Characteristics
2035-xx-SM Precision Gas Discharge Tube Surge Protector
*RoHS Directive 2002/95/EC Jan 27, 2003 including Annex.
Specifi cations are subject to change without notice.
Customers should verify actual device performance in their specifi c applications.
Test Methods per ITU-T (CCITT) K.12, IEEE C62.31
Characteristic Model No.
2035-09 2035-15 2035-20 2035-23 2035-25 2035-30
DC Sparkover ±15 %
(±20 % for Model 2035-09) @ 100 V/s 90 V 150 V 200 V 230 V 250 V 300V
Impulse Sparkover
100 V/µs
1000 V/µs
350 V
525 V
400 V
550 V
425 V
575 V
450 V
600 V
475 V
625 V
525 V
650 V
Insulation Resistance (IR) ...................100 V (50 V for Model 2035-09) ............................................. > 1010 Ω
Glow Voltage ......................................10 mA ..................................................................................... ~ 70 V
Arc Voltage .........................................>1 A ........................................................................................ ~ 10 V
Glow-Arc Transition Current ............................................................................................................... < 0.5 A
Capacitance .......................................1 MHz ..................................................................................... < 1 pF
DC Holdover Voltage1 .......................>135 V, (52 V for Model 2035-09, ........................................... < 150 ms
80 V for Model 2035-15)
Impulse Discharge Current .................10000 A, 8/20 µs2 .................................................................. 1 operation minimum
5000 A, 8/20 µs ...................................................................... > 10 operations
1000 A, 10/350 µs .................................................................. 1 operation
100 A, 10/1000 µs ................................................................. > 300 operations
100 A, 10/700 µs ................................................................... > 500 operations
Alternating Discharge Current ............20 Arms, 11 cycles2 ............................................................... 1 operation minimum
5 Arms, 1 s ............................................................................. > 10 operations
Operating Temperature ....................................................................................................................... -55 to +85 °C
Climatic Category (IEC 60068-1) ........................................................................................................ 40/90/21
Notes:
• UL Recognized component, UL File E153537
• Surface Mount (SM) parts may show a temporary increase in DCBD after the solder refl ow process. Most devices will recover
within 24 hours time. It should be noted that there is no quality defect nor change in protection levels during the temporary change
in DCBD.
• Sparkover limits after life ±20 % (-25 %, +30 % for Model 2035-09, 2035-60), IR >108.
• At delivery AQL 0.65 Level II, DIN ISO 2859.
1 Network applied.
2 Tube may exceed ±20 % but will continue to protect without venting.
Characteristic Model No.
2035-35 2035-40 2035-42 2035-47 2035-60
DC Sparkover ±15 % @ 100 V/s
(-12 %, +15 % for Model 2035-60) @ 100 V/s 350 V 400 V 420 V 470 V 600 V
Impulse Sparkover
100 V/µs
1000 V/µs
600 V
750 V
650 V
800 V
675 V
850 V
750 V
950 V
950 V
1100 V
Bourns now offers a surface mount (SM) 2-electrode GDT surge protection device. The industry-leading quality and features of the
Bourns® miniature 2035 Series GDT continue in this new SM version. Compatible with “pick and place” assembly systems, the SM is
ideal for high-density applications such as PCBs for telecommunications, commercial and industrial applications.
*RoHS COMPLIANT
VERSIONS
AVAILABLE
2035 - xx - SM - RP LF
Model Number Designator
Voltage
Surface Mount
Packaging Options
Blank = Bulk Packaging (Standard)
RP = Reelpack (Optional)
RP3 = Reelpack (Optional)
RoHS Compliant Option
Blank = Standard Product
LF = RoHS Compliant Product
How to Order
Specifi cations are subject to change without notice.
Customers should verify actual device performance in their specifi c applications.
2035-xx-SM Precision Gas Discharge Tube Surge Protector
Product Dimensions
REV. L 04/11
DIMENSIONS: MM
(INCHES)
Packaging Specifi cations
The Model 2035-xx-SM ships standard bulk pack,
100 pieces per bag.
-RP
The optional -RP reelpack contains 1,500 pieces per reel.
Reel is 13 inches in diameter and 3/4 inch wide.
Recommended Pad Layout
4.4
(.173)
4.8
(.190) DIA.
5.0
(.195)
3.9
(.155)
1.3
(.050)
5.6
(.220)
-RP3
The optional -RP3 reelpack contains 1,000 pieces per reel.
Reel is 13 inches in diameter and 11/16 inch wide.
4.00
(.158)
2.00
(.079)
8.00
(.315)
16.0
(.63)
1.75
(.069)
7.5
(.30)
12.00
(.473)
4.00
(.158)
12.00 ± 1.27
(.473 ± .050)
DIMENSIONS: MM
(INCHES)