MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 1 of 12
www.murata-ps.com
www.murata.com
For full details go to
www.murata-ps.com/rohs
SELECTION GUIDE
Order Code
Nominal Input
Voltage
Output Voltage 1
Output Voltage 2
Output Current 1
Output Current 2
Input Current
at Rated Load
Load Regulation
(Typ)
Load Regulation
(Max)
Ripple & Noise
(Typ)2
Ripple & Noise
(Max)2
Efficiency
(Min)
Efficiency
(Typ)
Isolation Capacitance
MTTF1
MIL. Tel.
V V V mA % mVp-p % pF kHrs
MGJ2D051505SC 5 15 -5 80 40 360 5.7 7 30 50 71 76 3 2095
MGJ2D051509SC 5 15 -8.7 80 40 390 6 7 30 50 73 77.5 3 1902
MGJ2D051515SC 5 15 -15 67 67 492 7 8.5 20 35 74 78 3 2629
MGJ2D051802SC 5 18 -2.5 80 80 410 9 12 20 50 70 75 3 1376 31920
MGJ2D052003SC 5 20 -3.5 80 80 470 8 11 20 50 72 77 3 1253 32603
MGJ2D052005SC 5 20 -5 80 40 440 6.2 8 30 50 74 78.5 3 1655
MGJ2D121503SC 12 15 -3 95 95 170 8 10 25 50 76 80 3 2014 80644
MGJ2D121505SC 12 15 -5 80 40 150 4.7 6 30 50 76 80 3 2339
MGJ2D121509SC 12 15 -8.7 80 40 155 5.3 7.5 30 50 76 80 3 2296
MGJ2D121515SC 12 15 -15 67 67 203 6.0 7 24 40 78 82 3 2707
MGJ2D121802SC 12 18 -2.5 80 80 170 8 11 20 50 74 80 3 1553 36519
MGJ2D122003SC 12 20 -3.5 80 80 190 7 10 20 50 77 82 3 1371 36431
MGJ2D122005SC 12 20 -5 80 40 195 5.5 8 30 45 78 82 3 1799
MGJ2D151505SC 15 15 -5 80 40 120 5 7 30 50 75 80 3 2374
MGJ2D151509SC 15 15 -8.7 80 40 130 5 7 30 50 76 80 3 2736
MGJ2D151515SC 15 15 -15 67 67 167 5.5 7 23 35 75 79 3 2100
MGJ2D151802SC 15 18 -2.5 80 80 130 8 11 20 50 73 79 3 1392 32908
MGJ2D152003SC 15 20 -3.5 80 80 150 7 10 20 50 76 81 3 2000 80000
MGJ2D152005SC 15 20 -5 80 40 145 6 8 30 50 78 81 3 1864
MGJ2D241503SC 24 15 -3 95 95 90 8 10 25 50 76 80 4 2535 70910
MGJ2D241505SC 24 15 -5 80 40 75 4.6 7 30 50 75 80.5 4 2194
MGJ2D241509SC 24 15 -8.7 80 40 80 4.8 7 30 50 77 82 4 2275
MGJ2D241709SC 24 17 -9 80 80 105 6 8 30 50 78 83 4 1050 47000
MGJ2D241802SC 24 18 -2.5 80 80 90 8 11 20 50 74 80 4 1461 32315
MGJ2D242003SC 24 20 -3.5 80 80 90 7 10 20 50 76 82 4 1333 32482
MGJ2D242005SC 24 20 -5 80 40 90 6 8 30 50 78 82 4 1725
INPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Voltage range
Continuous operation, 5V input types 4.5 5 5.5
V
Continuous operation, 12V input types 10.8 12 13.2
Continuous operation, 15V input types 13.5 15 16.5
Continuous operation, 24V input types 21.6 24 26.4
Input reflected ripple
051505, 051509, 051515, 052003 & 052005 types 40
mA
121503, 121505, 121509, 121515, 122003,
122005, 151505, 151509, 151515 & 152005 types 20
051802, 241505, 241509, 241709, 241802 &
242005 types 15
122003, 121802, 151802, 152003, 241503,
241802 & 242003 types 10
1. Calculated using MIL-HDBK-217 FN2 and Telecordia SR-332 calculation model with nominal input voltage at full load.
2. See ripple & noise test method.
3. ANSI/AAMI ES60601-1 recognition is currently pending for the MGJ2D241709SC, MGJ2Dxx1515SC, MGJ2Dxx1802SC,
MGJ2Dxx1503SC and MGJ2Dxx2003SC variants.
All specifications typical at TA=25°C, nominal input voltage and rated output current unless otherwise specified.
FEATURES
Optimised bipolar output voltages for IGBT/
Mosfet gate drives
Reinforced insulation to UL60950
recognised
ANSI/AAMI ES60601-1, 1 MOPP/2 MOOP’s
recognised3
5.2kVDC isolation test voltage ‘Hi Pot Test’
Ultra low coupling capacitance
SIP package style
5V, 12V, 15V & 24V inputs
+15V/-3V, +15V/-5V, +15V/-8.7V,
+15V/-15V, +17V/-9V, +18V/-2.5V,
+20V/-3.5V & +20V/-5V outputs
Operation to 100°C
Characterised CMTI >200kV/ȝS
Continuous barrier withstand voltage
2.4kVDC
Characterised partial discharge performance
PRODUCT OVERVIEW
The MGJ2 series of DC-DC converters is ideal
for powering ‘high side’ and ‘low side’ gate drive
circuits for IGBTs and Mosfets in bridge circuits.
A choice of asymmetric output voltages allows
optimum drive levels for best system efficiency
and EMI. The MGJ2 series is characterised for high
isolation and dv/dt requirements commonly seen in
bridge circuits used in motor drives and inverters,
while the MGJ2 industrial grade temperature
rating and construction gives long service life and
reliability.
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 2 of 12
www.murata.com
TEMPERATURE CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Specification All output types (see safety approval section for limitations) -40 100
°C
Storage -55 125
Case Temperature above ambient 5V input types 24
All other input types 20
Cooling Free air convection
ABSOLUTE MAXIMUM RATINGS
Short-circuit protection Continuous
Lead temperature 1mm from case for 10 seconds 260°C
Input voltage VIN, MGJ2D05xxxxSC 5.5V
Input voltage VIN, MGJ2D12xxxxSC 13.2V
Input voltage VIN, MGJ2D15xxxxSC 16.5V
Input voltage VIN, MGJ2D24xxxxSC 26.4V
Wave Solder Wave Solder profile not to exceed the profile recommended in IEC 61760-1
Section 6.1.3. Please refer to application notes for further information.
1. ANSI/AAMI ES60601-1 recognition is currently pending for the MGJ2D241709SC, MGJ2Dxx1515SC, MGJ2Dxx1802SC, MGJ2Dxx1503SC and MGJ2Dxx2003SC variants.
GENERAL CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Switching frequency All other types 45 kHz
MGJ2Dxx1802SC & MGJ2D241503SC types 50
ISOLATION CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Isolation test voltage Production tested for 1 second 5200 VDC
Qualification tested for 1 minute 5200
Resistance Viso= 500VDC 1G
Continuous barrier withstand voltage Non-safety barrier application 2400 VDC
Safety standard
UL60950-1
MGJ2Dxx1515SC types Basic/supplementary 200
Vrms
All others Reinforced 150
Basic/supplementary 300
ANSI/AAMI
ES60601-1
MGJ2Dxx1515SC types 1 MOOP 200
All others11 MOOP 300
2 MOOP/1 MOPP 200
OUTPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Rated Power TA=-40ºC to 100ºC 2W
Voltage Set Point Accuracy See tolerance envelopes
Line regulation High VIN to low VIN 1.0 1.2 %/%
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 3 of 12
www.murata.com
TECHNICAL NOTES
ISOLATION VOLTAGE
‘Hi Pot Test’, ‘Flash Tested’, ‘Withstand Voltage’, ‘Proof Voltage’, ‘Dielectric Withstand Voltage’ & ‘Isolation Test Voltage’ are all terms that relate to the same thing, a test
voltage, applied for a specified time, across a component designed to provide electrical isolation, to verify the integrity of that isolation.
Murata Power Solutions MGJ2 series of DC-DC converters are all 100% production tested at 5.2kVDC for 1 second and have been qualification tested at 5.2kVDC for 1
minute.
The MGJ2 series is recognised by Underwriters Laboratory, please see safety approval section for more information. When the insulation in the MGJ2 series is not used
as a safety barrier, i.e. provides functional isolation only, continuous or switched voltages across the barrier up to 2.4kV are sustainable. This is established by measuring
the partial discharge Inception voltage in accordance with IEC 60270. Please contact Murata for further information.
REPEATED HIGH-VOLTAGE ISOLATION TESTING
It is well known that repeated high-voltage isolation testing of a barrier component can actually degrade isolation capability, to a lesser or greater degree depending on
materials, construction and environment. We therefore strongly advise against repeated high voltage isolation testing, but if it is absolutely required, that the voltage be
reduced by 20% from specified test voltage.
SAFETY APPROVAL
MGJ2Dxx1515SC
ANSI/AAMI ES60601-1
The MGJ2Dxx1515SC variants are pending recognition by Underwriters Laboratory (UL) to ANSI/AAMI ES60601-1 and provides 1 MOOP (Means Of Operator Protection) based upon
a working voltage of 200 Vrms max and 280 Vpk max., between Primary and Secondary and between Primary and its Enclosure, in a maximum ambient temperature of 85°C and/
or case temperature limit of 130°C (case temperature measured on the face opposite the pins).
File Number E202895 applies.
UL60950
The MGJ2Dxx1515SC variants have been recognised by Underwriters Laboratory (UL) to UL60950 for basic/supplementary insulation to a working voltage of 200Vrms in a
maximum ambient temperature of 85°C and/or case temperature limit of 130°C (case temperature measured on the face opposite the pins).
File number E151252 applies.
Creepage and clearance 2mm
Working altitude 4000m
Fusing
The MGJ2 Series of converters are not internally fused so to meet the requirements of UL an anti-surge input line fuse should always be used with ratings as defined below.
MGJ2D051515SC: 2A
MGJ2D121515SC: 750mA
MGJ2D151515SC: 750mA
All fuses should be UL recognised and rated to 125V.
All other variants
ANSI/AAMI ES60601-1
The MGJ2 series has been recognised by Underwriters Laboratory (UL) to ANSI/AAMI ES60601-1 and provides 1 MOOP (Means Of Operator Protection) based on a working voltage
of 300Vrms or 2 MOOP based upon a working voltage of 200 Vrms, and 1 MOPP (Mean Of Patient Protection) based on a working voltage of 200Vrms., between Primary and
Secondary. The MGJ2D241709SC, MGJ2Dxx1802SC, MGJ2Dxx1503SC and MGJ2Dxx2003SC variants are currently pending recognition.
File number E202895 applies.
UL60950
The MGJ2 series is recognised by Underwriters Laboratory (UL) to UL60950 for reinforced insulation to a working voltage of 150Vrms and for basic/supplementary insulation to a
working voltage of 300Vrms.
File number E151252 applies.
Fusing
The MGJ2 Series of converters are not internally fused so to meet the requirements of UL an anti-surge input line fuse should always be used with ratings as defined below.
MGJ2D05xxxxSC: 1.25A
MGJ2D12xxxxSC: 750mA
MGJ2D15xxxxSC: 750mA
MGJ2D24xxxxSC: 750mA
All fuses should be UL recognised and rated to 125V.
Over voltage category OVC I OVC II
Working voltage 150Vrms 300Vrms
Working altitude 2000m 2000m
Creepage & clearance 2mm 2mm
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 4 of 12
www.murata.com
PART NUMBER STRUCTURE
MGJ 2 D XX XXXX S C
Series name
Power rating
Output type
S - Single
D - Dual
T - Triple
Q - Quad
RoHS compliant
Package type
S - SIP
D - DIP
M - Surface mount
Z - ZIP
Output voltage
Input voltage
ENVIRONMENTAL VALIDATION TESTING
The following tests have been conducted on this product series, as part of our design verification process. The datasheet characteristics specify user operating conditions for this
series, please contact Murata if further information about the tests is required.
Test Standard Condition
Temperature cycling MIl-STD 883 1010, Condition B 10 cycles between two chambers set to achieve -55°C and +125°C.The dwell time shall not be
less than 10min.
Humidity bias JEDEC JESD22-A101 85°C ± 2°C, 85% ± 5% R.H. for >1000 hours.
High temperature storage life JEDEC JESD22-A103, Condition A 125°C +10/-0°C for ≥1000 hours.
Vibration MIL STD 883 Method 2007, Condition A 1.5mm pk-pk / 20g pk min, 20-2000Hz, 4 sweeps in each of 3 mutually perpendicular axes at
3 oct/min.
Shock MIL STD 883 method 2002, Condition A 500g 1.0ms half sine, 5 shocks in each direction of 3 mutually perpendicular axes.
ESD JEDEC JESD22-A114 HBM Testing Standard at 3 stress levels; 2.0kV, 4.0kV and 8.0kV.
Bump IEC Class 4M5 of ETS 300 019-2-4 Shock Spectrum Type II, 6mS duration, 250m/s2 500 bumps in 6 directions.
Solderability IPC/ECA J-STD-002, Test A and A1
SnPb (Test A): For lead free solderability the parts are conditioned in a steam ager for 8 hours
±15 min. at a temperature of 93±3°C. Dipped in solder at 255°C ±5°C for 5 +0/-0.5 seconds.
Pb-free (Test A1): For leaded solderability the parts are conditioned in a steam ager for 8 hours
±15 min. at a temperature of 93±3°C. Dipped in solder at 245°C ±5°C for 5 +0/-0.5 seconds
Solder heat JEDEC JESD22-B106 The test sample is subjected to a molten solder bath at 260 ±5°C for 10 seconds (96SC tin/
silver/copper).
Solder heat (hand) MIL-STD 202 Method 210, Condition A The soldering iron is heated to 350°C ± 10°C and applied to the terminations for a duration of 4
to 5 seconds.
Solvent cleaning Resistance to cleaning agents. Solvent – Novec 71IPA & Topklean EL-20A. Pulsed ultrasonic immersion 45°C- 65°C
Solvent Resistance MIL-STD 883 Method 2015 Separate samples subjected to solvent A, solvent B and solvent D
Lead Integrity (Adhesion) MIL-STD 883 Method 2025 Leads are bent through 90º until a fracture occurs.
Lead Integrity (Fatigue) MIL-STD 883 Method 2004, condition B2The leads are bent to an angle of 15º. Each lead is subjected to 3 cycles.
Lead Integrity (Tension/Pull) MIL-STD 883 Method 2004, Condition A1Pull of 0.227kg applied for 30 seconds. The force is then increased until the pins snap.
RoHS COMPLIANCE INFORMATION
This series is compatible with RoHS soldering systems with a peak wave solder temperature of 260ºC for 10 seconds. Please refer to application
notes for further information. The pin termination finish on this product series is Tin Plate, Hot Dipped over Matte Tin with Nickel Preplate. The
series is backward compatible with Sn/Pb soldering systems. For further information, please visit www.murata-ps.com/rohs
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 5 of 12
www.murata.com
CHARACTERISATION TEST METHODS
Ripple & Noise Characterisation Method
Ripple and noise measurements are performed with the following test configuration.
C1 1µF X7R m ultilayer ceramic capacitor, voltage rating to be a minimum of 3 times the output voltage of the DC-DC converter
C2 10µF tantalum capacitor, voltage rating to be a minimum of 1.5 times the output voltage of the DC-DC converter with an ESR of less
than 100m at 100 kHz
C3 100nF multilayer ceramic capacitor, general purpose
R1 450 resistor, carbon film, ±1% tolerance
R2 50 BNC termination
T1 3T of the coax cable through a ferrite toroid
RLOAD Resistive load to the maximum power rating of the DC-DC converter. Connections should be made via twisted wires
Measured values are multiplied by 10 to obtain the specified values.
Differential Mode Noise Test Schematic
OSCILLOSCOPE
Y INPUT
SUPPLY
C1 C2 C3 R1 T1 R2
Input Output
DC/DC Converter
R LOAD
+
+
-
-
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 6 of 12
www.murata.com
APPLICATION NOTES
Minimum load
The minimum load to meet datasheet specification is 10% of the full rated load across the specified input voltage range. Lower than 10% minimum loading will result in
an increase in output voltage, which may rise to typically 1.25 times the specified output voltage if the output load falls to less than 5%.
Gate Drive Applications Advisory Note
For general guidance for product usage in gate drive applications please refer to “gate drive application notes”.
Capacitive loading and start up
Typical start up times for this series, with a typical input voltage rise time of 2.2µs and output capacitance of 10µF, are shown in the table below. The product series
will start into capacitance ranging from 47µF up to 220µF with increased start times.
Start-up time
ms
MGJ2D051505SC 3
MGJ2D051509SC 4.5
MGJ2D051515SC 21
MGJ2D051802SC 4
MGJ2D052003SC 5
MGJ2D052005SC 5
MGJ2D121503SC 3
MGJ2D121505SC 3
MGJ2D121509SC 4
MGJ2D121515SC 14.5
MGJ2D121802SC 5
MGJ2D122003SC 5
MGJ2D122005SC 5.5
Typical Start-Up Wave Form
Start-up time
ms
MGJ2D151505SC 2.5
MGJ2D151509SC 3
MGJ2D151515SC 10.5
MGJ2D151802SC 3
MGJ2D152003SC 5
MGJ2D152005SC 4.5
MGJ2D241503SC 3
MGJ2D241505SC 3
MGJ2D241509SC 3
MGJ2D241709SC 4
MGJ2D241802SC 3
MGJ2D242003SC 4
MGJ2D242005SC 4
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 7 of 12
www.murata.com
EFFICIENCY VS LOAD
5V INPUT 12V INPUT
15V INPUT 24V INPUT
0
10
20
30
40
50
60
70
80
90
0 102030405060708090100
Efficiency (%)
Load (%)
MGJ2D121503SC
MGJ2D121505SC
MGJ2D121509SC
MGJ2D121515SC
MGJ2D121802SC
MGJ2D122003SC
MGJ2D122005SC
0
10
20
30
40
50
60
70
80
90
0 102030405060708090100
Efficiency (%)
Load (%)
MGJ2D051505SC
MGJ2D051509SC
MGJ2D051515SC
MGJ2D051802SC
MGJ2D052003SC
MGJ2D052005SC
0
10
20
30
40
50
60
70
80
90
0 102030405060708090100
Efficiency (%)
Load (%)
MGJ2D151505SC
MGJ2D151509SC
MGJ2D152003SC
MGJ2D152005SC
MGJ2D151515SC
MGJ2D152005SC
0
10
20
30
40
50
60
70
80
90
0 102030405060708090100
Efficiency (%)
Load (%)
MGJ2D241503SC
MGJ2D241505SC
MGJ2D241509SC
MGJ2D241709SC
MGJ2D241802SC
MGJ2D242003SC
MGJ2D242005SC
TEMPERATURE DERATING GRAPHS
Full Output
Current Rating
95
400
-40
Ambient Temperature (ºC)
Safe
Operating Area
100
400
-40
Ambient Temperature (ºC)
Safe
Operating Area
051505, 052005, 121802, 122003, 151802,
152003, 241802 & 242003 All other variants
85
400
-40
Ambient Temperature (ºC)
Safe
Operating Area
Full Output
Current Rating
Full Output
Current Rating
051515, 051802, 052003, 121503, 121515
& 151515
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 8 of 12
www.murata.com
POSITIVE OUTPUT VOLTAGE TOLERANCE ENVELOPES
The voltage tolerance envelopes show typical load regulation characteristics for this product series. The tolerance envelope is the maximum output voltage variation due to
changes in output loading and set point accuracy.
051505, 051509, 151505 & 151509 122005, 152005& 242005
121509, 241509 & 052005 121505 & 241505
121515 & 151515 051515
Output Load Current (%)
Output Voltage
Output Voltage
100
100
100
75
75
75
50
50
50
25
25
25
10
10
10
Output Load Current (%)
100
100
75
75
50
50
25
25
10
10
Output Voltage
Output Voltage
Output Voltage
Output Load Current (%)
Output Load Current (%)
4%
2% 1%
-4%
3%
2% -1%
-5%
5%
3% 2%
-3%
4%
1% 0%
-7%
6%
3% 1%
-4%
Output Load Current (%)
6%
1% 0%
-7%
100
75
50
25
10
Output Voltage
Output Load Current (%)
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 9 of 12
www.murata.com
POSITIVE OUTPUT VOLTAGE TOLERANCE ENVELOPES CONTINUED
241709 052003
122003, 152003 & 242003 051802
121802, 151802 & 241802 121503
241503
7%
3.5% 3%
-3%
100
75
50
25
10
Output Voltage
Output Load Current (%)
5%
1% 0%
-7%
10075
50
25
10
Output Voltage
Output Load Current (%)
5%
5%
5%
0%
0%
2%
2%
2%
1%
-7%
-6%
-5%
100
100
100
75
75
75
50
50
50
25
25
25
10
10
10
Output Voltage
Output Voltage
Output Voltage
Output Load Current (%)
Output Load Current (%)
Output Load Current (%)
5%
0% 1%
-6%
10075
50
25
10
Output Voltage
Output Load Current (%)
5%
1% 0%
-5%
Output Voltage
Output Load Current (%)
100
75
50
25
10
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 10 of 12
www.murata.com
NEGATIVE OUTPUT VOLTAGE TOLERANCE ENVELOPES
051509, 052005, 121505, 122005, 152005 & 242005 151505
121509 & 241509 051505
151509 & 241505 121515 & 151515
7%
3% 2%
-4%
8%
6% 4%
0%
5%
3% 1%
-4%
4%
1% 1%
-6%
100
100 100
100
75
75 75
75
50
50 50
5025
25 25
25
10
10 10
10
Output Voltage
Output Voltage
Output Voltage Output Voltage
Output Load Current (%)
Output Load Current (%) Output Load Current (%)
Output Load Current (%)
6% 6%
3% 3%
2%
-3% 1%
-4%
100 100
75 75
50 50
25 25
10 10
Output Voltage
Output Voltage
Output Load Current (%) Output Load Current (%)
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 11 of 12
www.murata.com
NEGATIVE OUTPUT VOLTAGE TOLERANCE ENVELOPES CONTINUED
051515 241709
052003 122003, 152003 & 242003
051802 121802, 151802 & 241802
121503 241503
6%
1% 0%
-7%
1007550
25
10
Output Voltage
Output Load Current (%)
6.5%
3% 2%
-4%
100
755025 10
Output Voltage
Output Load Current (%)
9% 9%
3% 3%
3%
-7%
100
75
50
25 10
Output Voltage
Output Load Current (%)
4%
-5%
10075
50
25 10
Output Voltage
Output Load Current (%)
13%
5%
5%
5%
1%
10%
5%
2%
3%
-5%
-8% -4%
100
100 100
75
75 75
50
50 50
25
25 25
10
10 10
Output Voltage
Output Voltage
Output Voltage
Output Load Current (%)
Output Load Current (%) Output Load Current (%)
13%
5% 6%
-3%
100
7550
25
10
Output Voltage
Output Load Current (%)
MGJ2 Series
5.2kVDC Isolated 2W Gate Drive DC-DC Converters
KDC_MGJ2_K01 Page 12 of 12
www.murata.com
Murata Power Solutions (Milton Keynes) Ltd. makes no representation that the use of its products in the circuits described herein, or the use
of other technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do
not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change
without notice. © 2020 Murata Power Solutions (Milton Keynes) Ltd.
This product is subject to the following operating requirements
and the Life and Safety Critical Application Sales Policy:
Refer to: https://www.murata.com/en-eu/products/power/requirements
PACKAGE SPECIFICATIONS
MECHANICAL DIMENSIONS PIN CONNECTIONS
Tube outline dimensions
RECOMMENDED FOOTPRINT DETAILS
Weight: 4.3g
Unless otherwise stated all dimensions in mm (inches).
Tube length : 525mm [20.669} ±2.0 [0.079] Tube Quantity : 25
All dimensions in mm ±0.25mm (inches ±0.01). All pins on a 2.54 (0.1) pitch and within
±0.25 (0.01) of true position.
Pin Output
Pin Function
1+VIN
2-VIN
5-VOUT
6OV
7+V
OUT