2.3 Output over-current protection
! AEW series DC/DC converters feature Over-current Protection (OCP) circuits.
When output current exceeds 110% to 150% of rated current, such as during a short
circuit condition, the output will shutdown immediately, and can tolerate short
circuit conditions indefinitely.
! When the overcurrent condition is removed, the converter will automatically
restart.
2.4 Output over-voltage shutdown (OVP)
! The AEW series provides over-voltage protection on the output, which will
shut the output off if the voltage exceeds 116 to 150% of the nominal output
voltage, and the output is shutdown.#
! It must power the module on again to recover the output.#
! If the module is trimmed up to the voltage, which exceeds the 110% rated
output voltage, the output over-voltage protection will be probably triggered
off.#
! For dual output products:
Through testing the over-voltage condition between +Vo and –V, the
over-voltage protection active (operating at 116% 150% rated output
voltage).
! For triple output products:
Through testing the over-voltage condition between +Vo and COM, the
over-voltage protection active. When Vo1 exceeds 116%~150% rated output
voltage, the over-voltage protection active. After the protection, please turn off
the power supply, and restart after 2-3 seconds, the output will be normal.