IBS OPTOSUB-MA/M/R-LKOPC(-2MBD) Optical Fiber Converter With a Data Transmission Rate of 500 kbaud or 2 Mbaud Data Sheet 5571D 5 5 7 1 A 0 0 0 07/2001 Function Please observe the Optical Fiber Installation Guidelines (DB GB IBS SYS FOC ASSEMBLY). The IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) module converts the INTERBUS remote interface to polymer fibers. An INTERBUS controller board can be equipped with an optical fiber interface using this converter. Unlike other converters, this interface can automatically control the optical transmission power and provides improved bus system diagnostics (optical path diagnostics). 2 3 1 The converter is a bus device, since it is equipped with an INTERBUS protocol chip (OPC). Features - 9-pos. D-SUB connector for plugging onto the controller board - Optical fiber connection via F-SMA connectors - 500 kbaud or 2 Mbaud data transmission rate Figure 1 - Optical path diagnostics 1 Diagnostic indicators - Extended diagnostic options 2 Threaded joint for the D-SUB connector Voltage supply through the INTERBUS interface 3 9-pos. D-SUB male connector 4 Connection for F-SMA connectors - - 4 5 5 7 1 A 0 0 1 IBS OPTOSUB-MA/M/R-LK-OPC Supports paths with optical transmission 5571D 1 IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) Connector Pin Assignment Incoming Remote Bus (9-pos. D-SUB)) O u tg o in g r e m o te b u s R e m o te O U T O U T Pin Signal Designation 1 DO Data, sending direction 2 DI Data, receiving direction 3 GND 4 GND GND (pin 3 and pin 4 internally jumpered) 5 VCCI 5V DC supply, electrically isolated (is only required for RBST connector detection) 6 /DO Negated data, sending direction 7 /DI Negated data, receiving direction 8 VCC 5 V DC supply 9 RBST Connector detection (pin 5 and pin 9 are internally jumpered) IN In c o m in g re m o te b u s R e m o te IN 5 5 7 1 A 0 0 3 Figure 2 Position of the connectors Outgoing Remote Bus (F-SMA Connectors)) Connector Direction Wire Color IN Receive data Black OUT Send data Orange 2 5571D IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) Local Diagnostic and Status Indicators Des. Color Meaning IB DIAG Green INTERBUS diagnostics ON: Supply voltage present, bus active, no module error Flashing Supply voltage present, bus not active at 0.5 Hz: Flashing at 2 Hz: OFF: FO1 5571D Yellow Supply voltage present, module error (bus can be active or not active) Supply voltage not present Status of the incoming optical fiber path ON: If the previous device has optical path diagnostics, the system reserve of the optical transmission has dropped. OFF: Incoming optical fiber path is OK or the previous device does not have optical path diagnostics. 3 IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) Special Features Supports Paths with Optical Transmission 1 Adjustment of optical transmission power: - Automatic recognition of the control function on other modules - Additional diagnostics for optical transmission 2 Confirmation of optical system quality: - No need for an optical cable measuring device - Early error detection through I/O error message to the higher-level control or computer system and diagnostic display on the device - Long-term monitoring of the transmission path is possible 3 Optical path diagnostics 4 5571D IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) T E R B IB D IA G IN U S O U T IN 1 O U T IN R E M O T E O U T R E M O T E O U T C o n tr o lle r b o a rd F O U S R E M O T E IN B IB D IA G T E R 1 IN F O R E M O T E IN Installation C o n tr o lle r b o a rd 7 IB S R L 2 4 B K R B -L K 2 4 V D C IB S S T (Z F ) 2 4 B K M -L K -O P C F F T E R B F F IN E U S E U S E U S E U S R E M O T E IN U S - S IN T E R B U S - S M o d u le Id e n t.: 1 8 5 R E M O T E O U T 5 5 7 1 A 0 0 2 Figure 3 Connection examples Connecting the Converter to the Controller Board Recommended F-SMA connector with bending protection: PSM-SET-FSMA/4-KT. * Insert the converter into the INTERBUS interface of your controller board. * Fit both wires of the polymer fiber cables with F-SMA connectors. * Tighten the two screws manually with a bladed type screwdriver (e.g., SZF 1-0,6X3,5) through the openings above and below the diagnostics display. * Plug the F-SMA connectors into the connections provided and secure the connection with the cap nuts. An external voltage supply is not required for the converter. The converter is supplied via the INTERBUS interface. Connecting Optical Fibers Please refer to the Optical Fiber Installation Guidelines DB GB IBS SYS FOC ASSEMBLY when assembling polymer fiber cables. 5571D Please note that you must always connect sender and receiver with one another. The label for the optical fiber connection (black arrow/orange arrow) corresponds to the color of the optical fiber cables. Connect the individual optical fiber cables between adjacent terminals according to their color (e.g., orange cable for orange connections). 5 IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) Compatibility With Controller Boards You can connect the converter to the following controller boards. Order Designation Order No. Plug-in Converter IBS 24 ETH DSC/I-T 27 22 92 0 yes IBS 24 RFC/486DX/ETH/-T 27 23 00 0 yes IBS ABB DSC/SL/MEMC/I-T 27 22 89 4 yes IBS BA DSC/I-T 27 23 04 2 yes IBS GE 90-70 SC/I-T 27 22 84 9 yes IBS ISA FC/486DX/I-T 27 22 08 5 no IBS ISA FC/DI/I-T 27 25 11 8 no IBS ISA FC/I-T 27 22 02 7 no IBS ISA SC/486DX/I-T 27 23 94 5 no IBS MEA SC/I-T 27 25 59 0 yes IBS PC 104 SC-T 27 21 70 1 - IBS PC ISA SC/I-T 27 19 23 4 no IBS PLC5 DSC/I-T 27 19 02 7 yes IBS S5 DSC/I-T 27 52 00 0 yes IBS S7 300 DSC-T 27 19 97 5 no IBS ST 24 RFC-T 27 25 52 9 yes IBS STME 24 RFC-T 27 25 51 6 yes IBS USC/4-EVA 27 46 25 2 - IBS VME3H SC/I-T 27 22 86 5 yes IBS VME6H SC/I-T 27 22 85 2 yes IBS VME6H SC/RI/I-T 27 22 83 6 yes IBS S7 400 DSC/I-T 27 19 96 2 yes IBS S7 400 ETH DSC/I-T 27 31 10 2 yes 6 Remark Connection is not present. Observe the maximum power of the power supply unit used. Connection is not present. 5571D IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) Programming Data ID code 08hex Length code 00hex Process data channel 0 bits Input address area 0 bytes Output address area 0 bytes Parameter channel (PCP) 0 bytes Register length (bus) 0 bytes Housing Dimensions 5 9 m m 2 .3 2 3 " O rd . N o .: 2 7 3 2 6 3 5 M o d u le Id e n t.: 0 8 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 5 2 m m 2 .0 4 7 " IB S O P T O S U B -M A /M /R -L K -O P C 3 6 m m 1 .4 1 7 " 6 5 m m 2 .5 5 9 " 4 2 m m 1 .6 5 4 " 6 1 m m 2 .4 0 2 " 5 5 7 1 A 0 0 4 Figure 4 5571D Dimensions 7 IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) Technical Data General Data Degree of protection IP 20 Ambient temperature Operation: 0C to +55C (32F to +131F) Storage: -20C to +70C (-4F to +158F) Air and creepance distances DIN VDE 0110-1:1989-01 Supply Voltage Nominal voltage 5 V DC Permissible range 4.75 V DC to 5.25 V DC Current consumption IBS OPTOSUB-MA/M/R-LK-OPC 200 mA, maximum IBS OPTOSUB-MA/M/R-LK-OPC-2MBD 220 mA, maximum Permissible line length The module should only be connected directly to the controller board. Surge protection No Protection against polarity reversal No INTERBUS Interface Incoming remote bus 9-pos. D-SUB male connector Differential voltage interface according to RS-485 Outgoing remote bus F-SMA connector Optical fiber (polymer fiber 980/1000 m) Data transmission rate IBS OPTOSUB-MA/M/R-LK-OPC 500 kbaud IBS OPTOSUB-MA/M/R-LK-OPC-2MBD 2 Mbaud Wavelength 650 nm, typical Optical output power for operation at 0C to +55C (32F to 131F) -2.0 dBm Popt -6.2 dBm Optical output power after voltage reset at 0C to +55C (32F to +131F) -3.5 dBm Popt -7.7 dBm Optical receiver responsivity at 0C to +55C (32F to 131F) -20 dBm 8 5571D IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) INTERBUS Interface Optical overrange at 0C to +55C (32F to 131F) > -2.0 dBm Power reduction resulting from the wavelength drift Taken into consideration System reserve > 3 dBm Bit error rate 10-9 Optical Fiber Cable Cable type Step index Fiber (core/cladding diameter) 980/1000 m Numerical aperture 0.47 Attenuation (50 m [164.042 ft.] fiber measured with 660 nm LED source) 230 dB/km Transmission length between IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) and INTERBUS devices with 50 m (164.042 ft.) system without optical path diagnostics 1 m, minimum, to 35 m (3.281 ft. to 114.829 ft.) Transmission length between IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) and INTERBUS devices with 70 m (229.659 ft.) system or all INTERBUS devices with optical path diagnostics 1 m, minimum, to 50 m (3.281 ft. to 164.042 ft.) Connector type F-SMA standard (type 905 acc. to IEC 60874-2) I/O Error Message MAU error 5571D Yes 9 IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) Description Order Designation Order No. Optical fiber converter with a transmission speed of 500 kbaud IBS OPTOSUB-MA/M/R-LK-OPC 27 32 63 5 Optical fiber converter with a transmission speed of 2 Mbaud IBS OPTOSUB-MA/M/R-LK-OPC 2MBD 27 31 45 8 F-SMA connector set for polymer fiber cables with bending protection (4 pieces) PSM-SET-FSMA/4-KT. 27 99 72 0 Polymer fiber cables for use in humid climates, duplex, 980/100 m, installation PSM-LWL-KDHEAVY-980/1000 27 44 31 9 Polymer fiber cable with increased alternating bending ability (flexible cable tracks, industrial robots) for indoor use PSM-LWL/KDFLEX-980/1000 27 99 74 6 Optical fiber data line: Polymer fiber cable, duplex, 980/1000 m, red, welding-splash-resistant in standard applications; sold by the meter, cable is not pre-assembled PSM-LWL-RUGGED-980/1000 27 44 32 2 Optical fiber data line (flexible): Polymer fiber cable, duplex, 980/1000 m, dark red, welding-splash-resistant in standard applications; tested for flexible cable tracks, sold by the meter cable is not pre-assembled PSM-LWL-RUGGED-FLEX-980/ 1000 27 44 33 5 Optical Fiber Installation Guidelines DB GB IBS SYS FOC ASSEMBLY 94 23 43 9 Bladed type screwdriver SZF 1-0,6X3,5 12 04 51 7 Phoenix Contact GmbH & Co Flachsmarktstr. 8 32825 Blomberg Germany + 49 - 52 35 - 3 00 + 49 - 52 35 - 34 12 00 www.phoenixcontact.com 10 5571D (c) Phoenix Contact 07/2001 Subject to technical modification TNR 90 00 17 6 Ordering Data