Primary-switched STEP POWER power supply for DIN rail mounting, input: 1-phase, output: 15 V DC/4 A
Product Description
STEP POWER power supplies for distribution boards
The STEP POWER power supply range was developed especially for building automation. The low idling losses and high degree of efficiency ensure
maximum energy efficiency. They allow flexible use and can be snapped onto the DIN rail or screwed onto an even surface.
Your advantages
Flexible mounting by simply snapping onto the DIN rail or screwing onto a level surface
Reliable power supply thanks to high MTBF (mean time between failures) of more than 500,000 hours and U/I characteristic curve
Energy savings thanks to maximum energy efficiency and incredibly low idling losses
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4046356308540
Weight per Piece (excluding packing) 300.000 g
Custom tariff number 85044030
Country of origin Poland
Technical data
Dimensions
Width 72 mm
Height 90 mm
Depth 61 mm
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page2/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Technical data
Dimensions
55 mm (Device depth (DIN rail mounting))
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 30 mm / 30 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Input data
Nominal input voltage range 100 VAC ... 240 VAC
Input voltage range 85 VAC ... 264 VAC
95 VDC ... 250 VDC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Current consumption 0.8 A (120VAC)
0.5 A (230 V AC)
Nominal power consumption 118.1 VA
Inrush current < 15 A (typical)
Mains buffering time typ. 27 ms (120VAC)
typ. 120 ms (230 V AC)
Input fuse 3.15 A (slow-blow, internal)
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.58
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 15 VDC ±1%
Setting range of the output voltage (USet)10 VDC ... 16.5 VDC (> 15 VDC, constant capacity restricted)
Nominal output current (IN)4 A (-25°C...55°C)
4.4 A (-25°C...40°C permanent )
Output current Imax 9 A
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page3/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Technical data
Output data
Feedback voltage resistance ≤ 25 VDC
Protection against overvoltage at the output (OVP) < 25 VDC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 55 mVPP (20MHz)
Output power 60 W
Typical response time < 0.5 s
Peak switching voltages nominal load < 10 mVPP (20MHz)
Maximum power dissipation in no-load condition < 0.5 W
Power loss nominal load max. 8.6 W
General
Net weight 0.27 kg
Operating voltage display Green LED
Efficiency > 87 % (for 230 V AC and nominal values)
> 1134000 h (40°C)
Insulation voltage input/output 4 kV AC (type test)
3.75 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 VDC (routine test)
Degree of protection IP20
Protection class II (in closed control cabinet)
Housing material Polycarbonate
Foot latch material POM (Polyoxymethylen)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: 0mm horizontally, 30mm vertically
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 6.5 mm
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page4/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Technical data
Connection data, input
Screw thread M3
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 6.5 mm
Screw thread M3
Standards
EMC requirements for noise immunity EN61000-6-1
EN61000-6-2
EMC requirements for noise emission EN61000-6-3
EN61000-6-4
Standard - Safety of transformers EN61558-2-16
Standard - Electrical safety IEC60950-1/VDE0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN50178/VDE0160 (PELV)
Standard – Safety extra-low voltage IEC60950-1 (SELV) and EN60204-1 (PELV)
Standard - Safe isolation DINVDE0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment EN50178
Standard – Limitation of mains harmonic currents EN61000-3-2
Rail applications EN50121-4
Conformance/approvals
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T3C
(Hazardous Location)
CSA CSA-C22.2 No.107.1-01
Shipbuilding approval DNVGL(EMCB)ABS, NK
EMC data
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page5/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Technical data
EMC data
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Electromagnetic HF field EN61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst) EN61000-4-4
Input 4 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Comments Criterion B
Surge voltage load (surge) EN61000-4-5
Input 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
0.5 kV (Test Level 1 - asymmetrical)
Comments Criterion B
Conducted interference EN61000-4-6
Frequency range 10 kHz ... 15 kHz
0.15 MHz ... 80 MHz
Voltage 3 V (Test Level 2)
10 V (Test Level 3)
Comments Criterion A
Criterion A
Voltage dips EN61000-4-11
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page6/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Block diagram
N(-)
L (+)
+
+
Schematic diagram
OutputDC
12V 5A
STEP-PS/1AC/12DC/5
Order-No.:2868583
100-240V
85-264V~
-25...+70°C
Industrial
Information
ReadmanualNo.
9038813before
connectingtomains
www.interface.phoenixcontact.com
Control
Technology
Equipment
Equipment
43KA
(>+55°C/>+131°F
Derating:2,5%/k)
-15...+158°F
95-250V
12V
5A
50-60Hz
1.4-0.65A
INPUT
OUTPUT
TEMPERATURE
APPROVALS
AC:
DC:
OperationalVoltage:
LISTED
UL
-26
Classifications
eCl@ss
eCl@ss 10.0.1 27040701
eCl@ss 11.0 27040701
eCl@ss 4.0 27040700
eCl@ss 4.1 27040700
eCl@ss 5.0 27242200
eCl@ss 5.1 27242200
eCl@ss 6.0 27049000
eCl@ss 7.0 27049002
eCl@ss 9.0 27040701
ETIM
ETIM 2.0 EC001039
ETIM 3.0 EC001039
ETIM 4.0 EC002540
ETIM 6.0 EC002540
ETIM 7.0 EC002540
UNSPSC
UNSPSC 6.01 30211502
UNSPSC 7.0901 39121004
UNSPSC 11 39121004
UNSPSC 12.01 39121004
UNSPSC 13.2 39121004
UNSPSC 18.0 39121004
UNSPSC 19.0 39121004
UNSPSC 20.0 39121004
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page7/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Classifications
UNSPSC
UNSPSC 21.0 39121004
Approvals
Approvals
Approvals
DNV GL / NK / ABS / UL Listed / UL Recognized / cUL Recognized / IECEE CB Scheme / cUL Listed / EAC / EAC / cULus Recognized / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
DNV GL https://approvalfinder.dnvgl.com/ TAA00001YD
NK http://www.classnk.or.jp/hp/en/ 09A024
ABS http://www.eagle.org/eagleExternalPortalWEB/ 18-HG1797199_PDA
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 214596
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 214596
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page8/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Approvals
IECEE CB Scheme http://www.iecee.org/ DK-14416-M1
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
EAC EAC-Zulassung
EAC RU*DE*08.B.01873/19
cULus Recognized
cULus Listed
Accessories
Accessories
Device protection
Type 3 surge protection device-PLT-SEC-T3-230-FM-UT-2907919
Type2/3 surge protection, consisting of protective plug and base element with screw connection. For single-phase power
supply network with integrated status indicator and remote signaling. Nominal voltage: 230VAC/DC
https://www.phoenixcontact.com/us/products/2868619
04/20/2021Page9/9
Power supply unit-STEP-PS/ 1AC/15DC/4-2868619
Accessories
Type 3 surge protection device-PLT-SEC-T3-24-FM-UT-2907916
Type3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage: 24VAC/DC
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com