POWR-GARD(R) Ground-Fault Protection PGR-5701 SERIES Ground-Fault Relay ted or rimary Relay uration Inject conds. PGR-5701 MANUAL GROUND-FAULT RELAY JUNE 8, 2009 REVISION 6 POWR-GARD PGR-5701 SERIES ULT RELAY GROUND-FA 4 3 2 1 5 TRIP INHB PWR 6 7 8 9 4 3 2 1 5 6 7 8 9 0 0 Y % CT PRIMAR .50 1.0 .40 1.5 .30 2.0 .20 .10 .05 2.5 TIME (s) RESET TEST Copyright (c) 2009 by Littelfuse, Inc. All rights reserved. Publication: PGR-5701-SM Document: P95-C701-000SM Printed in Canada. Rev. 6 Page i PGR-5701 Ground-Fault Relay TABLE OF CONTENTS Page Table of Contents ........................................................................................................i List of Figures ..............................................................................................................i List of Tables ...............................................................................................................i 1. 1.1 1.2 2. 2.1 2.2 2.3 2.4 2.5 3. 4. 5. 6. INTRODUCTION............................................................................................1 General ...........................................................................................................1 Current-Transformer Selection.......................................................................1 OPERATION ..................................................................................................2 Configuration-Switch Settings ........................................................................2 2.1.1 Relay Operating Mode ........................................................................2 2.1.2 Trip Inhibit............................................................................................2 2.1.3 CT Verification.....................................................................................2 2.1.4 Filter Selection.....................................................................................2 2.1.5 Reset Mode .........................................................................................2 Front-Panel Controls ......................................................................................2 2.2.1 Ground-Fault Trip Level ......................................................................2 2.2.2 Ground-Fault Trip Time.......................................................................4 2.2.3 Reset ...................................................................................................4 2.2.4 Test......................................................................................................4 Front-Panel Indication.....................................................................................4 2.3.1 Power...................................................................................................4 2.3.2 Trip.......................................................................................................4 2.3.3 Trip Inhibit............................................................................................4 Analog Output.................................................................................................5 Self Diagnostics ..............................................................................................5 INSTALLATION .............................................................................................5 TECHNICAL SPECIFICATIONS................................................................ 10 ORDERING INFORMATION...................................................................... 13 GROUND-FAULT PERFORMANCE TEST............................................... 13 LIST OF FIGURES 1. 2. 3. 4. 5. 6. 7. Page PGR-5701 Outline and Mounting Details.......................................................3 Typical Connection Diagram ..........................................................................5 PGC-3026 Earth-Fault Current Transformer .................................................6 PGC-3082 Earth-Fault Current Transformer .................................................7 PGC-3140 Earth-Fault Current Transformer .................................................8 PGK-0055 and PGK-0060 Panel-Mount Adapters........................................9 Ground-Fault-Test Circuit............................................................................ 14 LIST OF TABLES 1. 2. Page Trip-Features Comparison .............................................................................6 Ground-Fault-Test Record .......................................................................... 14 Rev. 6 Page 1 PGR-5701 Ground-Fault Relay DISCLAIMER Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. 1. INTRODUCTION 1.1 General The PGR-5701 is a microprocessor-based ground-fault relay for resistancegrounded and solidly grounded systems. It is uniquely suited for use on systems with significant harmonic content. Its output relay can operate in the fail-safe or non-failsafe mode for undervoltage or shunt-trip applications. The PGR-5701 has one output relay with isolated normally open and normally closed contacts for use in independent control circuits. Additional features include LED trip, power, and inhibit indication, autoreset or latching trips with front-panel and remote reset, trip memory, test switch, self diagnostics, 0- to 5-V analog output, inputs for standard and sensitive ground-fault current transformers, CT verification for sensitive current transformers, digital selector switches, switch-selectable algorithms for fixed-frequency or variable-frequency applications, and an inhibit that can be enabled to prevent the output relay from operating during a high-current ground fault. Ground-fault current is sensed by a core-balance zero-sequence current transformer (CT). The trip level of the ground-fault circuit is switch selectable in 1% increments from 1 to 99% of the CT-primary rating. 1.2 Current-Transformer Selection A PGR-5701 has inputs for 1-, 5-A, and sensitive 50-mA-secondary CT's. Choose a CT that provides the required ground-fault-trip range. For ground-fault detection, the ground-fault trip level must be substantially below the prospective ground-fault current. In a solidly grounded system, prospective groundfault current is similar to phase-fault current. In a resistance-grounded system, prospective ground-fault current is defined by the neutral-grounding-resistor letthrough-current rating. In a solidly grounded system, protection against arcing ground faults requires a ground-fault CT that will detect low-level fault current but not saturate up to the operating value of the system overcurrent protection. In general, immunity to saturation is proportional to CT mass. To eliminate nuisance tripping, surge current must not saturate the CT. For low-level ground-fault protection use a PGC-3026 PGC-3082, or PGC-3140, sensitive earth-fault CT with a 5-A-primary rating. However, protection at this level might not be possible because of high surge current or prospective ground-fault current. Rev. 6 Page 2 PGR-5701 Ground-Fault Relay 2. OPERATION 2.1 Configuration-Switch Settings See Fig. 1. 2.1.1 Relay Operating Mode Switch 1 is used to set the operating mode of the output relay. In the fail-safe mode, the output relay energizes when the ground-fault circuit is not tripped. In the fail-safe mode, non-volatile memory retains the trip status of the PGR-5701. If tripped, and the supply voltage is cycled, the PGR-5701 will remain tripped, with the trip relay deenergized and the TRIP LED on, until reset. In the non-fail-safe mode, the output relay energizes when a ground-fault trip occurs. In the non-fail-safe mode, trip status is not retained in non-volatile memory. 2.1.2 Trip Inhibit Switch 2 is used to select Class I or Class II operation. In the OFF position, highcurrent trip inhibit is off for Class I operation. In the ON position, high-current inhibit is on for Class II operation. If high-current trip inhibit is on and ground-fault current escalates above eleven times the CT-primary rating before the ground-fault circuit trips, the output relay will not operate until ground-fault current falls below eight times the CTprimary rating. This feature allows overcurrent protection to operate in applications where the ground-fault current can be larger than the interrupting capacity of the device tripped by the PGR-5701. 2.1.3 CT Verification Switch 3 is used to enable CT verification with a PGC-3000-series CT. In the ON position, a trip will occur if the CT is disconnected. Switch 3 must be in the OFF position when a PGC-3000-series CT is not used. 2.1.4 Filter Selection Switch 4 is used to select the filtering algorithm for a fixed-frequency (50/60 Hz) or variable-frequency application. The FIXED FREQUENCY setting uses a DFT filter that allows lower trip levels to be used by rejecting harmonics that can cause nuisance tripping. The VARIABLE FREQUENCY setting uses a peak-detection algorithm with a wider band width for fault detection in variable-frequency drive applications. 2.1.5 Reset Mode Switch 5 is used to select autoreset or latching trips. See Section 2.2.3. 2.2 Front-Panel Controls 2.2.1 Ground-Fault Trip Level The % CT PRIMARY selector switches are used to set the ground-fault trip level as a percentage of the CT-primary rating. In tripping systems, a ground-fault trip level of 10 to 20% of the prospective groundfault current is often used. In alarm-only systems, a value of 50% of the prospective Rev. 6 Page 3 PGR-5701 Ground-Fault Relay 55.0 (2.17) 37.5 (1.48) 8.7 (0.34) CONFIGURATION SWITCHES 5 AUTORESET FIXED FREQUENCY CT VERIFICATION OFF 4 VARIABLE FREQUENCY 3 ON TRIP INHIBIT OFF 2 ON RELAY OPERATING MODE FAIL-SAFE 1 NON-FAIL-SAFE NOTE 2 61.2 (2.41) 75.0 (2.95) LATCHING RESET MODE FILTER SELECTION NOTE 5 1A 5A C 1A/5A CT 1 2 EFCT 3 4 RESET ANALOG OUTPUT 5 6 7 MOUNTING DETAIL 8 118.0 (NOTE 3) (4.65) 110.0 (4.33) TOP 55.0 (2.17) 6.9 (0.27) S1 S2 RS 6.3 (0.25) POWR-GARD GROUND-FAULT RELAY 5 INHB 6 7 8 9 4 3 2 1 5 0 0 % CT PRIMARY TRIP 6 7 8 9 .40 .30 .20 .10 TEST .50 1.0 1.5 2.0 2.5 .05 TIME (s) 75.0 (2.95) PWR 4 3 2 1 PGR-5701 SERIES RESET SIDE FRONT NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 9 10 11 12 13 14 15 16 L2 L1 N 2. MOUNTING SCREWS: M4 OR 8-32. 3. OVERALL DIMENSION WHEN MOUNTED ON DIN EN50022 35 mm x 7.5 mm TOP-HAT RAIL. 4. ADJUSTMENT KNOBS ARE REMOVABLE. 5. BOTTOM CONFIGURATION SWITCHES SHOWN IN DEFAULT POSITION. FIGURE 1. PGR-5701 Outline and Mounting Details. Rev. 6 Page 4 PGR-5701 Ground-Fault Relay ground-fault current is often used. To avoid sympathetic tripping, the trip level must be above the charging current of the protected feeder. A 0% selection provides protection at 1%. 2.2.2 Ground-Fault Trip Time The PGR-5701 has a definite-time trip characteristic. The TIME (s) selector switch is used to set the ground-fault trip delay time for coordination with upstream and downstream ground-fault devices. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault. 2.2.3 Reset If the Reset Mode switch is in the LATCHING position, a trip remains latched until the RESET switch is pressed or the remote-reset terminals are momentarily connected. In the non-fail-safe mode, cycling the supply voltage will also reset the PGR-5701. If the Reset Mode switch is in the AUTORESET position, a trip will reset when the fault is removed. The reset circuit responds only to a momentary closure so that a jammed or shorted switch will not prevent a trip. The front-panel RESET switch is inoperative when the remote-reset terminals (6 and 7) are connected. 2.2.4 Test The TEST switch is used to test the ground-fault circuit, the indication, and the output relay. When the TEST switch is pressed for one second, a test signal is applied to the ground-fault-detection circuit, the circuit will trip, the TRIP LED will light, and the output relay will operate. If high-current inhibit has been selected, the INHB LED will light. 2.3 Front-Panel Indication 2.3.1 Power The green LED labeled PWR indicates the presence of supply voltage. 2.3.2 Trip The red LED labeled TRIP indicates a trip. A solid red LED indicates a ground-fault trip. A regularly flashing LED indicates a trip initiated by a CT fault. Two fast flashes indicate a diagnostic trip. See Section 2.5. 2.3.3 Trip Inhibit The yellow LED labeled INHB indicates that output-relay operation was inhibited during a high-current ground fault. See Section 2.1.2. When a ground-fault trip occurs during a high-current ground fault, both the TRIP and INHB LED's will be ON. Inhibit indication is reset when the ground-fault trip is reset. Inhibit operation and indication will not respond if the Trip-Inhibit switch is in the OFF position. Rev. 6 Page 5 PGR-5701 Ground-Fault Relay 2.4 Analog Output The non-isolated, 0- to 5-V analog output indicates ground-fault current sensed by the ground-fault CT. The output is 5 V when ground-fault current is 100% of the CTprimary rating. 2.5 Self Diagnostics A diagnostic trip is indicated by two flashes of the TRIP LED. It can be caused by a diagnostic problem detected by the watchdog timer or from an incorrect reading from non-volatile memory. Press RESET or cycle supply voltage. If the problem persists, contact 1-800-TEC-FUSE (1-800-832-3873). 3. INSTALLATION A PGR-5701 can be surface or DIN-rail mounted. See Fig. 1. Panel mounting requires a PGK-0055 or PGK-0060 Panel-Mount Adapter. See Fig. 6. Pass the phase conductors through the CT window as shown in Fig. 2 (for 4-wire and single-phase systems, also pass the neutral conductor through the CT window). Do not pass ground conductors through the CT window. In applications that require shields or drain wires to pass through the CT window, return them through the CT window before connecting them to ground. If a ground-fault CT with a 5-A secondary is used, connect it to terminals 2 and 3 (terminals 1 and 3 with a 1-A secondary) and ground terminal 3. If a PGC-3000-series CT is used, connect it to terminals 4 and 5, connect the shield to terminal 5, and ground terminal 5. Remove the connection to terminal 9 for dielectric-strength testing--all inputs and outputs have ANSI/IEEE C37.90 surge-protection circuits that conduct above 300 Vac. See Figs. 3, 4, and 5 for sensitive PGC-3000-series CT dimensional drawings. XXX:5 L N 1 2 1A 5A 3 C 4 5 S1 S2 13 15 11 14 ISOLATED CONTACTS REMOTE RESET 6 L2 N L1 3 4 C S1 S2 1M 2 1A 5A PGR-5701 RS ANALOG OUTPUT 1 O/L 10 5 PGR-5701 RESET NOTE 1 START OR PGC-3000-XX 1M 16 NOTE: 7 LEAKAGE 8 V STOP XXX:1 9 1. USE OPTIONAL PGA-0500 ANALOG PERCENT CURRENT METER WITH PGA-05CV CURRENT VOLTAGE CONVERTER TO DISPLAY LEAKAGE CURRENT AS A PERCENT OF CT RATING. FIGURE 2. Typical Connection Diagram. Technical Information 11.1 provides additional information on CT selection. ALTERNATE CT CONNECTIONS Rev. 6 Page 6 PGR-5701 Ground-Fault Relay 68.0 68.0 (2.68) (2.68) 17.0 (0.67) P S1 2S2 P1 M4 OR 8-32 TAP 42.6 (1.68) 52.5 (2.07) 26.5 (1.04) 34.0 (1.34) M5 SCREWS 110.0 MAX (0.43) TOP MOUNTING DETAIL 25.0 (0.98) PGC-3026 600 V Class, Insulation Class A 26.5 (1.04) EARTH FAULT CURRENT TRANSFORMER R R C LR 53428 POWR-GARDTM Products US 0 34.0 (1.34) (1 .0 2) RECESSED FOR 7-mm HEX NUT 3.0 (0.12) DEEP 7.0 (0.87) 72.0 (2.83) 4.0 (0.16) 0 . 26 58.0 (2.28) 5.0 (0.20) 5.0 (0.20) 52.5 (2.07) FRONT MOUNTING FOOT INSTALLATION TOOL DETAIL `A' SIDE NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL `A') 3. MOUNTING SCREWS: M4 OR 8-32. FIGURE 3. PGC-3026 Earth-Fault Current Transformer. Rev. 6 Page 7 PGR-5701 Ground-Fault Relay P1 S1 S2 121.0 (4.76) 121.0 (4.76) 20.5 (0.81) 30.0 (1.18) 56.0 (2.21) 46.0 (1.81) 80.0 (3.15) NOTE 2 M5 SCREWS TOP MOUNTING DETAIL 25.0 (0.98) PGC-3082 600 V Class, Insulation Class A 30.0 (1.18) EARTH FAULT CURRENT TRANSFORMER R US POWR-GARDTM Products .0 82 3) .2 (3 69 .8 (2. 75 ) 5.0 (0.20) 0 RECESSED FOR 8-mm HEX NUT 1.0 (0.04) DEEP EFCT-1FC FLUX CONDITIONER (OPTIONAL) 22.0 (0.87) 138.0 MAX (5.43) C LR 53428 126.0 (4.96) R 5.5 (0.22) 110.0 (4.33) 5.5 (0.22) FRONT NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR 8-32. 3. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED. FIGURE 4. PGC-3082 Earth-Fault Current Transformer. 56.0 (2.21) SIDE Rev. 6 Page 8 PGR-5701 Ground-Fault Relay C US R POWR-GARDTM Products LR 53428 R 600 V Class, Insulation Class A PGC-3140 EARTH FAULT CURRENT TRANSFORMER 215.0 (8.46) 26.5 (1.04) 52.3 (2.06) P S1 2S2 P1 31.0 (1.22) 64.0 (2.52) 215.0 (8.46) 162.0 (6.38) M5 OR 10-32 TAP M5 SCREWS TOP MOUNTING DETAIL 31.0 (1.22) 25.0 (0.98) P1 5.0 (0.20) DIA 60.0 (2.36) 139.7 (5.50) FLUX CONDITIONER (INCLUDED) BONDING SCREW 215.0 (8.46) 236 MAX (9.29) S1 8.5 (0.33) 198.0 (7.80) 8.5 (0.33) FRONT NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M5 OR 10-32. FIGURE 5. PGC-3140 Earth-Fault Current Transformer. SIDE 42.5 (1.67) 6.0 (0.24) FIGURE 6. PGK-0055 and PGK-0060 Panel-Mount Adapters. 5 .50 1.0 1.5 2.0 2.5 RESET .05 TIME (s) .40 .30 .20 .10 TRIP 72.0 (2.83) 60.0 (2.36) 85.0 (3.35) FRONT VIEW 6 7 8 9 ALTERNATE CONFIGURATIONS 4.3 (0.17) RAD 8.7 (0.34) DIA 4.0 (0.16) DIA 2.0 (0.08) RAD MAXIMUM TEST 0 0 % CT PRIMARY INHB 4 3 2 1 5 6 7 8 9 PWR PGR-5701 SERIES 6.0 (0.24) BEZEL 110.0 (4.33) SIDE VIEW BRACKET 4. INSTALL BEZEL USING 6-32 x 0.31 SCREWS PROVIDED. 3. CONNECT WIRING TO TERMINALS. 2. INSERT BRACKET THROUGH FRONT OF PANEL CUTOUT AND SECURE WITH FLAT WASHERS AND LOCKNUTS PROVIDED. 1. REMOVE BEZEL AND LATCH MONITOR TO BRACKET. 1. DIMENSIONS IN MILLIMETRES (INCHES). NOTE: 75.0 (2.95) 55 mm (2.2) WIDE MONITOR INSTALLATION INSTRUCTIONS: 6-32 6-32 PANEL THICKNESS 1.6 (0.06) TO 4.8 (0.19) PGK-0055 Panel-Mount Adapter PANEL CUTOUT DETAIL 4 3 2 1 GROUND-FAULT RELAY POWR-GARD 85.0 (3.35) 85.0 (3.35) 9.5 (0.37) 60.0 (2.36) 79.0 (3.11) 6.0 (0.24) 5 RESET .50 1.0 1.5 2.0 2.5 .05 TIME (s) .40 .30 .20 .10 TRIP 72.0 (2.83) 60.0 (2.36) 99.0 (3.90) FRONT VIEW 6 7 8 9 ALTERNATE CONFIGURATIONS 4.3 (0.17) RAD 8.7 (0.34) DIA 4.5 (0.18) DIA 2.0 (0.08) RAD MAXIMUM TEST 0 0 % CT PRIMARY INHB 4 3 2 1 5 6 7 8 9 PWR PGR-5701 SERIES 6.0 (0.24) 116.0 (4.57) SIDE VIEW BRACKET 55 mm (2.2) WIDE MONITOR 2. MEETS NEMA 3, IP53. 1. DIMENSIONS IN MILLIMETRES (INCHES). NOTE: 4. ATTACH COVER USING THUMB SCREWS PROVIDED. 3. CONNECT WIRING TO TERMINALS. 2. INSERT BRACKET THROUGH FRONT OF PANEL CUTOUT AND SECURE WITH FLAT WASHERS AND LOCKNUTS PROVIDED. 1. WITH COVER REMOVED LATCH MONITOR TO BRACKET. INSTALLATION INSTRUCTIONS: TRANSPARENT COVER (NOTE 2) M4 M4 PANEL THICKNESS 1.6 (0.06) TO 4.8 (0.19) PGK-0060 Panel-Mount Adapter PANEL CUTOUT DETAIL 4 3 2 1 GROUND-FAULT RELAY POWR-GARD 99.0 (3.90) 88.0 (3.46) 44.0 (1.73) ibited ccurs nhibit cation 42.5 (1.67) 30.0 (1.18) d-fault ashes 9.5 (0.37) d the pplied d the D will 9.5 (0.37) orted n the 9.5 (0.37) n the 44.0 (1.73) 30.0 (1.18) d until ntarily et the 60.0 (2.36) 79.0 (3.11) ust be 75.0 (2.95) switch m and or all ream. e first Rev. 6 Page 9 PGR-5701 Ground-Fault Relay Rev. 6 Page 10 PGR-5701 Ground-Fault Relay 4. TECHNICAL SPECIFICATIONS Supply: 0U Option ........................... 2.5 VA, 120 to 240 Vac (+20, -55%), 50/60 Hz, 2.0 W, 100 to 240 Vdc (+20, -25%) 0D Option ........................... 2.0 W, 12 to 30 Vdc (+20, -25%) 0T Option............................ 2.0 W, 40 to 55 Vdc (+20, -25%) Trip-Level Range ....................... 1 to 99% CT-Primary Rating in 1% increments (50 mA to 4.95 A with PGC-3000-series CT's) Trip-Time Settings ..................... 0.05, 0.10, 0.20, 0.30, 0.40, 0.50, 1.0, 1.5, 2.0, and 2.5 s Accuracies (1): (2) Trip Level ........................ Largest of 5% of Setting or: 1-A input: 1% setting ............ -10, +15 mA 2 - 99% setting .... 10 mA 5-A and EFCT (4) inputs: 1% setting ............ -35, +60 mA 2 - 99% setting .... 35 mA Trip Time (3) ........................ 5% of Setting (-25, +20 ms minimum) Trip Inhibit: Off ...................................... Class I On ...................................... Class II Level .............................. 11 x CT-Primary Rating Input: Algorithms .......................... DFT or Peak DFT 3 dB Frequency Response ....................... 32 to 86 Hz Peak 3 dB Frequency Response ....................... 20 to 420 Hz CT ...................................... 1- or 5-A Secondary Rating, or PGC-3000 series CT Detection .................. Open-Circuit Detection with PGC-3000 series Thermal Withstand: Continuous ..................... 5 x CT-Secondary Rating 1-Second........................ 80 x CT-Secondary Rating Burden: 5-A input......................... < 0.01 1-A input......................... < 0.05 EFCT input ..................... 2 Rev. 6 Page 11 PGR-5701 Ground-Fault Relay Analog Output: Range ............................... 0 to 5 Vdc, 5 V = 100% CT Rating Output Impedance ............ 220 Reset ....................................... Front-Panel Switch and Remote N.O. Momentary Contact Functional Test ........................ Front-Panel Switch Relay Contacts: Configuration ...................... Isolated N.O. and N.C. Operating Mode.................. Fail-Safe or Non-Fail-Safe CSA/UL Contact Rating...... 8 A resistive 250 Vac, 8 A resistive 30 Vdc Supplemental Contact Ratings: Make/Carry 0.2 s .......... 20 A Break: dc............................... 30 W resistive, 15 W inductive (L/R = 0.04) ac............................... 2,000 VA resistive, 1,400 VA inductive (PF = 0.4) Subject to maximums of 8 A and 250 V (ac or dc). Operating Mode ....................... Latching or Autoreset Terminals ................................. Wire-clamping, 24 to 12 AWG (0.2 to 2.5 mm2) conductors Dimensions: Height ............................... 75 mm (3.0") Width................................. 55 mm (2.2") Depth ................................ 115 mm (4.5") Shipping Weight ....................... 0.45 kg (1 lb.) Environment: Operating Temperature..... -40 to 60C Storage Temperature........ -55 to 80C Humidity............................ 85% Non-Condensing Surge Withstand ...................... ANSI/IEEE 37.90.1-1989 (Oscillatory and Fast Transient) EMC Tests: Verification tested in accordance with EN 50263:2000 Electrostatic Discharge ....... IEC 61000-4-2, EN 61000-4-2, 6 kV Contact Discharge, 8 kV Air Discharge Rev. 6 Page 12 PGR-5701 Ground-Fault Relay Radiated RF ...................... IEC 61000-4-3, EN 61000-4-3 10 V/m, 80-1000 MHz, 80% AM (1 kHz) 10 V/m, 900 MHz, 200 Hz Pulse Modulated Fast Transient ................... IEC 61000-4-4, EN 61000-4-4 2 kV Common Mode, 1 kV Differential Mode Surge Immunity ................. IEC 61000-4-5, EN 61000-4-5 2.0 kV Common Mode, 1.0 kV Differential Mode Conducted RF ................... IEC 61000-4-6, EN 61000-4-6 10Vrms, 0.15-80 MHz, 80% AM (1 kHz) Magnetic Field ................... IEC 61000-4-8, EN 61000-4-8 50 Hz, 30 A/m (continuous) 50 Hz, 300 A/m (1 to 3 seconds) Voltage Interruption ........... IEC 255-22-11, EN 60255-11 100% for 2, 5, 10, 20, 50, 100 & 200 ms MHz Burst.......................... IEC.255-22-1, EN 60255-22-1 1 kV Differential Mode, 2.5 kV Common Mode RFI Compliance...................... FCC Part 15, Subpart B, Class A - Unintentional Radiators Certification............................. CSA, Canada and USA R C LR 53428 US Notes: (1) (2) (3) (4) Over operating temperature range of -40 to 60C. CT accuracy not included. Trip time at 3 x trip-level setting. For maximum lead resistance of 1 !. Rev. 6 Page 13 PGR-5701 Ground-Fault Relay 5. ORDERING INFORMATION PGR-5701-0 U Universal 120/240-Vac/Vdc Supply D 12/24-Vdc Supply T 48-Vdc Supply PGA-0500 ........Analog Percent Current Meter PGC-3026.........Sensitive Earth-Fault CT, 5-A-primary rating, 26-mm (1") window PGC-3082.........Sensitive Earth-Fault CT, 5-A-primary rating, 82-mm (3.2") window PGC-31FC........Flux Conditioner for PGC-3082, 70-mm (2.7") window PGC-3140.........Sensitive Earth-Fault CT, with Flux Conditioner, 5-A-primary rating, 139-mm (5.5") window PGK-0055.........Panel-Mount Adapter, NEMA 1 PGK-0060.........Panel-Mount Adapter, NEMA 3, IP53 PGK-0003.........Adapter Plate, GES/MCGG PGK-0006.........Adapter Plate, FPL-GFRM PGT-0400.........Ground-Fault Relay Tester 6. GROUND-FAULT PERFORMANCE TEST To meet the requirements of the National Electrical Code (NEC), as applicable, the overall ground-fault protection system requires a performance test when first installed. A written record of the performance test is to be retained by those in charge of the electrical installation in order to make it available to the authority having jurisdiction. A test-record form is provided for recording the date and the final results of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel: a) Evaluate the interconnected system in accordance with the overall equipment manufacturer's detailed instructions. b) Verify proper location of the ground-fault current transformer. Ensure the cables pass through the ground-fault-current-transformer window. This check can be done visually with knowledge of the circuit. The connection of the current-transformer secondary to the PGR-5701 is not polarity sensitive. c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current transformer. High-voltage testers and resistance bridges can be used to determine the existence of alternate ground paths. Rev. 6 Page 14 PGR-5701 Ground-Fault Relay d) Verify proper reaction of the circuit-interrupting device in response to a simulated or controlled ground-fault current. To simulate ground-fault current, use CT-primary current injection. Fig. 7 shows a test circuit using a PGT-0400 Ground-Fault-Relay Test Unit. The PGT-0400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Set the test current to 120% of the PGR-5701 setting. Inject the test current through the current-transformer window for at least 2.5 seconds. Verify that the circuit under test has reacted properly. Correct any problems and retest until the proper reaction is verified. e) Record the date and the results of the test on the attached test-record form. NOTE: Do not inject test current directly into CT-input terminals 1, 2, 3, 4, and 5. XXX:5 FROM POWER SOURCE LOAD 1 2 3 1A 5A C L N 11 10 11 L N 3 5 8 9 5 S1 S2 L1 PGR-5701 L2/N OP1 OP2 12 L1 L2 PGT-0400 1 REMOTE TEST 4 RMT1 RMT2 FIGURE 7. Ground-Fault-Test Circuit using PGT-0400. DATE TABLE 2. Ground-Fault-Test Record TEST RESULTS Retain this record for authority having jurisdiction.