 544 A50N2-30-11-84 330
10 15 25 M1-2E1 A50N2-30-11-84 E80DU80 (27 - 80) 188
3
———30 N1-2E1 A75N3-30-11-84
E80DU80 (27 - 80) 188
15 30 40 N1-2E1 649 A75N3-30-11-84 413
20 20 40 50 N1-2E1 A75N3-30-11-84
25 25,30 50 N1-2E1 A75N3-30-11-84
4
60 60, 75 P1-2E2 A145N4-30-11-84
E200DU200 (60 - 200) 32530 40 75 100 P1-2E2 1,415 A145N4-30-11-84 825
40 50 100 P1-2E2 A145N4-30-11-84
5
50
60
75
60
75
100
125
150
200
200 Q1-2E3 3,027 A260N5-30-11-84 1,815 E320DU320 (105-320) 775
100 200
6
100
125
125
150
250
300
250
300 R1-70E5 5,700 AF460N6-3011-70 4,425 E500DU500 (170 - 500) 865
150 200 400 400
7 250
300
500
600
500
600 S1-70E8 8,646 AF750N7-3011-70 7,200 E800DU800 (270 - 800) 950
Selection by motor horsepower
NEMA Starters with electronic overload
Open Enclosed
Discount schedule AA [OA] AAE [EA] – A9 - A110
AEA [OC] AEAE [EC] – A145 - AF1650
3
Starters
3.16 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Control transformer option
Contactor VA List price
size rating adder
A9 A40 50 360
A9 A40 (N7 & 9) 50 630 2
A50 A75 75 435
A95 A110 100 560
A145 A185 150 720
A210 A300 250 795
AF400 AF460 150 720
AF580 AF750 250 795
Reference page 3.3 for Extra VA under all (Control Transformer Options chart)
Non-reversing
A9 - AF750
Three phase
NOTE: For AF50 – AF 300 starters, consult factory.
1 AF400 - AF750 only.
2 NEMA 7 & 9 Enclosed starter only.
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the sufx
code after the last dash in the catalog number.
Ex.: A 240V coil is required for an A75 starter: 91-4F
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
UL motor
switching
current
Contactor
size
Maximum ratings - UL Listed Open
type
UL Type 1
(Indoor metal)
UL type 3R
(Outdoor metal)
Maximum motor horsepower ratings
200/208V 230/240V 480/480V 575/600V Catalog
number List price Catalog
number
List
price
Catalog
number
List
price
UL rated
9 A9 2 2 5 7.5 11-2∆ $ 165 111-2∆ $ 255 113-2∆ $ 330
11 A12 3 3 7.5 10 21-2∆ 171 211-2∆ 285 213-2∆ 360
17 A16 5 5 10 15 31-2∆ 200 311-2∆ 300 313-2∆ 383
28 A26 7.5 10 20 25 41-2∆ 294 411-2∆ 405 413-2∆ 465
34 A30 10 10 25 30 51-2∆ 365 511-2∆ 473 513-2∆ 533
42 A40 10 15 30 40 61-2∆ 423 611-2∆ 525 613-2∆ 578
54 A50 15 20 40 50 71-2∆ 458 711-2∆ 600 713-2∆ 719
65 A63 20 25 50 50 81-2∆ 522 811-2∆ 713 813-2∆ 795
80 A75 25 30 60 75 91-2∆ 563 911-2∆ 975 913-2∆ 1,058
110 A110 30 40 75 100 A1-2∆ 765 A11-2∆ 1,170 A13-2∆ 1,515
130 A145 40 50 100 125 B1-2∆ 1,315 B11-2∆ 1,765 B13-2∆ 2,130
156 A185 50 60 125 150 C1-2∆ 1,730 C11-2∆ 2,400 C13-2∆ 2,805
192 A210 60 75 150 200 D1-2∆ 2,135 D11-2∆ 2,650 D13-2∆ 3,375
248 A260 75 100 200 250 E1-2∆ 2,740 E11-2∆ 3,825 E13-2∆ 4,650
302 A300 100 100 250 300 F1-2∆ 2,890 F11-2∆ 4,125 F13-2∆ 4,875
414 AF400 125 150 350 400 G1-70∆ 4,125 G11-70∆ 7,857 G13-70∆ 8,625
480 AF460 150 200 400 500 H1-70∆ 5,700 H11-70∆ 9,375 H13-70∆ 9,435
590 AF580 200 250 500 600 T1-70∆ 8,346 T11-70∆ 12,400 T13-70∆ 13,465
810 AF750 250 300 600 700 U1-70∆ 8,646 U11-70∆ 13,350 U13-70∆ 14,325
NEMA rated
NEMA Contactor Continuous 200V 230V 460/575V
size size current
00 A9 9 1.5 1.5 2 J1-2∆ $ 165 J11-2∆ $ 255 J13-2∆ $ 330
0 A16 18 335 K1-2∆ 200 K11-2∆ 300 K13-2∆ 383
1A26 27 7.5 7.5 10 L1-2∆ 294 L11-2∆ 405 L13-2∆ 465
2 A50 45 10 15 25 M1-2∆ 458 M11-2∆ 600 M13-2∆ 719
3A75 90 25 30 50 N1-2∆ 563 N11-2∆ 975 N13-2∆ 1,058
4 A145 135 40 50 100 P1-2∆ 1,315 P11-2∆ 1,765 P13-2∆ 2,130
5 AF260 270 75 100 200 Q1-2∆ 2,740 Q11-2∆ 3,825 Q13-2∆ 4,650
6 AF460 540 150 200 400 R1-70∆ 5,700 R11-70∆ 9,375 R13-70∆ 9,435
7AF750 810 300 600 S1-70∆ 8,646 S11-70∆ 13,350 S13-70∆ 14,325
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7.
Coil voltage selection – A9 - A300
Hz Contactor
type
Volts
24 110 120 208 220 240 440 480 500 600
60 A 1 23456 7
50 A 1 2 4 7
Coil voltage selection – AF400 - AF750 1
Hz Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E FG H
Open Enclosed
Discount schedule AA [OA] AAE [EA] – A9 - A110
AEA [OC] AEAE [EC] – A145 - AF1650
3
Starters
Low Voltage Products & Systems 3.17
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
Non-reversing
A9 - AF750
Three phase
UL Type 12
(Metal dustight)
UL Type 4
(Watertight)
UL Type 4X
(Stainless steel)
UL Type 1, 3R, 4, 4X & 12
(Plastic)
UL Type 7 & 9 non-reversing
(Explosion proof)
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
UL rated
112-2∆ $ 330 114-2∆ $ 495 11X-2∆ $ 645 11P-2∆ $ 315 117-2∆ $ 1,500
212-2∆ 360 214-2∆ 540 21X-2∆ 713 21P-2∆ 345 217-2∆ 1,560
312-2∆ 383 314-2∆ 570 31X-2∆ 743 31P-2∆ 360 317-2∆ 1,590
412-2∆ 465 414-2∆ 630 41X-2∆ 831 41P-2∆ 443 417-2∆ 1,680
512-2∆ 533 514-2∆ 690 51X-2∆ 885 51P-2∆ 510 517-2∆ 2,040
612-2∆ 578 614-2∆ 1,050 61X-2∆ 1,275 61P-2∆ 555 617-2∆ 2,410
712-2∆ 719 714-2∆ 1,103 71X-2∆ 1,328 71P-2∆ 698 717-2∆ 2,600
812-2∆ 795 814-2∆ 1,170 81X-2∆ 1,410 81P-2∆ 773 817-2∆ 3,350
912-2∆ 1,058 914-2∆ 1,425 91X-2∆ 2,010 91P-2∆ 1,035 917-2∆ 3,900
A12-2∆ 1,515 A14-2∆ 2,100 A1X-2∆ 2,813 A1P-2∆ 1,440 A17-2∆ 5,550
B12-2∆ 2,130 B14-2∆ 2,700 B1X-2∆ 3,375 B1P-2∆ 1,950 B17-2∆ 6,040
C12-2∆ 2,805 C14-2∆ 3,340 C1X-2∆ 3,900 C1P-2∆ 2,440 C17-2∆ 8,100
D12-2∆ 3,375 D14-2∆ 3,900 D1X-2∆ 4,785 D1P-2∆ 3,000 D17-2∆ 9,600
E12-2∆ 4,650 E14-2∆ 5,175 E1X-2∆ 5,815 E1P-2∆ 4,200 E17-2∆ 11,740
F12-2∆ 4,875 F14-2∆ 5,400 F1X-2∆ 6,040 F1P-2∆ 4,425 F17-2∆ 11,965
G12-70∆ 8,625 G14-70∆ 9,000 G1X-70∆ 9,855 Consult factory Consult factory
H12-70∆ 10,380 H14-70∆ 10,800 H1X-70∆ 11,700 Consult factory Consult factory
T12-70∆ 13,465 T14-70∆ 14,250 T1X-70∆ 14,590 Consult factory Consult factory
U12-70∆ 14,325 U14-70∆ 14,850 U1X-70∆ 15,745 Consult factory Consult factory
NEMA rated
J12-2∆ $ 330 J14-2∆ $ 495 J1X-2∆ $ 645 J1P-2∆ $ 315 J17-2∆ $ 1,500
K12-2∆ 383 K14-2∆ 570 K1X-2∆ 743 K1P-2∆ 360 K17-2∆ 1,590
L12-2∆ 465 L14-2∆ 630 L1X-2∆ 831 L1P-2∆ 443 L17-2∆ 1,680
M12-2∆ 719 M14-2∆ 1,103 M1X-2∆ 1,328 M1P-2∆ 698 M17-2∆ 2,600
N12-2∆ 1,058 N14-2∆ 1,425 N1X-2∆ 2,010 N1P-2∆ 1,035 N17-2∆ 3,900
P12-2∆ 2,130 P14-2∆ 2,700 P1X-2∆ 3,375 P1P-2∆ 1,950 P17-2∆ 6,040
Q12-2∆ 4,650 Q14-2∆ 5,175 Q1X-2∆ 5,815 Q1P-2∆ 4,200 Q17-2∆ 11,740
R12-70∆ 10,380 R14-70∆ 10,800 R1X-70∆ 11,700 Consult factory Consult factory
S12-70∆ 14,325 S14-70∆ 14,850 S1X-70∆ 15,745 Consult factory Consult factory
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7.
Enclosed Explosion-proof
Discount schedule AAE [EA] AXE [EB] – A9 - A110
AEAE [EC] – A145 - AF1650
3
Starters
3.18 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Non-reversing
A9 - A185
Single phase
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the sufx
code after the last dash in the catalog number.
Ex.: A 240V coil is required for an A75 starter: 91S-4F
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
Control transformer option
Contactor VA List price
size rating adder
A9 A30 50 $ 360
A40 A75 75 435
A95 A110 100 560
A145 A185 150 720
UL motor
switching
current
Contactor
size
Maximum ratings - UL Listed Open
type
UL Type 1
(Indoor metal)
Maximum motor horsepower ratings
115V 230V Catalog
number List price Catalog
number
List
price
UL rated
9 A9 1/2 111S-2∆ $ 165 11S1-2∆ $ 255
11 A12 3/4 2 21S-2∆ 171 21S1-2∆ 285
17 A16 1 3 31S-2∆ 200 31S1-2∆ 300
28 A26 1.5 5 41S-2∆ 294 41S1-2∆ 405
34 A30 2 7.5 51S-2∆ 372 51S1-2∆ 473
42 A40 37.5 61S-2∆ 423 61S1-2∆ 525
54 A50 37.5 71S-2∆ 458 71S1-2∆ 600
65 A63 5 10 81S-2∆ 522 81S1-2∆ 713
80 A75 7.5 15 91S-2∆ 563 91S1-2∆ 975
110 A110 10 20 A1S-2∆ 765 A1S1-2∆ 1,170
130 A145 10 25 B1S-2∆ 1,315 B1S1-2∆ 1,765
156 A185 15 30 C1S-2∆ 1,730 C1S1-2∆ 2,400
NEMA rated
NEMA
size
Contactor
size
Continuous
current 115V 200V
00 A9 9 1/3 1J1S-2∆ $ 165 J1S1-2∆ $ 255
0 A16 18 12 K1S-2∆ 200 K1S1-2∆ 300
1A26 27 2 3L1S-2∆ 294 L1S1-2∆ 405
2 A50 45 37.5 M1S-2∆ 458 M1S1-2∆ 600
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7.
Coil voltage selection – AF400 - AF750 1
Hz Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E FG H
Open Enclosed
Discount schedule AA [OA] AAE [EA] – A9 - A110
AEA [OC] AEAE [EC] – A145 - AF1650
3
Starters
Low Voltage Products & Systems 3.19
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
Non-reversing
A9 - A185
Single phase
Enclosed
Discount schedule AAE [EA] – A9 - A110
AEAE [EC] – A145 - AF1650
UL Type 3R
(Outdoor metal)
UL Type 12
(Metal dustight)
UL Type 4
(Watertight)
UL Type 4X
(Stainless steel)
UL Type 1, 3R, 4, 4X & 12
(Plastic)
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
UL rated
11S3-2∆ $ 330 11S2-2∆ $ 330 11S4-2∆ $ 495 11SX-2∆ $ 645 11SP-2∆ $ 315
21S3-2∆ 360 21S2-2∆ 360 21S4-2∆ 540 21SX-2∆ 713 21SP-2∆ 345
31S3-2∆ 383 31S2-2∆ 383 31S4-2∆ 570 31SX-2∆ 743 31SP-2∆ 360
41S3-2∆ 465 41S2-2∆ 465 41S4-2∆ 630 41SX-2∆ 831 41SP-2∆ 443
51S3-2∆ 533 51S2-2∆ 533 51S4-2∆ 690 51SX-2∆ 885 51SP-2∆ 510
61S3-2∆ 578 61S2-2∆ 578 61S4-2∆ 1,050 61SX-2∆ 1,275 61SP-2∆ 555
71S3-2∆ 719 71S2-2∆ 719 71S4-2∆ 1,103 71SX-2∆ 1,328 71SP-2∆ 698
81S3-2∆ 795 81S2-2∆ 795 81S4-2∆ 1,170 81SX-2∆ 1,410 81SP-2∆ 773
91S3-2∆ 1,058 91S2-2∆ 1,058 91S4-2∆ 1,425 91SX-2∆ 2,010 91SP-2∆ 1,035
A1S3-2∆ 1,515 A1S2-2∆ 1,515 A1S4-2∆ 2,100 A1SX-2∆ 2,813 A1SP-2∆ 1,440
B1S3-2∆ 2,130 B1S2-2∆ 2,130 B1S4-2∆ 2,700 B1SX-2∆ 3,375 B1SP-2∆ 1,950
C1S3-2∆ 2,805 C1S2-2∆ 2,805 C1S4-2∆ 3,340 C1SX-2∆ 3,900 C1SP-2∆ 2,440
NEMA rated
J1S3-2∆ $ 330 J1S2-2∆ $ 330 J1S4-2∆ $ 495 J1SX-2∆ $ 645 J1SP-2∆ $ 315
K1S3-2∆ 383 K1S2-2∆ 383 K1S4-2∆ 570 K1SX-2∆ 743 K1SP-2∆ 360
L1S3-2∆ 465 L1S2-2∆ 465 L1S4-2∆ 630 L1SX-2∆ 831 L1SP-2∆ 443
M1S3-2∆ 719 M1S2-2∆ 719 M1S4-2∆ 1,103 M1SX-2∆ 1,328 M1SP-2∆ 698
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7.
3
Starters
3.20 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Reversing
A9 - AF750
Three phase
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the sufx
code after the last dash in the catalog number.
Ex.: A 240V coil is required for an A75 starter: 92-4F
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
NOTE: For AF50 – AF 300 starters, consult factory.
1 AF400 - AF750 only.
UL motor
switching
current
Contactor
size
Maximum ratings - UL Listed Open
type
UL Type 1
(Indoor metal)
UL type 3R
(Outdoor metal)
Maximum motor horsepower ratings
200/208V 230/240V 480/480V 575/600V Catalog
number List price Catalog
number
List
price
Catalog
number
List
price
UL rated
9 A9 2 2 5 7.5 12-2∆ $ 342 121-2∆ $ 510 123-2∆ $ 630
11 A12 3 3 7.5 10 22-2∆ 387 221-2∆ 585 223-2∆ 705
17 A16 5 5 10 15 32-2∆ 443 321-2∆ 630 323-2∆ 750
28 A26 7.5 10 20 25 42-2∆ 503 421-2∆ 810 423-2∆ 900
34 A30 10 10 25 30 52-2∆ 675 521-2∆ 953 523-2∆ 1,043
42 A40 10 15 30 40 62-2∆ 765 621-2∆ 1,080 623-2∆ 1,305
54 A50 15 20 40 50 72-2∆ 1,152 721-2∆ 1,395 723-2∆ 1,763
65 A63 20 25 50 50 82-2∆ 1,515 821-2∆ 1,780 823-2∆ 2,310
80 A75 25 30 60 75 92-2∆ 1,620 921-2∆ 1,905 923-2∆ 2,813
110 A110 30 40 75 100 A2-2∆ 1,800 A21-2∆ 2,970 A23-2∆ 3,630
130 A145 40 50 100 125 B2-2∆ 2,997 B21-2∆ 3,570 B23-2∆ 4,275
156 A185 50 60 125 150 C2-2∆ 3,996 C21-2∆ 4,755 C23-2∆ 5,215
192 A210 60 75 150 200 D2-2∆ 4,650 D21-2∆ 5,580 D23-2∆ 6,255
248 A260 75 100 200 250 E2-2∆ 5,436 E21-2∆ 7,615 E23-2∆ 8,355
302 A300 100 100 250 300 F2-2∆ 6,190 F21-2∆ 8,070 F23-2∆ 8,835
414 AF400 125 150 350 400 G2-70∆ 7,980 G21-70∆ 15,450 G23-70∆ 16,125
480 AF460 150 200 400 500 H2-70∆ 14,550 H21-70∆ 22,482 H23-70∆ 23,230
590 AF580 200 250 500 600 T2-70∆ 19,755 T21-70∆ 25,800 T23-70∆ 26,250
810 AF750 250 300 600 700 U2-70∆ 21,105 U21-70∆ 29,250 U23-70∆ 30,225
NEMA rated
NEMA Contactor Continuous 200V 230V 460/575V
size size current
00 A9 9 1.5 1.5 2 J2-2∆ $ 342 J21-2∆ $ 510 J23-2∆ $ 630
0 A16 18 3 3 5 K2-2∆ 443 K21-2∆ 630 K23-2∆ 750
1A26 27 7.5 7.5 10 L2-2∆ 503 L21-2∆ 810 L23-2∆ 900
2 A50 45 10 15 25 M2-2∆ 1,152 M21-2∆ 1,395 M23-2∆ 1,763
3A75 90 25 30 50 N2-2∆ 1,620 N21-2∆ 1,905 N23-2∆ 2,813
4 A145 135 40 50 100 P2-2∆ 2,997 P21-2∆ 3,570 P23-2∆ 4,275
5 A260 270 75 100 200 Q2-2∆ 5,436 Q21-2∆ 7,615 Q23-2∆ 8,355
6 AF460 540 150 200 400 R2-70∆ 14,550 R21-70∆ 22,482 R23-70∆ 23,230
7AF750 810 300 600 S2-70∆ 21,105 S21-70∆ 29,250 S23-70∆ 30,225
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7.
Control transformer option
Contactor VA List price
size rating adder
A9 A40 50 $ 360
A50 A75 75 435
A95 A110 100 560
A145 A185 150 720
A210 A300 250 795
AF400 AF460 150 720
AF580 AF750 250 795
Reference page 3.3 for Extra VA under all (Control Transformer Options chart)
Coil voltage selection – A9 - A300
Hz Contactor
type
Volts
24 110 120 208 220 240 440 480 500 600
60 A 1 23456 7
50 A 1 2 4 7
Coil voltage selection – AF400 - AF750 1
Hz Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E FG H
Open Enclosed
Discount schedule AA [OA] AAE [EA] – A9 - A110
AEA [OC] AEAE [EC] – A145 - AF1650
3
Starters
Low Voltage Products & Systems 3.21
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
Reversing
A9 - AF750
Three phase
UL Type 12
(Metal dustight)
UL Type 4
(Watertight)
UL Type 4X
(Stainless steel)
UL Type 1, 3R, 4, 4X & 12
(Plastic)
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
UL rated
122-2∆ $ 630 124-2∆ $ 810 12X-2∆ $ 1,125 12P-2∆ $ 608
222-2∆ 705 224-2∆ 915 22X-2∆ 1,230 22P-2∆ 683
322-2∆ 750 324-2∆ 990 32X-2∆ 1,313 32P-2∆ 765
422-2∆ 900 424-2∆ 1,125 42X-2∆ 1,725 42P-2∆ 960
522-2∆ 1,043 524-2∆ 1,313 52X-2∆ 1,868 52P-2∆ 1,103
622-2∆ 1,305 624-2∆ 1,500 62X-2∆ 2,010 62P-2∆ 1,230
722-2∆ 1,763 724-2∆ 1,875 72X-2∆ 2,213 72P-2∆ 1,530
822-2∆ 2,310 824-2∆ 2,588 82X-2∆ 3,143 82P-2∆ 1,695
922-2∆ 2,813 924-2∆ 3,113 92X-2∆ 3,600 92P-2∆ 2,250
A22-2∆ 3,630 A24-2∆ 3,900 A2X-2∆ 4,479 A2P-2∆ 3,230
B22-2∆ 4,275 B24-2∆ 4,650 B2X-2∆ 5,665 B2P-2∆ 3,804
C22-2∆ 5,215 C24-2∆ 5,550 C2X-2∆ 6,555 C2P-2∆ 4,640
D22-2∆ 6,255 D24-2∆ 6,640 D2X-2∆ 7,680 D2P-2∆ 5,566
E22-2∆ 8,355 E24-2∆ 9,340 E2X-2∆ 11,995 E2P-2∆ 7,434
F22-2∆ 8,835 F24-2∆ 10,015 F2X-2∆ 12,055 F2P-2∆ 7,861
G22-70∆ 16,125 G24-70∆ 17,100 G2X-70∆ 20,690 Consult factory
H22-70∆ 23,230 H24-70∆ 23,625 H2X-70∆ 24,250 Consult factory
T22-70∆ 26,250 T24-70∆ 27,000 T2X-70∆ 28,500 Consult factory
U22-70∆ 30,225 U24-70∆ 31,275 U2X-70∆ 32,625 Consult factory
NEMA rated
J22-2∆ $ 630 J24-2∆ $ 810 J2X-2∆ $ 1,125 J2P-2∆ $ 608
K22-2∆ 750 K24-2∆ 990 K2X-2∆ 1,313 K2P-2∆ 765
L22-2∆ 900 L24-2∆ 1,125 L2X-2∆ 1,725 L2P-2∆ 960
M22-2∆ 1,763 M24-2∆ 1,875 M2X-2∆ 2,213 M2P-2∆ 1,530
N22-2∆ 2,813 N24-2∆ 3,113 N2X-2∆ 3,600 N2P-2∆ 2,250
P22-2∆ 4,275 P24-2∆ 4,650 P2X-2∆ 5,665 P2P-2∆ 3,804
Q22-2∆ 8,355 Q24-2∆ 9,340 Q2X-2∆ 11,995 Q2P-2∆ 7,434
R22-70∆ 23,230 R24-70∆ 23,625 R2X-70∆ 24,250 Consult factory
S22-70∆ 30,225 S24-70∆ 31,275 S2X-70∆ 32,625 Consult factory
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7.
Enclosed
Discount schedule AAE [EA] – A9 - A110
AEAE [EC] – A145 - AF1650
3
Starters
3.22 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2 Speed, 1 winding
A9 - AF750
Three phase
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the sufx
code after the last dash in the catalog number.
Ex.: A 240V coil is required for an A110 starter: A3-4∆1∆
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
Description
Motors that have separate windings for each speed provide more combinations of
speed variations. Multi-speed starters from ABB Control are available for constant
horsepower, constant torque and variable torque motors.
Constant horsepower
Motors that maintain the same horsepower regardless of speed are called
constant horsepower motors. These motors are used in applications like
metal working.
Constant torque
Motors that maintain constant torque at all speeds are called constant torque
motors. In applications like conveyors, horsepower varies directly with speed.
Variable torque motors
Motors that produce a torque characteristic which varies as the square of
the speed are called variable torque motors and are used in applications like
blowers and fans.
NOTE: For AF50 – AF 300 starters, consult factory.
1 AF400 - AF750 only.
UL motor
switching
current
Contactor
size
Maximum ratings - UL Listed Open
type
UL Type 1
(Indoor metal)
UL type 3R
(Outdoor metal)
Maximum motor horsepower ratings
200/208V 230/240V 480/480V 575/600V Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
UL rated
9A92 2 5 7.5 13-2∆1∆ $ 504 131-2∆1∆ $ 690 133-2∆1∆ $ 810
11 A12 3 3 7.5 10 23-2∆1∆ 525 231-2∆1∆ 771 233-2∆1∆ 891
17 A16 5 5 10 15 33-2∆1∆ 581 331-2∆1∆ 837 333-2∆1∆ 957
28 A26 7.5 10 20 25 43-2∆1∆ 752 431-2∆1∆ 1,097 433-2∆1∆ 1,187
34 A30 10 10 25 30 53-2∆1∆ 1,038 531-2∆1∆ 1,316 533-2∆1∆ 1,406
42 A40 10 15 30 40 63-2∆1∆ 1,259 631-2∆1∆ 1,577 633-2∆1∆ 1,802
54 A50 15 20 40 50 73-2∆1∆ 1,697 731-2∆1∆ 1,940 733-2∆1∆ 2,307
65 A63 20 25 50 50 83-2∆1∆ 2,150 831-2∆1∆ 2,195 833-2∆1∆ 2,945
80 A75 25 30 60 75 93-2∆1∆ 2,307 931-2∆1∆ 2,592 933-2∆1∆ 3,500
110 A110 30 40 75 100 A3-2∆1∆ 2,681 A31-2∆1∆ 3,851 A33-2∆1∆ 4,511
130 A145 40 50 100 125 B3-2∆1∆ 4,506 B31-2∆1∆ 5,079 B33-2∆1∆ 5,784
156 A185 50 60 125 150 C3-2∆1∆ 5,845 C31-2∆1∆ 6,605 C33-2∆1∆ 7,059
192 A210 60 75 150 200 D3-2∆1∆ 6,895 D31-2∆1∆ 7,825 D33-2∆1∆ 8,500
248 A260 75 100 200 250 E3-2∆1∆ 8,535 E31-2∆1∆ 10,710 E33-2∆1∆ 11,455
302 A300 100 100 250 300 F3-2∆1∆ 9,171 F31-2∆1∆ 11,391 F33-2∆1∆ 12,155
414 AF400 125 150 350 400 G3-70∆1∆ 10,100 G31-70∆1∆ 19,460 G33-70∆1∆ 20,135
480 AF460 150 200 400 500 H3-70∆1∆ 17,995 H31-70∆1∆ 28,910 H23-70∆1∆ 29,652
590 AF580 200 250 500 600 T3-70∆1∆ 23,735 T31-70∆1∆ 35,400 T33-70∆1∆ 35,850
810 AF750 250 300 600 700 U3-70∆1∆ 26,645 U31-70∆1∆ 39,195 U33-70∆1∆ 40,170
NEMA rated
NEMA Contactor Continuous 200V 230V 460/575V
size size current
00 A9 9 1.5 1.5 2 J3-2∆1∆ $ 504 J31-2∆1∆ $ 690 J33-2∆1∆ $ 810
0 A16 18 335 K3-2∆1∆ 581 K31-2∆1∆ 837 K33-2∆1∆ 957
1A26 27 7.5 7.5 10 L3-2∆1∆ 752 L31-2∆1∆ 1,097 L33-2∆1∆ 1,187
2 A50 45 10 15 25 M3-2∆1∆ 1,697 M31-2∆1∆ 1,940 M33-2∆1∆ 2,307
3A75 90 25 30 50 N3-2∆1∆ 2,307 N31-2∆1∆ 2,589 N33-2∆1∆ 3,500
4 A145 135 40 50 100 P3-2∆1∆ 4,506 P31-2∆1∆ 5,079 P33-2∆1∆ 5,784
5 A260 270 75 100 200 Q3-2∆1∆ 8,535 Q31-2∆1∆ 10,710 Q33-2∆1∆ 11,455
6 AF460 540 150 200 400 R3-70∆1∆ 17,995 R31-70∆1∆ 28,910 R33-70∆1∆ 29,652
7AF750 810 300 600 S3-70∆1∆ 26,645 S31-70∆1∆ 39,195 S33-70∆1∆ 40,170
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7. 1st ∆ low speed; 2nd ∆ high speed.
Control transformer option
Contactor VA List price
size rating adder
A9 A40 50 $ 360
A50 A75 75 435
A95 A110 100 560
A145 A185 150 720
A210 A300 250 795
AF400 AF460 150 720
AF580 AF750 250 795
Reference page 3.3 for Extra VA under all (Control Transformer Options chart)
Coil voltage selection – A9 - A300
Hz Contactor
type
Volts
24 110 120 208 220 240 440 480 500 600
60 A 1 23456 7
50 A 1 2 4 7
Coil voltage selection – AF400 - AF750 1
Hz Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E FG H
Open Enclosed
Discount schedule AA [OA] AAE [EA] – A9 - A110
AEA [OC] AEAE [EC] – A145 - AF1650
3
Starters
Low Voltage Products & Systems 3.23
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
2 Speed, 1 winding
A9 - AF750
Three phase
UL Type 12
(Metal dustight)
UL Type 4
(Watertight)
UL Type 4X
(Stainless steel)
UL Type 1, 3R, 4, 4X & 12
(Plastic)
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
UL rated
132-2∆1∆ $ 810 134-2∆1∆ $ 1,020 13X-2∆1∆ $ 1,305 13P-2∆1∆ $ 788
232-2∆1∆ 891 234-2∆1∆ 1,095 23X-2∆1∆ 1,416 23P-2∆1∆ 869
332-2∆1∆ 957 334-2∆1∆ 1,215 33X-2∆1∆ 1,520 33P-2∆1∆ 972
432-2∆1∆ 1,187 434-2∆1∆ 1,515 43X-2∆1∆ 2,012 43P-2∆1∆ 1,247
532-2∆1∆ 1,406 534-2∆1∆ 1,688 53X-2∆1∆ 2,231 53P-2∆1∆ 1,466
632-2∆1∆ 1,802 634-2∆1∆ 2,100 63X-2∆1∆ 2,507 63P-2∆1∆ 1,727
732-2∆1∆ 2,307 734-2∆1∆ 2,528 73X-2∆1∆ 2,757 73P-2∆1∆ 2,075
832-2∆1∆ 2,945 834-2∆1∆ 3,285 83X-2∆1∆ 3,777 83P-2∆1∆ 2,330
932-2∆1∆ 3,500 934-2∆1∆ 3,788 93X-2∆1∆ 4,287 93P-2∆1∆ 2,835
A32-2∆1∆ 4,511 A34-2∆1∆ 4,800 A3X-2∆1∆ 5,358 A3P-2∆1∆ 4,300
B32-2∆1∆ 5,784 B34-2∆1∆ 6,265 B3X-2∆1∆ 7,175 B3P-2∆1∆ 5,513
C32-2∆1∆ 7,059 C34-2∆1∆ 7,440 C3X-2∆1∆ 8,400 C3P-2∆1∆ 6,729
D32-2∆1∆ 8,500 D34-2∆1∆ 8,890 D3X-2∆1∆ 9,925 D3P-2∆1∆ 8,103
E32-2∆1∆ 11,455 E34-2∆1∆ 12,940 E3X-2∆1∆ 15,090 E3P-2∆1∆ 10,919
F32-2∆1∆ 12,155 F34-2∆1∆ 13,425 F3X-2∆1∆ 16,275 F3P-2∆1∆ 11,586
G32-70∆1∆ 20,135 G34-70∆1∆ 21,600 G3X-70∆1∆ 24,700
H32-70∆1∆ 29,652 H34-70∆1∆ 30,000 H3X-70∆1∆ 30,675
T32-70∆1∆ 35,850 T34-70∆1∆ 36,225 T3X-70∆1∆ 38,097
U32-70∆1∆ 40,170 U34-70∆1∆ 40,875 U3X-70∆1∆ 42,570
NEMA rated
J32-2∆1∆ $ 810 J34-2∆1∆ $ 1,020 J3X-2∆1∆ $ 1,305 J3P-2∆1∆ $ 788
K32-2∆1∆ 957 K34-2∆1∆ 1,215 K3X-2∆1∆ 1,520 K3P-2∆1∆ 972
L32-2∆1∆ 1,187 L34-2∆1∆ 1,515 L3X-2∆1∆ 2,012 L3P-2∆1∆ 1,247
M32-2∆1∆ 2,307 M34-2∆1∆ 2,528 M3X-2∆1∆ 2,757 M3P-2∆1∆ 2,075
N32-2∆1∆ 3,500 N34-2∆1∆ 3,788 N3X-2∆1∆ 4,287 N3P-2∆1∆ 2,835
P32-2∆1∆ 5,748 P34-2∆1∆ 6,265 P3X-2∆1∆ 7,175 P3P-2∆1∆ 5,513
Q32-2∆1∆ 11,455 Q34-2∆1∆ 12,940 Q3X-2∆1∆ 15,090 Q3P-2∆1∆ 10,919
R32-70∆1∆ 29,652 R34-70∆1∆ 30,000 R3X-70∆1∆ 30,675
S32-70∆1∆ 40,170 S34-70∆1∆ 40,875 S3X-70∆1∆ 42,570
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7. 1st ∆ low speed; 2nd ∆ high speed.
Enclosed
Discount schedule AAE [EA] – A9 - A110
AEAE [EC] – A145 - AF1650
3
Starters
3.24 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2 Speed, 2 winding
A9 - AF750
Three phase
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the sufx
code after the last dash in the catalog number.
Ex.: A 240V coil is required for an A110 starter: A3-4∆2∆
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
Description
Motors that have separate windings for each speed provide more combinations of
speed variations. Multi-speed starters from ABB Control are available for constant
horsepower, constant torque and variable torque motors.
Constant horsepower
Motors that maintain the same horsepower regardless of speed are called
constant horsepower motors. These motors are used in applications like
metal working.
Constant torque
Motors that maintain constant torque at all speeds are called constant torque
motors. In applications like conveyors, horsepower varies directly with speed.
Variable torque motors
Motors that produce a torque characteristic which varies as the square of
the speed are called variable torque motors and are used in applications like
blowers and fans.
NOTE: For AF50 – AF 300 starters, consult factory.
1 AF400 - AF 750 only.
UL motor
switching
current
Contactor
size
Maximum ratings - UL Listed Open
type
UL Type 1
(Indoor metal)
UL type 3R
(Outdoor metal)
Maximum motor horsepower ratings
200/208V 230/240V 480/480V 575/600V Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
UL rated
9A92 2 5 7.5 13-2∆2∆ $ 396 131-2∆2∆ $ 582 133-2∆2∆ $ 702
11 A12 3 3 7.5 10 23-2∆2∆ 426 231-2∆2∆ 657 233-2∆2∆ 777
17 A16 5 5 10 15 33-2∆2∆ 476 331-2∆2∆ 702 333-2∆2∆ 822
28 A26 7.5 10 20 25 43-2∆2∆ 552 431-2∆2∆ 882 433-2∆2∆ 972
34 A30 10 10 25 30 53-2∆2∆ 747 531-2∆2∆ 1,025 533-2∆2∆ 1,115
42 A40 10 15 30 40 63-2∆2∆ 834 631-2∆2∆ 1,152 633-2∆2∆ 1,377
54 A50 15 20 40 50 73-2∆2∆ 1,224 731-2∆2∆ 1,467 733-2∆2∆ 1,835
65 A63 20 25 50 50 83-2∆2∆ 1,587 831-2∆2∆ 1,632 833-2∆2∆ 2,382
80 A75 25 30 60 75 93-2∆2∆ 1,692 931-2∆2∆ 1,977 933-2∆2∆ 2,885
110 A110 30 40 75 100 A3-2∆2∆ 1,872 A31-2∆2∆ 3,042 A33-2∆2∆ 3,702
130 A145 40 50 100 125 B3-2∆2∆ 3,069 B31-2∆2∆ 3,642 B33-2∆2∆ 4,347
156 A185 50 60 125 150 C3-2∆2∆ 4,068 C31-2∆2∆ 4,827 C33-2∆2∆ 5,285
192 A210 60 75 150 200 D3-2∆2∆ 4,722 D31-2∆2∆ 5,652 D33-2∆2∆ 6,327
248 A260 75 100 200 250 E3-2∆2∆ 5,500 E31-2∆2∆ 7,685 E33-2∆2∆ 8,427
302 A300 100 100 250 300 F3-2∆2∆ 6,340 F31-2∆2∆ 8,142 F33-2∆2∆ 8,905
414 AF400 125 150 350 400 G3-70∆2∆ 6,855 G31-70∆2∆ 15,522 G33-70∆2∆ 16,197
480 AF460 150 200 400 500 H3-70∆2∆ 13,560 H31-70∆2∆ 22,554 H23-70∆2∆ 23,300
590 AF580 200 250 500 600 T3-70∆2∆ 18,660 T31-70∆2∆ 25,872 T33-70∆2∆ 26,332
810 AF750 250 300 600 700 U3-70∆2∆ 20,025 U31-70∆2∆ 29,332 U33-70∆2∆ 30,297
NEMA rated
NEMA Contactor Continuous 200V 230V 460/575V
size size current
00 A9 9 1.5 1.5 2 J3-2∆2∆ $ 396 J31-2∆2∆ $ 582 J33-2∆2∆ $ 702
0 A16 18 335 K3-2∆2∆ 476 K31-2∆2∆ 702 K33-2∆2∆ 822
1A26 27 7.5 7.5 10 L3-2∆2∆ 552 L31-2∆2∆ 882 L33-2∆2∆ 972
2 A50 45 10 15 25 M3-2∆2∆ 1,224 M31-2∆2∆ 1,467 M33-2∆2∆ 1,835
3A75 90 25 30 50 N3-2∆2∆ 1,692 N31-2∆2∆ 1,977 N33-2∆2∆ 2,885
4 A145 135 40 50 100 P3-2∆2∆ 3,069 P31-2∆2∆ 3,642 P33-2∆2∆ 4,347
5 A260 270 75 100 200 Q3-2∆2∆ 5,508 Q31-2∆2∆ 7,685 Q33-2∆2∆ 8,427
6 AF460 540 150 200 400 R3-70∆2∆ 13,560 R31-70∆2∆ 22,554 R33-70∆2∆ 23,300
7AF750 810 300 600 S3-70∆2∆ 20,025 S31-70∆2∆ 29,322 S33-70∆2∆ 30,297
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7. 1st ∆ low speed; 2nd ∆ high speed.
Control transformer option
Contactor VA List price
size rating adder
A9 A40 50 $ 360
A50 A75 75 435
A95 A110 100 560
A145 A185 150 720
A210 A300 250 795
AF400 AF460 150 720
AF580 AF750 250 795
Reference page 3.3 for Extra VA under all (Control Transformer Options chart)
Coil voltage selection – A9 - A300
Hz Contactor
type
Volts
24 110 120 208 220 240 440 480 500 600
60 A 1 23456 7
50 A 1 2 4 7
Coil voltage selection – AF400 - AF750 1
Hz Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E FG H
Open Enclosed
Discount schedule AA [OA] AAE [EA] – A9 - A110
AEA [OC] AEAE [EC] – A145 - AF1650
3
Starters
Low Voltage Products & Systems 3.25
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202
2 Speed, 2 winding
A9 - AF750
Three phase
UL Type 12
(Metal dustight)
UL Type 4
(Watertight)
UL Type 4X
(Stainless steel)
UL Type 1, 3R, 4, 4X & 12
(Plastic)
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
Catalog
number
List
price
UL rated
132-2∆2∆ $ 702 134-2∆2∆ $ 915 13X-2∆2∆ $ 1,197 13P-2∆2∆ $ 680
232-2∆2∆ 777 234-2∆2∆ 990 23X-2∆2∆ 1,302 23P-2∆2∆ 755
332-2∆2∆ 822 334-2∆2∆ 1,065 33X-2∆2∆ 1,385 33P-2∆2∆ 837
432-2∆2∆ 972 434-2∆2∆ 1,200 43X-2∆2∆ 1,797 43P-2∆2∆ 1,032
532-2∆2∆ 1,115 534-2∆2∆ 1,388 53X-2∆2∆ 1,940 53P-2∆2∆ 1,175
632-2∆2∆ 1,377 634-2∆2∆ 1,545 63X-2∆2∆ 2,082 63P-2∆2∆ 1,302
732-2∆2∆ 1,835 734-2∆2∆ 1,988 73X-2∆2∆ 2,285 73P-2∆2∆ 1,602
832-2∆2∆ 2,382 834-2∆2∆ 2,513 83X-2∆2∆ 3,215 83P-2∆2∆ 1,767
932-2∆2∆ 2,885 934-2∆2∆ 3,090 93X-2∆2∆ 3,672 93P-2∆2∆ 2,200
A32-2∆2∆ 3,702 A34-2∆2∆ 3,863 A3X-2∆2∆ 4,550 A3P-2∆2∆ 3,300
B32-2∆2∆ 4,347 B34-2∆2∆ 4,650 B3X-2∆2∆ 5,735 B3P-2∆2∆ 3,919
C32-2∆2∆ 5,285 C34-2∆2∆ 5,740 C3X-2∆2∆ 6,627 C3P-2∆2∆ 4,857
D32-2∆2∆ 6,327 D34-2∆2∆ 6,510 D3X-2∆2∆ 7,752 D3P-2∆2∆ 5,899
E32-2∆2∆ 8,427 E34-2∆2∆ 9,150 E3X-2∆2∆ 12,065 E3P-2∆2∆ 7,512
F32-2∆2∆ 8,905 F34-2∆2∆ 9,750 F3X-2∆2∆ 13,025 F3P-2∆2∆ 7,990
G32-70∆2∆ 16,197 G34-70∆2∆ 17,100 G3X-70∆2∆ 20,760
H32-70∆2∆ 23,300 H34-70∆2∆ 23,700 H3X-70∆2∆ 24,320
T32-70∆2∆ 26,322 T34-70∆2∆ 27,000 T3X-70∆2∆ 28,570
U32-70∆2∆ 30,297 U34-70∆2∆ 30,900 U3X-70∆2∆ 32,697
NEMA rated
J32-2∆2∆ $ 702 J34-2∆2∆ $ 915 J3X-2∆2∆ $ 1,197 J3P-2∆2∆ $ 680
K32-2∆2∆ 822 K34-2∆2∆ 1,065 K3X-2∆2∆ 1,385 K3P-2∆2∆ 837
L32-2∆2∆ 972 L34-2∆2∆ 1,200 L3X-2∆2∆ 1,797 L3P-2∆2∆ 1,032
M32-2∆2∆ 1,835 M34-2∆2∆ 1,988 M3X-2∆2∆ 2,285 M3P-2∆2∆ 1,602
N32-2∆2∆ 2,885 N34-2∆2∆ 3,090 N3X-2∆2∆ 3,672 N3P-2∆2∆ 2,200
P32-2∆2∆ 4,347 P34-2∆2∆ 4,650 P3X-2∆2∆ 5,735 P3P-2∆2∆ 3,919
Q32-2∆2∆ 8,427 Q34-2∆2∆ 9,150 Q3X-2∆2∆ 12,065 Q3P-2∆2∆ 7,512
R32-70∆2∆ 23,300 R34-70∆2∆ 23,700 R3X-70∆2∆ 24,320
S32-70∆2∆ 30,297 S34-70∆2∆ 30,900 S3X-70∆2∆ 32,697
∆ Overload relay sufx code. Select from the overload relay selection chart on pages 3.6 - 3.7. 1st ∆ low speed; 2nd ∆ high speed.
Enclosed
Discount schedule AAE [EA] – A9 - A110
AEAE [EC] – A145 - AF1650
3
Starters
3.26 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Plastic enclosed, IP65
A9 - A16
Three phase & single phase
Enclosed – Three phase
Maximum motor horsepower ratings
2 2 5 7.5 A9SD-84∆ $ 233 A9SD-84∆R$ 240 A9SD-84∆A $ 278
3 3 7.5 10 A12SD-84∆ 248 A12SD-84∆R 255 A12SD-84∆A 293
5 5 10 15 A16SD-84∆ 278 A16SD-84∆R 293 A16SD-84∆A 330
208V 240V 480V 575V/600V
Catalog List Catalog List Catalog List
number price number price number price
with blank cover with reset only with start & stop/reset
∆ Overload Relay sufx code. Select from the overload relay selection chart on page 3.6.
0.1 – 0.16 TA25DU0.16 A
0.16 – 0.25 TA25DU0.25 B
0.25 – 0.4 TA25DU0.4 C
0.4 – 0.63 TA25DU0.63 D
0.63 – 1.0 TA25DU1.0 E
1.0 – 1.4 TA25DU1.4 F
1.4 – 1.8 TA25DU1.8 G
1.7 – 2.4 TA25DU2.4 H
2.2 – 3.1 TA25DU3.1 J
2.8 – 4.0 TA25DU4.0 K
3.5 – 5.0 TA25DU5.0 L
4.5 – 6.5 TA25DU6.5 M
6.0 – 8.5 TA25DU8.5 N
7.5 – 11 TA25DU11 P
10 – 14 TA25DU14 Q
13 – 19 TA25DU19 R
Overload relay selection chart
For Current Catalog Starter
contactor range number sufx
sizes (motor a) code
A16
A9
A12
Enclosed
Discount schedule AAE [EA]
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the sufx
code after the last dash in the catalog number.
Ex.: A 240V coil is required for an A9 starter: A9SD-80E
D.C. operated starters
If DC operation is required, consult factory.
Coil voltage selection – A9 - A16 starters
Cntr Volts
Hz type 12 24 48 110 120 125 208 220 240 277 380 415 440 480 500 600
60 A 81 83 84 84 34 36 80 42 86 86 51 53 55
50 A 81 83 84 80 85 86 55
Enclosed – Single phase
Maximum motor horsepower ratings
1/2 1 A9SSD-84∆ $ 233 A9SSD-84∆R$ 240 A9SSD-84∆A $ 278
3/4 2 A12SSD-84∆ 248 A12SSD-84∆R 255 A12SSD-84∆A 293
1 3 A16SSD-84∆ 278 A16SSD-84∆R 293 A16SSD-84∆A 330
115V 230V
Catalog List Catalog List Catalog List
number price number price number price
with blank cover with reset only with start & stop/reset