RF-TRAB Order No.: 2782135
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2782135
PHOENIX CONTACT GmbH & Co. KG Page 2 / 5
http://www.phoenixcontact.com Jul 12, 2009
Ambient temperature (operation) -40 °C ... -90 °C
Mounting type Connection-specific intermediate plugging
Design Attachment plug
Degree of protection IP20
Direction of action Line-Shield/Earth Ground
Width 60.50 mm
Height 40.00 mm
Length 18.10 mm
Protective circuit
IEC category C2
C3
D1
Arrester rated voltage UC130 V AC
Arrester rated voltage UC (Core-Earth) 130 V AC
Arrester rated voltage UC (Core-Shield) 130 V AC
Nominal current IN10 A (25°C)
Operating effective current IC at UC≤ 1 µA
Discharge current to PE at UC≤ 1 µA
Nominal discharge surge current In (8/20) µs
(Core-Earth)
10 kA
Nominal discharge surge current In (8/20) µs
(Core-Shield)
10 kA
Total surge current (8/20) µs 10 kA
Output voltage limitation at 1 kV/µs (Core-Earth)
spike
≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Shield)
spike
≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Earth)
static
≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Shield)
static
≤ 600 V
Protection level UP (Core-Earth) ≤ 600 V
Protection level UP (Core-Shield) ≤ 600 V
Response time tA (Core-Earth) ≤ 100 ns
Response time tA (Core-GND) ≤ 100 ns
Input attenuation aE, asym. 0.3 dB (≤ 250 MHz)