SIMATIC NET
Industrial Ethernet switches
SCALANCE X-100
Operating Instructions
02/2019
A2B00060666-10
Introduction 1
Safety notices 2
Network topologies 3
Description of the device 4
Assembly 5
Connecting up 6
Maintenance and
troubleshooting 7
Technical specifications 8
Dimension drawings 9
Certifications and approvals 10
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Siemens AG
Division Process Industries and Drives
Postfach 48 48
90026 NÜRNBERG
GERMANY
A2B00060666-10
Ⓟ 03/2019 Subject to change
Copyright © Siemens AG 2008 - 2019.
All rights reserved
Table of contents
1 Introduction...................................................................................................................................................5
1.1 On the Operating Instructions ..................................................................................................5
2 Safety notices ...............................................................................................................................................9
3 Network topologies .....................................................................................................................................11
4 Description of the device ............................................................................................................................13
4.1 Purpose..................................................................................................................................13
4.2 Product overview....................................................................................................................13
4.3 Product properties and device views .....................................................................................15
4.3.1 Overview of the SCALANCE X-100 .......................................................................................15
4.3.2 SCALANCE X104-2 ...............................................................................................................16
4.3.3 SCALANCE X106-1 ...............................................................................................................17
4.3.4 SCALANCE X108 ..................................................................................................................17
4.3.5 SCALANCE X108PoE............................................................................................................19
4.3.6 SCALANCE X112-2 ...............................................................................................................20
4.3.7 SCALANCE X116 ..................................................................................................................21
4.3.8 SCALANCE X124 ..................................................................................................................22
4.4 TP ports (twisted pair) ............................................................................................................22
4.5 FO port (fiber optic) ................................................................................................................25
4.6 LED display ............................................................................................................................26
4.7 SET button .............................................................................................................................26
5 Assembly ....................................................................................................................................................29
5.1 Safety notices for installation .................................................................................................29
5.2 Types of installation ...............................................................................................................31
5.3 Installation on a DIN rail .........................................................................................................31
5.4 Installation on a standard rail .................................................................................................33
5.5 Wall mounting ........................................................................................................................34
6 Connecting up ............................................................................................................................................35
6.1 Safety when connecting up ....................................................................................................35
6.2 Power supply..........................................................................................................................36
6.3 Signaling contact....................................................................................................................37
6.4 Grounding ..............................................................................................................................38
6.5 IE FC RJ-45 Plug 180 ............................................................................................................39
7 Maintenance and troubleshooting ..............................................................................................................41
7.1 Possible sources of problems and how to deal with them .....................................................41
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 3
8 Technical specifications..............................................................................................................................43
8.1 SCALANCE X104-2 ...............................................................................................................43
8.1.1 SCALANCE X104-2 ...............................................................................................................43
8.2 SCALANCE X106-1 ...............................................................................................................46
8.2.1 SCALANCE X106-1 ...............................................................................................................46
8.3 SCALANCE X108 ..................................................................................................................49
8.4 SCALANCE X108PoE............................................................................................................51
8.5 SCALANCE X112-2 ...............................................................................................................53
8.5.1 SCALANCE X112-2 ...............................................................................................................53
8.6 SCALANCE X116 ..................................................................................................................56
8.7 SCALANCE X124 ..................................................................................................................58
8.8 Mechanical stability (in operation)..........................................................................................61
9 Dimension drawings ...................................................................................................................................63
10 Certifications and approvals .......................................................................................................................69
Index...........................................................................................................................................................77
Table of contents
SCALANCE X-100
4Operating Instructions, 02/2019, A2B00060666-10
Introduction 1
1.1 On the Operating Instructions
Purpose of the Operating Instructions
These Operating Instructions support you when commissioning networks with the Industrial
Ethernet switches of the SCALANCE X‑100 product group.
Validity of the Operating Instructions
These Operating Instructions apply to the following devices:
SCALANCE X104‑2
SCALANCE X106‑1
SCALANCE X108
SCALANCE X108PoE
SCALANCE X112-2
SCALANCE X116
SCALANCE X124
Unless mentioned otherwise, the descriptions in these operating instructions refer to all devices
of the SCALANCE X-100 product group named above in the section on validity. If information
applies to a specific device, the device name is used, e.g. SCALANCE X104‑2.
See also
SIMATIC NET Industrial TP and FO networks (https://support.automation.siemens.com/WW/
view/en/1172207)
https://siemens.com/scalance (https://siemens.com/scalance)
Further documentation
In the system manuals "Industrial Ethernet / PROFINET Industrial Ethernet" and "Industrial
Ethernet / PROFINET passive network components", you will find information on other
SIMATIC NET products that you can operate along with the devices of this product line in an
Industrial Ethernet network.
There, you will find among other things optical performance data of the communications partner
that you require for the installation.
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 5
You will find the system manuals here:
On the data medium that ships with some products:
Product CD / product DVD
SIMATIC NET Manual Collection
On the Internet pages of Siemens Industry Online Support:
Industrial Ethernet / PROFINET Industrial Ethernet System Manual (https://
support.industry.siemens.com/cs/ww/en/view/27069465)
Industrial Ethernet / PROFINET Passive Network Components System Manual (https://
support.industry.siemens.com/cs/ww/en/view/84922825)
SIMATIC NET manuals
You will find the SIMATIC NET manuals here:
On the data medium that ships with some products:
Product CD / product DVD
SIMATIC NET Manual Collection
On the Internet pages of Siemens Industry Online Support (https://
support.industry.siemens.com/cs/ww/en/ps/15247).
SIMATIC NET glossary
Explanations of many of the specialist terms used in this documentation can be found in the
SIMATIC NET glossary.
You will find the SIMATIC NET glossary here:
SIMATIC NET Manual Collection or product DVD
The DVD ships with certain SIMATIC NET products.
On the Internet under the following address:
50305045 (https://support.industry.siemens.com/cs/ww/en/view/50305045)
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is necessary and
only when appropriate security measures (e.g. firewalls and/or network segmentation) are in
place.
Introduction
1.1 On the Operating Instructions
SCALANCE X-100
6Operating Instructions, 02/2019, A2B00060666-10
For additional information on industrial security measures that may be implemented, please
visit
https://www.siemens.com/industrialsecurity (https://www.siemens.com/industrialsecurity)
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customers’ exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under
https://www.siemens.com/industrialsecurity (https://www.siemens.com/industrialsecurity)
Catalogs
You will find the article numbers for the Siemens products of relevance here in the following
catalogs:
SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI
SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog ST 70
Industry Mall - catalog and ordering system for automation and drive technology, Online
catalog (https://mall.industry.siemens.com/goos/WelcomePage.aspx?regionUrl=/
de&language=en)
You can request the catalogs and additional information from your Siemens representative.
Device defective
If a fault develops, please send the device to your SIEMENS service center for repair. Repairs
on-site are not possible.
Recycling and disposal
The products are low in pollutants, can be recycled and meet the requirements of the WEEE
directive 2012/19/EU for the disposal of electrical and electronic equipment.
Do not dispose of the products at public disposal sites.
For environmentally friendly recycling and the disposal of your old device contact a certified
disposal company for electronic scrap or your Siemens contact (Product return (https://
support.industry.siemens.com/cs/ww/en/view/109479891)).
Note the different national regulations.
Trademarks
The following and possibly other names not identified by the registered trademark sign ® are
registered trademarks of Siemens AG:
SIMATIC NET, SCALANCE, C-PLUG, OLM
Introduction
1.1 On the Operating Instructions
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 7
Electrostatic discharge
NOTICE
Electrostatic sensitive devices (ESD)
Electronic modules contain electrostatic sensitive components
These components can easily be destroyed if handled incorrectly.
Note the following instructions to avoid damage.
Touch electronic modules only when you absolutely need to work on them.
If electronic modules need to be touched, the body of the person involved must first be
electrostatically discharged and grounded.
Do not bring electronic modules in contact with electrically isolating materials such as
plastic film, isolating table top pads or clothing made of synthetic fibers.
Place the modules only on conductive surfaces.
Pack, store and transport electronic modules and components only in conductive
packaging such as metalized plastic or metal containers, conductive foam or household
aluminum foil.
Introduction
1.1 On the Operating Instructions
SCALANCE X-100
8Operating Instructions, 02/2019, A2B00060666-10
Safety notices 2
Read the safety notices
Note the following safety notices. These relate to the entire working life of the device.
You should also read the safety notices relating to handling in the individual sections,
particularly in the sections "Installation" and "Connecting up".
CAUTION
To prevent injury, read the manual before use.
Safety notices on use in hazardous areas
General safety notices relating to protection against explosion
WARNING
EXPLOSION HAZARD
Do not open the device when the supply voltage is turned on.
Safety notices when using the device according to Hazardous Locations (HazLoc) and FM.
If you use the device under HazLoc or FM conditions you must also keep to the following safety
notices in addition to the general safety notices for protection against explosion:
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous
locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations only.
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 9
Safety notices
SCALANCE X-100
10 Operating Instructions, 02/2019, A2B00060666-10
Network topologies 3
Switching technology allows extensive networks to be set up with numerous nodes and
simplifies network expansion.
Which topologies can be implemented?
Using the IE switches of the SCALANCE X-100 product line, you can implement star
topologies.
Note
Keep to the maximum permitted cable lengths of the devices you are using. You will find the
permitted cable lengths in the section "Technical specifications (Page 43)".
Star topology
6ZLWK&36ZLWK&3&DELQHW,3&ZLWK&3$&3,3&ZLWK&3$&36ZLWK&3$GYDQFHG6ZLWK&303036,0$7,&)LHOG3*,()&2XWOHW5-,(73&RUG
0ELWV,QGXVWULDO(WKHUQHW)&&DEOH[
6ZLWFKHV6&$/$1&(;
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 11
Figure 3-1 Example of an electrical star topology with SCALANCE X124
0ELWV,QGXVWULDO(WKHUQHW)&&DEOH[
603ZLWK&3&DELQHW6ZLWK&3$GYDQFHG,3&ZLWK&3$&36ZLWK&36ZLWK&3$GYDQFHG6ZLWK&36ZLWK&36ZLWK&3PROFINET
Industrial
Ethernet 6&$/$1&(;6ZLWFK6&$/$1&(;036ZLWFK6&$/$1&(;6ZLWFK6&$/$1&(;,()&5-3OXJ[Industrial Ethernet (Twisted Pair)
Industrial Ethernet (Fiber Optic)
Figure 3-2 Example of an electrical/optical star topology with SCALANCE X112-2 and SCALANCE X104-2
Network topologies
SCALANCE X-100
12 Operating Instructions, 02/2019, A2B00060666-10
Description of the device 4
4.1 Purpose
What is possible?
The devices of the SCALANCE X100 product line allow the cost-effective installation of
Industrial Ethernet bus and star structures with switching functionality.
With the following IE switches, there are also electrical/optical media transitions:
SCALANCE X104-2
SCALANCE X106-1
SCALANCE X112-2
IE switches with the suffix PoE also allow the supply of power to end devices over Ethernet
cables with Power-over-Ethernet complying with 802.3af.
Note
If devices are supplied over long 24 V power supply lines or networks, measures are necessary
to prevent interference by strong electromagnetic pulses on the supply lines. These can result,
for example, due to lightning or switching of large inductive loads.
One of the tests used to attest the immunity of these devices to electromagnetic interference is
the "surge immunity test" according to EN 61000-4-5. This test requires overvoltage protection
for the power supply lines. A suitable device is, for example, the Dehn Blitzductor BVT AVD 24
V type no. 918 422 or a comparable protective element.
Manufacturer:
DEHN+SÖHNE GmbH+Co.KG Hans Dehn Str.1 Postfach 1640 D-92306 Neumarkt, Germany
4.2 Product overview
Article numbers
Device Description Article number
SCALANCE X104‑2 4x 10/100 Mbps RJ45 ports, 2x 100 Mbps mul‐
timode BFOC
6GK5 104‑2BB00‑2AA3
SCALANCE X106‑1 6x 10/100 Mbps RJ45 ports, 1x 100 Mbps mul‐
timode BFOC
6GK5 106‑1BB00‑2AA3
SCALANCE X108 8x 10/100 Mbps RJ45 ports 6GK5 108‑0BA00‑2AA3
SCALANCE X108PoE 2x 10/100 Mbps RJ45 Power over-Ethernet
ports and 6x 10/100 Mbps RJ45 ports
6GK5 108-0PA00-2AA3
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 13
Device Description Article number
SCALANCE X112-2 12x 10/100 Mbps RJ45 ports, 2x 100 Mbps
multimode BFOC
6GK5 112-2BB00-2AA3
SCALANCE X116 16x 10/100 Mbps RJ45 ports 6GK5 116-0BA00-2AA3
SCALANCE X124 24x 10/100 Mbps RJ45 ports 6GK5 124-0BA00-2AA3
Unpacking and checking
WARNING
Do not use any parts that show evidence of damage
If you use damaged parts, there is no guarantee that the device will function according to the
specification.
If you use damaged parts, this can lead to the following problems:
Injury to persons
Loss of the approvals
Violation of the EMC regulations
Damage to the device and other components
Use only undamaged parts.
1. Make sure that the package is complete.
2. Check all the parts for transport damage.
Components of the product
The following components are supplied with a SCALANCE X-100:
IE Switch SCALANCE X-100
2-pin plug-in terminal block (signaling contact)
4-pin plug-in terminal block (power supply)
Product information
Accessories
Component Packaging unit Order number
IE FC Stripping Tool 1 6GK1901‑1GA00
IE FC blade cassettes (5 mm) 1 6GK1901‑1GB01
IE FC TP standard cable GP 1 6XV1840‑2AH10
IE FC TP trailing cable 1 6XV1840‑3AH10
IE FC TP marine cable 1 6XV1840‑4AH10
IE FC TP trailing cable GP 1 6XV1870‑2D
IE FC TP flexible cable GP 1 6XV1870‑2B
IE FC TP FRNC cable GP 1 6XV1871-2F
Description of the device
4.2 Product overview
SCALANCE X-100
14 Operating Instructions, 02/2019, A2B00060666-10
Component Packaging unit Order number
IE FC TP festoon cable GP 1 6XV1871-2S
IE FC TP food cable 1 6XV1871-2L
IE TP torsion cable 1 6XV1870-2F
FO standard cable GP (50/125) 1 6XV1873-2A
FO trailing cable (50/125) 1 6XV1873-2C
FO trailing cable GP (50/125) 1 6XV1873-2D
FO ground cable (50/125) 1 6XV1873-2G
FO FRNC cable (50/125) 1 6XV1873-2B
IE FC RJ-45 Plug 180 1 6GK1901‑1BB10‑2AA0
IE FC RJ-45 Plug 180 10 6GK1901‑1BB10‑2AB0
IE FC RJ-45 Plug 180 50 6GK1901‑1BB10‑2AE0
4.3 Product properties and device views
4.3.1 Overview of the SCALANCE X-100
Table 4-1 Overview of the product characteristics
Device type SCALANCE
X104-2 X106-1 X108 X108PoE X112-2 X116 X124
SIMATIC environment + + + + + + +
Diagnostics LED + + + + + + +
24 VDC + + + + + + +
2 x 24 VDC + + + + + + +
Compact housing
(securing collar, etc.)
+ + + + + + +
Signaling contact + on-site oper‐
ation
+ + + + + + +
Diagnostics: Web, SNMP, PRO‐
FINET
- - - - - - -
C-PLUG - - - - - - -
Ring redundancy with RM - - - - - - -
Passive ring redundancy - - - - - - -
Standby redundancy - - - - - - -
IRT capability - - - - - - -
Fast learning - - - - - - -
Passive listening - - - - - - -
Log table - - - - - - -
SNTP + SICLOCK - - - - - - -
Cut Through - - - - - - -
Number of PoE ports - - - 2 - - -
Description of the device
4.3 Product properties and device views
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 15
Fast learning:
Fast recognition of MAC addresses on the device that change during operation (for example,
when an end node is reconnected).
Table 4-2 Overview of the connection options
Device type SCALANCE
X104-2 X106-1 X108 X108PoE X112-2 X116 X124
TP (RJ-45)
Fast Ethernet 10 / 100 Mbps
4 6 8 8 12 16 24
Fiber multimode (BFOC)
Fast Ethernet 100 Mbps
2 1 - - 2 - -
4.3.2 SCALANCE X104-2
Possible connections
The SCALANCE X104-2 has four RJ-45 jacks and two BFOC sockets for the connection of end
devices or other network segments.
Note
The BFOC socket (Bayonet Fiber Optic Connector) corresponds to the ST socket.
Figure 4-1 SCALANCE X104-2
Description of the device
4.3 Product properties and device views
SCALANCE X-100
16 Operating Instructions, 02/2019, A2B00060666-10
4.3.3 SCALANCE X106-1
Possible connections
The SCALANCE X106-1 has six RJ-45 jacks and a BFOC socket for the connection of end
devices or other network segments.
Note
The BFOC socket (Bayonet Fiber Optic Connector) corresponds to the ST socket.
Figure 4-2 SCALANCE X106-1
4.3.4 SCALANCE X108
Possible connections
The SCALANCE X108 has eight RJ-45 jacks for the connection of end devices or other network
segments.
Description of the device
4.3 Product properties and device views
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 17
Figure 4-3 SCALANCE X108
Description of the device
4.3 Product properties and device views
SCALANCE X-100
18 Operating Instructions, 02/2019, A2B00060666-10
4.3.5 SCALANCE X108PoE
Possible connections
The SCALANCE X108 PoE has eight RJ-45 jacks for the connection of end devices or other
network segments. Ports 1 and 2 have the PoE function.
Figure 4-4 SCALANCE X108PoE
Power over Ethernet (PoE) function
The PoE function allows the power supply of connected Ethernet devices via the Ethernet cable
so that the end device does not need a separate power supply.
Per PoE port of the PSE (Power Sourcing Equipment), a maximum of 15.4 W power are
available according to the 802.3af standard.
Note
With a 100 m long cable connected, the end device then has a maximum of 12.95 W available.
You will find more information on the PoE function in the section "TP ports (Page 22)".
Description of the device
4.3 Product properties and device views
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 19
4.3.6 SCALANCE X112-2
Possible connections
The SCALANCE X112-2 has twelve RJ-45 jacks and two BFOC sockets for the connection of
end devices or other network segments.
Note
The BFOC socket (Bayonet Fiber Optic Connector) corresponds to the ST socket.
Figure 4-5 SCALANCE X112-2
Description of the device
4.3 Product properties and device views
SCALANCE X-100
20 Operating Instructions, 02/2019, A2B00060666-10
4.3.7 SCALANCE X116
Possible connections
The SCALANCE X116 has 16 RJ-45 jacks for the connection of end devices or other network
segments.
Figure 4-6 SCALANCE X116
Description of the device
4.3 Product properties and device views
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 21
4.3.8 SCALANCE X124
Possible connections
The SCALANCE X124 has 24 RJ-45 jacks for the connection of end devices or other network
segments.
Figure 4-7 SCALANCE X124
4.4 TP ports (twisted pair)
Note
Strain relief for the Ethernet cables
In order to avoid mechanical stress on the Ethernet cables and resulting interruption of the
contact, fasten the cables at a short distance from the connector using a cable guide or busbar.
Description of the device
4.4 TP ports (twisted pair)
SCALANCE X-100
22 Operating Instructions, 02/2019, A2B00060666-10
RJ-45 connector pinout
With SCALANCE X-100, the twisted-pair port is designed as an RJ-45 jack with MDI-X pin
assignment (Medium Dependent Interface Autocrossover) of a network component.
Special features of the SCALANCE X108PoE
Over and above the pure Ethernet functionality, ports 1 and 2 of the SCALANCE X108PoE can
also be used to supply power to Power-over-Ethernet end devices (for example SCALANCE-
W) in compliance with 802.3af.
The two ports providing PoE are supplied from the same power source. This means that they
are electrically interconnected. They are however isolated from ground, from the ports that do
not provide PoE and from the power connector (24 V). Their use is therefore subject to the
conditions listed in IEEE 802.3af for Environment A.
The ports that do not provide PoE are all isolated from each other.
Ports 3 to 8 do not have the PoE function.
To supply PoE end devices, 4 or 8-wire connecting cables can be used (according to IEEE
802.3).
Note
Ethernet devices without PoE functionality can also be connected to ports 1 and 2. A voltage
is applied only after the SCALANCE X108 PoE has detected a PoE end device complying with
the standard at the port.
Pin number Assignment Additional pins P1, P2 of the SCALANCE X108PoE
Pin 8 n. c. -
Pin 7 n. c. -
Pin 6 TD- positive supply voltage
Pin 5 n. c. -
Pin 4 n. c. -
Pin 3 TD+ positive supply voltage
Pin 2 RD- negative supply voltage
Pin 1 RD+ negative supply voltage
Description of the device
4.4 TP ports (twisted pair)
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 23
Note
Permitted cable lengths
TP cords or TP-XP cords with a maximum length of 10 m can be connected to the TP port with
the RJ-45 jack.
With the IE FC cables and IE FC RJ-45 plugs 180, an overall cable length of a maximum of 100
m is permitted between two devices depending on the cable type.
Autonegotiation
With the autonegotiation mechanism, repeaters and end devices can automatically determine
the transmission speed and the transmission mode of the partner port. This makes it possible
to configure different devices automatically.
Two components connected to a link segment can exchange information about the data
transfer and can adapt their settings to each other. The mode with the highest possible speed
is set.
Note
Devices not supporting autonegotiation must be set permanently to 100 Mbps half duplex or
10 Mbps half duplex.
Note
The IE switches of the SCALANCE X-100 product line are plug-and-play devices that require
no settings during commissioning.
Auto polarity exchange
If the pair of receiving cables is connected incorrectly (RD+ and RD- interchanged), the polarity
is adapted automatically.
MDI / MDI-X autocrossover function
With the MPI/MDI-X autocrossover function, the send and receive contacts of an Ethernet port
are assigned automatically. The assignment depends on the cable with which the
communications partner is connected. This means that it does not matter whether the port is
connected using a patch cable or crossover cable. This prevents malfunctions resulting from
mismatching send and receive wires. This makes installation much easier for the user.
Description of the device
4.4 TP ports (twisted pair)
SCALANCE X-100
24 Operating Instructions, 02/2019, A2B00060666-10
The IE Switches SCALANCE X-100 all support the MDI / MDI-X autocrossover function.
NOTICE
Formation of loops
Note that the direct connection of two ports or accidental connection over several switches
causes an illegal loop that can cause network overload and failure.
4.5 FO port (fiber optic)
Transmission speed
The transmission speed of the optical Fast Ethernet ports is 100 Mbps.
Transmission technique
The transmission mode for 100Base-FX is specified in the IEEE 802.3 standard.
Since the full duplex mode and the transmission rate cannot be modified for optical
transmission, autonegotiation cannot be selected.
Transmission medium
Data transmission is over multimode fiber-optic cable (FO cable). The wavelength is 1310 nm.
Multimode fiber-optic cables are used with a core of 50 or 62.5 µm; the light source is an LED.
The outer diameter of the FO cable is 125 µm.
Transmission range
The maximum transmission range (segment length) is as follows:
with 62.5/125 µm fiber multimode SIMATIC NET cable: 4 km
with 50.0/125 µm fiber multimode SIMATIC NET cable: 5 km
Connectors
The cables are connected over BFOC sockets.
Description of the device
4.5 FO port (fiber optic)
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 25
4.6 LED display
Fault LED "F" (red LED)
The fault LED indicates the incorrect functioning of the device.
LED color LED status Meaning
Red Lit The IE switch detects an error. At the same time, the signaling contact opens.
The following faults/errors are detected:
1. Link down event on a monitored port.
2. Loss of the power supply of one of the two redundant power supplies or the power
supply drops below 14 V.
3. Both power supplies are below approximately 14 V (voltage too low).
- Off No error detected.
Power LEDs “L1” and “L2” (green LEDs)
The power LEDs show the status of the power supply at connectors L1 and L2.
L1/L2 LEDs L1/L2 connector
LED color LED status
Green Lit Power supply L1 or L2 is connected.
- Off Power supply L1 and L2 are not connected or L1 and L2 < 14 V.
Note
If the green LED is not lit, no other signal LED lights up either.
Port LEDs "P" (green/yellow LEDs)
The port LEDs indicate the status of the ports.
LED color LED status Meaning
Green Lit Link exists, no data reception at port
Yellow Lit Link exists, data reception at port
Yellow Flashing Setting or display of the fault mask
4.7 SET button
Function
With the SET button, you can display and change the set fault mask.
Description of the device
4.7 SET button
SCALANCE X-100
26 Operating Instructions, 02/2019, A2B00060666-10
Setting the fault mask
Factory setting
In its delivery condition (factory default), the following settings are monitored via the message
screen:
Link up to all ports
Redundant power supply (L1+/M1 und L2+/M2) connected
When you turn the device on and at least one of the settings is not fulfilled, the device registers
a fault. Switch the device to the required operating mode and save these settings in the
message screen.
Changing the setting
The changed settings remain after cycling power to the device.
Different settings are made depending on how long you hold down the SET button, as
described in the following table:
3KDVH3KDVH3KDVH7LPHWKHEXWWRQLVSUHVVHGLQVHFRQGVVVV
Phase Description
1
LEDs flash at 5 Hz The currently set fault mask is displayed. The LEDs of the monitored ports
flash.
If no fault mask is set, all port LEDs flash one after the other.
If you release the button in phase 1, this has no effect.
2 LEDs flash at 2.5 Hz The current status is displayed.
The LEDs of the ports at which there is currently a link flash.
If you release the button in phase 2, this has no effect.
3 This new status is adopted and stored as the new fault mask in phase 3.
LEDs flashing If you release the SET button while the LEDs are still flashing, storing is
aborted.
LEDs lit If you release the SET button as soon as the LEDs light up, the current
settings will be stored.
The stored status is displayed.
The monitored ports are indicated by statically lit LEDs.
The monitored power supply is indicated by statically lit LEDs.
Error/fault
If the link is lost (link down) at a monitored port or a monitored power supply is lost, this is
signaled as follows:
The red fault LED lights up.
The signaling contact is opened.
Description of the device
4.7 SET button
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 27
Description of the device
4.7 SET button
SCALANCE X-100
28 Operating Instructions, 02/2019, A2B00060666-10
Assembly 5
5.1 Safety notices for installation
Safety notices
When installing the device, keep to the safety notices listed below.
WARNING
Ambient temperature above 55 °C
If a device is operated in an ambient temperature of more than 55 °C, the temperature of the
device housing may be higher than 70 °C. The device must therefore be installed so that it is
only accessible to service personnel or users that are aware of the reason for restricted access
and the required safety measures at an ambient temperature higher than 55 °C.
WARNING
If a SCALANCE X108PoE is operated at ambient temperatures between 55 °C and 60 °C,
there must be a minimum clearance of 40 mm to neighboring modules.
Safety notices on use in hazardous areas
General safety notices relating to protection against explosion
WARNING
EXPLOSION HAZARD
Replacing components may impair suitability for Class 1, Division 2 or Zone 2.
WARNING
The device may only be operated in an environment with pollution degree 1 or 2 (see
IEC 60664-1).
WARNING
When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone
2, the device must be installed in a cabinet or a suitable enclosure.
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 29
Safety notices for use according to ATEX and IECEx
If you use the device under ATEX or IECEx conditions you must also keep to the following
safety notices in addition to the general safety notices for protection against explosion:
WARNING
To comply with EC Directive 2014/34/EU (ATEX 114) or the conditions of IECEx, this
enclosure or cabinet must meet the requirements of at least IP54 in compliance with EN
60529.
WARNING
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors exceeds
80 °C, special precautions must be taken. If the equipment is operated in an air ambient in
excess of 50 °C to 60 °C, only use cables with admitted maximum operating temperature of
at least 80 ℃.
Further notes
CAUTION
Use only approved components
If you use components and accessories that are not approved for SIMATIC NET devices or
their target systems, this may violate the requirements and regulations for safety and
electromagnetic compatibility.
Only use components approved for the SIMATIC NET devices.
NOTICE
Warming and premature aging of the IE switch due to direct sunlight
Direct sunlight can heat up the device and can lead to premature aging of the IE switch and
its cabling.
Provide suitable shade to protect the IE switch against direct sunlight.
Note
During installation and operation, keep to the installation guidelines and safety notices
described in this document and in the system manuals "Industrial Ethernet / PROFINET
Industrial Ethernet" and "Industrial Ethernet / PROFINET passive network components".
You will find information on the system manuals in the chapter "Introduction", in the section
"Further documentation".
Assembly
5.1 Safety notices for installation
SCALANCE X-100
30 Operating Instructions, 02/2019, A2B00060666-10
5.2 Types of installation
The devices can be installed in the following ways:
Installation on a 35 mm DIN rail
Installation on a SIMATIC S7-300 standard rail
Wall mounting
WARNING
If a device is operated in an ambient temperature between 50 and 75 ℃, the temperature
of the device housing may be higher than 70 °C. The device must therefore be installed so that
it is only accessible to service personnel or users that are aware of the reason for restricted
access and the required safety measures at an ambient temperature of 50 ℃ to 75 ℃.
Installation clearance
Keep to the minimum clearances so that the convection ventilation of the device is not blocked.
Below at least 10 cm
Above at least 10 cm
5.3 Installation on a DIN rail
Installation
To install the device on a 35 mm DIN rail complying with DIN EN 50022, follow the steps below:
1. Place the second housing guide of the device on the top edge of the DIN rail.
2. Press the device down against the DIN rail until the spring catch locks in place.
3. Fit the connectors for the power supply. See also section "Power supply (Page 36)".
4. Fit the connectors for the signaling contacts. See also section "Signaling contacts
(Page 37)".
5. Insert the terminal blocks into the sockets on the device.
WARNING
Use of the SCALANCE X108PoE in shipbuilding
When used in shipbuilding, mounting the SCALANCE X108PoE on 35 mm DIN rails is not
permitted.
35 mm DIN rails do not ensure sufficient stability when used in shipbuilding.
Assembly
5.3 Installation on a DIN rail
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 31
Figure 5-1 Installation on a 35 mm DIN rail
Uninstalling
To remove the device from the DIN rail, follow the steps below:
1. Disconnect all connected cables.
2. Release the DIN rail catch on the bottom of the device using a screwdriver.
3. Pull the lower part of the device away from the DIN rail.
Assembly
5.3 Installation on a DIN rail
SCALANCE X-100
32 Operating Instructions, 02/2019, A2B00060666-10
Figure 5-2 Removal from a 35 mm DIN rail
5.4 Installation on a standard rail
Installation on a SIMATIC S7-300 standard rail
To install the device on an S7-300 standard rail, follow the steps below:
1. Place the first housing guide of the device on the top edge of the S7-300 standard rail.
2. Screw the device to the underside of the standard rail (tightening torque 2 Nm).
3. Fit the connectors for the power supply. See also section "Power supply (Page 36)".
Assembly
5.4 Installation on a standard rail
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 33
4. Fit the connectors for the signaling contacts. See also section "Signaling contacts
(Page 37)".
5. Insert the terminal blocks into the sockets on the device.
Figure 5-3 Installation on a SIMATIC S7-300 standard rail
Uninstalling
To remove the device from the S7-300 standard rail, follow the steps below:
1. Disconnect all connected cables.
2. Release the screw holding the device on the bottom of the standard rail.
3. Lift the device off the standard rail.
5.5 Wall mounting
Note
Depending on the mounting surface, use suitable fittings.
Note
The wall mounting must be capable of supporting at least four times the weight of the device.
To mount the device on a wall, follow the steps below:
1. Prepare the drill holes for wall mounting. For the precise dimensions, refer to the section
"Dimension drawings (Page 63)".
2. Screw the device to the wall using the keyhole hang-up mechanisms.
3. Fit the connectors for the power supply, see the section "Power supply (Page 36)".
4. Fit the connectors for the signaling contact, refer to the section ""Signaling contacts
(Page 37)".
Assembly
5.5 Wall mounting
SCALANCE X-100
34 Operating Instructions, 02/2019, A2B00060666-10
Connecting up 6
6.1 Safety when connecting up
Safety notices
When connecting up the device, keep to the safety notices listed below.
WARNING
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a Limited
Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals, or the power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code (r)
(ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
NOTICE
Failure of the data traffic due to contamination of optical plug-in connections
Optical sockets and plugs are sensitive to contamination of the end face. Contamination can
lead to the failure of the optical transmission network. Take the following precautions to avoid
functional impairments:
Clean the end face of field-assembled connectors carefully before connecting. No residues
of processing may remain on the connector.
Only remove the dust caps of optical transceivers and pre-configured cables shortly before
connecting the cables.
Close unused optical sockets and plugs as well as pluggable transceivers and slots with
the supplied protective caps.
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 35
Safety notices on use in hazardous areas
General safety notices relating to protection against explosion
WARNING
EXPLOSION HAZARD
Do not connect or disconnect cables to or from the device when a flammable or combustible
atmosphere is present.
Safety notices when using the device according to Hazardous Locations (HazLoc)
If you use the device under HazLoc conditions you must also keep to the following safety
notices in addition to the general safety notices for protection against explosion:
WARNING
EXPLOSION HAZARD
You may only connect or disconnect cables carrying electricity when the power supply is
switched off or when the device is in an area without inflammable gas concentrations.
Safety notices for use according to ATEX and IECEx
If you use the device under ATEX or IECEx conditions you must also keep to the following
safety notices in addition to the general safety notices for protection against explosion:
WARNING
Take measures to prevent transient voltage surges of more than 40% of the rated voltage.
This is the case if you only operate devices with SELV (safety extra-low voltage).
6.2 Power supply
The power supply is connected using a 4-pin plug-in terminal block. The power supply can be
connected redundantly. Both inputs are isolated. There is no distribution of load. When a
redundant power supply is used, the power supply unit with the higher output voltage supplies
the device alone. The power supply is connected over a high resistance with the enclosure to
allow an ungrounded set up. The two power supplies are non-floating.
The following figure shows the position of the power supply of the SCALANCE X-100 IE
switches and the assignment of the terminal block.
Connecting up
6.2 Power supply
SCALANCE X-100
36 Operating Instructions, 02/2019, A2B00060666-10
//00
Pin number Assignment
Pin 1 L1+ (24 VDC)
Pin 2 M1 (ground)
Pin 3 M2 (ground)
Pin 4 L2+ (24 VDC)
WARNING
Incorrect power supply
The power supply unit to supply the device must comply with NEC Class 2 (voltage range 18
- 32 V, current requirement 350 mA).
Do not operate the device with an AC voltage.
Never operate the device with DC voltages higher than 32 VDC.
6.3 Signaling contact
The signaling contact is connected to a 2-pin plug-in terminal block. The signaling contact (relay
contact) is a floating switch with which error/fault states can be signaled by breaking the
contact.
NOTICE
Damage due to voltage being too high
The signaling contact can be subjected to a maximum load of 100 mA (safety extra‑low
voltage SELV, 24 VDC).
Higher voltages or currents can damage the device!
The following figure shows the position of the signaling contacts of the SCALANCE X-100 IE
switches and the assignment of the terminal block.
Connecting up
6.3 Signaling contact
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 37
))
Pin number Assignment
Pin 1 F1
Pin 2 F2
The following errors/faults can be signaled by the signaling contact:
The failure of a link at a monitored port.
The failure of one of the two monitored power supplies.
The connection or disconnection of a communication node on an unmonitored port does not
lead to an error message.
The signaling contact remains activated until the error/fault is eliminated or until the current
status is applied as the new desired status using the button.
When the device is turned off, the signaling contact is always activated (open).
6.4 Grounding
Installation on a DIN rail
The device is grounded over the DIN rail.
S7 standard rail
The device is grounded over its rear panel and the neck of the screw.
Wall mounting
The device is grounded by the securing screw in the unpainted hole.
Note that the device must be grounded over a securing screw with as low a low resistance as
possible.
If the device is mounted on a non-conductive base, a grounding cable must be fitted. The
grounding cable is not supplied with the device. Connect the paint-free surface of the device to
the nearest grounding point using the grounding cable.
Connecting up
6.4 Grounding
SCALANCE X-100
38 Operating Instructions, 02/2019, A2B00060666-10
6.5 IE FC RJ-45 Plug 180
The rugged node connectors are designed for industry with PROFINET-compliant connectors
and provide additional strain and bending relief with a locking mechanism on the casing.
Fitting the IE FC RJ45 Plug 180 to the IE FC Standard Cable
You will find the notes on installation in the instructions that ship with the IE FC RJ45 Plug 180.
Figure 6-1 IE FC 45 Plug 180
Connecting up
6.5 IE FC RJ-45 Plug 180
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 39
Plugging in the IE FC RJ45 Plug 180
Plug the IE FC RJ45 Plug 180 into the twisted-pair port of the device until it locks in place.
Figure 6-2 Plugging in the IE FC RJ45 Plug 180
With its tight fit and locking mechanism with the PROFINET-compliant male connector
IE FC RJ45 Plug 180, the securing collar on the TP port of the device ensures a rugged node
attachment that provides strain and bending relief for the RJ-45 jack.
Pulling the IE FC RJ45 Plug 180
Press on the locking lever of the IE FC RJ45 Plug 180 gently to remove the plug.
If there is not enough space to release the lock with your hand, you can also use a 2.5 mm
screwdriver. You can then remove the IE FC RJ45 Plug 180 from the RJ-45 jack.
Connecting up
6.5 IE FC RJ-45 Plug 180
SCALANCE X-100
40 Operating Instructions, 02/2019, A2B00060666-10
Maintenance and troubleshooting 7
7.1 Possible sources of problems and how to deal with them
Fuses
Some of the Industrial Ethernet switches of the SCALANCE X-100 product line have a
resettable fuse / PTC. If the fuse triggers (all LEDs are off despite correctly applied power
supply), the device should be disconnected from the power supply for approximately 30
minutes before turning it on again.
Link display on the optical ports
The Industrial Ethernet switches SCALANCE X104‑2, SCALANCE X106‑1 and
SCALANCE X112‑2 support "far-end fault" on the optical ports but do not use this for the
corresponding link display. This means that if there is only a cable connected in the receive
direction on the optical port, a far-end fault is detected and no data is forwarded. The Link LED
is already lit.
LED display when voltage drops
If both of the power supplies drop below approximately 14 V, this reduced voltage is indicated
by the red fault LED. The L LEDs go off.
Device defective
If a fault develops, please send the device to your SIEMENS service center for repair. Repairs
on-site are not possible.
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 41
Maintenance and troubleshooting
7.1 Possible sources of problems and how to deal with them
SCALANCE X-100
42 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications 8
8.1 SCALANCE X104-2
8.1.1 SCALANCE X104-2
Table 8-1 Technical specifications of the SCALANCE X104-2
Technical specifications
Order number
SCALANCE X104-2 6GK5104‑2BB00‑2AA3
Connection to Industrial Ethernet
Number 4
Design RJ-45 jacks with MDI‑X pinning
Properties Half / full duplex
Transmission speed 10/100 Mbps
Optical connectors
Number 2
Design BFOC sockets
Properties Full duplex to 100 Base-FX
Transmission speed 100 Mbps
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 to 85 m Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 to 100 m Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Optical parameters
Cable type Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm
Permitted cable length (glass FO ca‐
ble)
Cable cross-section Permitted cable length
62.5/125 μm
50/125 μm
0 to 4000 m
0 to 5000 m
Attenuation ≤ 1 dB/km at 1300 nm
1200 MHz x km at 1300 nm
6 dB max. permitted FO cable attenuation with
3 dB link power margin
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 43
Technical specifications
Electrical data
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
(SELV)
Rated voltage 24 VDC
Design 4-terminal plug-in block
Signaling contact Current max. 100 mA
Rated voltage 24 VDC
Design 2-pin plug-in terminal block
Current consumption Typical 160 mA
Power loss at 24 VDC Typical 3.8 W
Overvoltage protection at input PTC resettable fuse (0.6 A / 60 V)
Permitted ambient conditions
Ambient temperature During operation -10 °C to +60 °C
During storage -40 °C to +80 °C
During transportation -40 °C to +80 °C
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C
ambient temperature
≤ 3,000 m above sea level at max. 50 °C
ambient temperature
Design, dimensions and weight
Immunity to interference EN 61000-6-2
Emission EN 61000-6-4
Degree of protection IP 30
MTBF (EN/IEC 61709, 40 °C) 134.87 years
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene (PPE
+PS plastic)
Weight 780 g
Dimensions (W x H x D) 60 x 125 x 124 mm
Installation options Installation on a DIN rail
Installation on an S7-300 standard rail
Wall mounting
Switching properties
Aging time 30 seconds
Max. number of learnable MAC ad‐
dresses
2048
Response to LLDP frames Blocking
Response to spanning tree BPDU
frames
Forwarding
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
Technical specifications
8.1 SCALANCE X104-2
SCALANCE X-100
44 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications
Maximum frame size 1536 bytes
Forwarding of PRP frames (Parallel
Redundancy Protocol)
Yes
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
This means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.
Optical connectors
Quantity 2
Connectors
The attachment to Industrial Ethernet uses ST/
BFOC connector technology (Straight Tip/Bayo‐
net Fiber Optic Connector).
Properties
Transmission mode 100Base-FX complying with IEEE 802.3
Transmission rate 100 Mbps (Fast Ethernet)
Transmission medium Multimode fiber-optic cable
Light source LED/Class1-LASER "Eye safe"
Wavelength 1300 nm
Cable length (max.) *) At 50 µm fiber core diameter 3 km
At 62.5 µm fiber core diameter 3 km
Transmitter output (optical) Minimum At 50 μm -23 dBm
At 62.5 μm -19 dBm
Maximum -14 dBm
Technical specifications
8.1 SCALANCE X104-2
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 45
Properties
Receiver input Sensitivity min. -32 dBm
Input power max. -3 dBm
*) Depending on the cable used:
If you are using at least OM1 fibers (attenuation ≤ 1.5 dB/km, bandwidth length product ≥
500 MHz*km), you can reach a cable length of up to 3 km.
When are using fibers with attenuation values ≤ 1 dB/km, you can reach a cable length of
up to 5 km.
You can find additional information in the "Industrial Ethernet / PROFINET Passive network
components" System Manual, see also section "Introduction", paragraph "Additional
documentation".
8.2 SCALANCE X106-1
8.2.1 SCALANCE X106-1
Table 8-2 Technical specifications of the SCALANCE X106-1
Technical specifications
Order number
SCALANCE X106-1 6GK5106‑1BB00‑2AA3
Connection to Industrial Ethernet
Number 6
Design RJ-45 jacks with MDI‑X pinning
Properties Half / full duplex
Transmission speed 10/100 Mbps
Optical connectors
Number 1
Design BFOC socket
Properties Full duplex to 100 Base-FX
Transmission speed 100 Mbps
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 to 85 m Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 to 100 m Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Technical specifications
8.2 SCALANCE X106-1
SCALANCE X-100
46 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications
Optical parameters
Cable type Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm
Permitted cable length (glass FO ca‐
ble)
Cable cross-section Permitted cable length
62.5/125 μm
50/125 μm
0 to 4000 m
0 to 5000 m
Attenuation ≤ 1 dB/km at 1300 nm
1200 MHz x km at 1300 nm
6 dB max. permitted FO cable attenuation with
3 dB link power margin
Electrical data
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
(SELV)
Rated voltage 24 VDC
Design 4-terminal plug-in block
Signaling contact Current max. 100 mA
Rated voltage 24 VDC
Design 2-pin plug-in terminal block
Current consumption Typical 150 mA
Power loss at 24 VDC Typical 3.6 W
Overvoltage protection at input PTC resettable fuse (0.6 A / 60 V)
Permitted ambient conditions
Ambient temperature During operation -10 °C to +60 °C
During storage -40 °C to +80 °C
During transportation -40 °C to +80 °C
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C
ambient temperature
≤ 3,000 m above sea level at max. 50 °C
ambient temperature
Design, dimensions and weight
Immunity to interference EN 61000-6-2
Emission EN 61000-6-4
Degree of protection IP 30
MTBF (EN/IEC 61709, 40 °C) 136.65 years
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene (PPE
+PS plastic)
Weight 780 g
Dimensions (W x H x D) 60 x 125 x 124 mm
Installation options Installation on a DIN rail
Installation on an S7-300 standard rail
Wall mounting
Switching properties
Technical specifications
8.2 SCALANCE X106-1
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 47
Technical specifications
Aging time 30 seconds
Max. number of learnable MAC ad‐
dresses
2048
Response to LLDP frames Blocking
Response to spanning tree BPDU
frames
Forwarding
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
Maximum frame size 1536 bytes
Forwarding of PRP frames (Parallel
Redundancy Protocol)
Yes
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
This means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.
Optical connectors
Quantity 2
Connectors
The attachment to Industrial Ethernet uses ST/
BFOC connector technology (Straight Tip/Bayo‐
net Fiber Optic Connector).
Properties
Transmission mode 100Base-FX complying with IEEE 802.3
Transmission rate 100 Mbps (Fast Ethernet)
Transmission medium Multimode fiber-optic cable
Light source LED/Class1-LASER "Eye safe"
Technical specifications
8.2 SCALANCE X106-1
SCALANCE X-100
48 Operating Instructions, 02/2019, A2B00060666-10
Properties
Wavelength 1300 nm
Cable length (max.) *) At 50 µm fiber core diameter 3 km
At 62.5 µm fiber core diameter 3 km
Transmitter output (optical) Minimum At 50 μm -23 dBm
At 62.5 μm -19 dBm
Maximum -14 dBm
Receiver input Sensitivity min. -32 dBm
Input power max. -3 dBm
*) Depending on the cable used:
If you are using at least OM1 fibers (attenuation ≤ 1.5 dB/km, bandwidth length product ≥
500 MHz*km), you can reach a cable length of up to 3 km.
When are using fibers with attenuation values ≤ 1 dB/km, you can reach a cable length of
up to 5 km.
You can find additional information in the "Industrial Ethernet / PROFINET Passive network
components" System Manual, see also section "Introduction", paragraph "Additional
documentation".
8.3 SCALANCE X108
Table 8-3 Technical specifications of the SCALANCE X108
Technical specifications
Order number
SCALANCE X108 6GK5108‑0BA00‑2AA3
Connection to Industrial Ethernet
Number 8
Design RJ-45 jacks with MDI‑X pinning
Properties Half / full duplex
Transmission speed 10/100 Mbps
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 to 85 m Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 to 100 m Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Electrical data
Technical specifications
8.3 SCALANCE X108
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 49
Technical specifications
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
(SELV)
Rated voltage 24 VDC
Design 4-terminal plug-in block
Signaling contact Current max. 100 mA
Rated voltage 24 VDC
Design 2-pin plug-in terminal block
Current consumption Typical 140 mA
Power loss at 24 VDC Typical 3.36 W
Overvoltage protection at input PTC resettable fuse (0.6 A / 60 V)
Permitted ambient conditions
Ambient temperature During operation -20 °C to +70 °C
During storage -40 °C to +80 °C
During transportation -40 °C to +80 °C
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C
ambient temperature
≤ 3,000 m above sea level at max. 50 °C
ambient temperature
Design, dimensions and weight
Immunity to interference EN 61000-6-2
Emission EN 61000-6-4
Degree of protection IP 30
MTBF (EN/IEC 61709, 40 °C) 139.83 years
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene (PPE
+PS plastic)
Weight 780 g
Dimensions (W x H x D) 60 x 125 x 124 mm
Installation options Installation on a DIN rail
Installation on an S7-300 standard rail
Wall mounting
Switching properties
Aging time 30 seconds
Max. number of learnable MAC ad‐
dresses
2048
Response to LLDP frames Blocking
Response to spanning tree BPDU
frames
Forwarding
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
Technical specifications
8.3 SCALANCE X108
SCALANCE X-100
50 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications
Maximum frame size 1536 bytes
Forwarding of PRP frames (Parallel
Redundancy Protocol)
Yes
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
This means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.
8.4 SCALANCE X108PoE
Table 8-4 Technical specifications of the SCALANCE X108PoE
Technical specifications
Order number
SCALANCE X108PoE 6GK5108‑0PA00‑2AA3
Connection to Industrial Ethernet
Number 8
Design RJ-45 jacks with MDI‑X pinning
Properties Half / full duplex
Transmission speed 10/100 Mbps
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 to 85 m Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 to 100 m Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Technical specifications
8.4 SCALANCE X108PoE
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 51
Technical specifications
Electrical data
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
(SELV)
Rated voltage 24 VDC
Design 4-terminal plug-in block
Signaling contact Current max. 100 mA
Rated voltage 24 VDC
Design 2-pin plug-in terminal block
Current consumption Typical 1700 mA
Power loss at 24 VDC Typical 10.0 W
Overvoltage protection at input Fuse slow (4 A / 125 V)
Permitted ambient conditions
Ambient temperature During operation -20 °C to +60 °C
During storage -40 °C to +80 °C
During transportation -40 °C to +80 °C
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C
ambient temperature
≤ 3,000 m above sea level at max. 50 °C
ambient temperature
Design, dimensions and weight
Immunity to interference EN 61000-6-2
Emission EN 61000-6-4
Degree of protection IP 30
MTBF (EN/IEC 61709, 40 °C) 61.64 years
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene (PPE
+PS plastic)
Weight 550 g
Dimensions (W x H x D) 40 x 125 x 124 mm
Installation options Installation on a DIN rail
Installation on an S7-300 standard rail
Wall mounting
Switching properties
Aging time 30 seconds
Max. number of learnable MAC ad‐
dresses
2048
Response to LLDP frames Blocking
Response to spanning tree BPDU
frames
Forwarding
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
Maximum frame size 1536 bytes
Technical specifications
8.4 SCALANCE X108PoE
SCALANCE X-100
52 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications
Forwarding of PRP frames (Parallel
Redundancy Protocol)
Yes
PoE properties
PoE standard 802.3af
Performance maximum 15.4 W
Note
As of an ambient temperature of 55 °C, there must be a clearance of 40 mm to neighboring
devices on both sides.
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
This means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.
8.5 SCALANCE X112-2
8.5.1 SCALANCE X112-2
Table 8-5 Technical specifications of the SCALANCE X112-1
Technical specifications
Order number
SCALANCE X112-2 6GK5112-2BB00-2AA3
Connection to Industrial Ethernet
Number 12
Design RJ-45 jacks with MDI‑X pinning
Properties Half / full duplex
Transmission speed 10/100 Mbps
Technical specifications
8.5 SCALANCE X112-2
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 53
Technical specifications
Optical connectors
Number 2
Design BFOC sockets
Properties Full duplex to 100 Base-FX
Transmission speed 100 Mbps
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 to 85 m Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 to 100 m Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Optical parameters
Cable type Multimode glass FO cable, cable cross sections 62.5/125 μm and 50/125 μm
Permitted cable length (glass FO ca‐
ble)
Cable cross-section Permitted cable length
62.5/125 μm
50/125 μm
0 to 4000 m
0 to 5000 m
Attenuation ≤ 1 dB/km at 1300 nm
1200 MHz x km at 1300 nm
6 dB max. permitted FO cable attenuation with
3 dB link power margin
Electrical data
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
(SELV)
Rated voltage 24 VDC
Design 4-terminal plug-in block
Signaling contact Current max. 100 mA
Rated voltage 24 VDC
Design 2-pin plug-in terminal block
Current consumption Typical 215 mA
Power loss at 24 VDC Typical 5.16 W
Permitted ambient conditions
Ambient temperature During operation -10 °C to +70 ℃
During storage -40 ℃ to +80 ℃
During transportation -40 ℃ to +80 ℃
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C
ambient temperature
≤ 3,000 m above sea level at max. 50 °C
ambient temperature
Design, dimensions and weight
Technical specifications
8.5 SCALANCE X112-2
SCALANCE X-100
54 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications
Immunity to interference EN 61000-6-2
Emission EN 61000-6-3
Degree of protection IP 30
MTBF (EN/IEC 61709, 40 °C) 61.3 years
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene (PPE
+PS plastic)
Weight 1100 g
Dimensions (W x H x D) 120 x 125 x 124 mm
Installation options Installation on a DIN rail
Installation on an S7-300 standard rail
Wall mounting
Switching properties
Aging time 30 seconds
Max. number of learnable MAC ad‐
dresses
2048
Response to LLDP frames Blocking
Response to spanning tree BPDU
frames
Forwarding
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
Maximum frame size 1536 bytes
Forwarding of PRP frames (Parallel
Redundancy Protocol)
Yes
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
This means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.
Technical specifications
8.5 SCALANCE X112-2
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 55
Optical connectors
Quantity 2
Connectors
The attachment to Industrial Ethernet uses ST/
BFOC connector technology (Straight Tip/Bayo‐
net Fiber Optic Connector).
Properties
Transmission mode 100Base-FX complying with IEEE 802.3
Transmission rate 100 Mbps (Fast Ethernet)
Transmission medium Multimode fiber-optic cable
Light source LED/Class1-LASER "Eye safe"
Wavelength 1300 nm
Cable length (max.) *) At 50 µm fiber core diameter 3 km
At 62.5 µm fiber core diameter 3 km
Transmitter output (optical) Minimum At 50 μm -23 dBm
At 62.5 μm -19 dBm
Maximum -14 dBm
Receiver input Sensitivity min. -32 dBm
Input power max. -3 dBm
*) Depending on the cable used:
If you are using at least OM1 fibers (attenuation ≤ 1.5 dB/km, bandwidth length product ≥
500 MHz*km), you can reach a cable length of up to 3 km.
When are using fibers with attenuation values ≤ 1 dB/km, you can reach a cable length of
up to 5 km.
You can find additional information in the "Industrial Ethernet / PROFINET Passive network
components" System Manual, see also section "Introduction", paragraph "Additional
documentation".
8.6 SCALANCE X116
Table 8-6 Technical specifications of the SCALANCE X116
Technical specifications
Order number
SCALANCE X116 6GK5116‑0BA00‑2AA3
Connection to Industrial Ethernet
Number 16
Technical specifications
8.6 SCALANCE X116
SCALANCE X-100
56 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications
Design RJ-45 jacks with MDI‑X pinning
Properties Half / full duplex
Transmission speed 10/100 Mbps
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 to 85 m Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 to 100 m Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Electrical data
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
(SELV)
Rated voltage 24 VDC
Design 4-terminal plug-in block
Signaling contact Current max. 100 mA
Rated voltage 24 VDC
Design 2-pin plug-in terminal block
Current consumption Typical 185 mA
Power loss at 24 VDC Typical 4.40 W
Permitted ambient conditions
Ambient temperature During operation -20 ℃ to +70 ℃
During storage -40 ℃ to +80 ℃
During transportation -40 ℃ to +80 ℃
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 °C
ambient temperature
≤ 3,000 m above sea level at max. 50 ℃
ambient temperature
Design, dimensions and weight
Immunity to interference EN 61000-6-2
Emission EN 61000-6-3
Degree of protection IP 30
MTBF (EN/IEC 61709, 40 °C) 61.3 years
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene (PPE
+PS plastic)
Weight 1100 g
Dimensions (W x H x D) 120 x 125 x 124 mm
Technical specifications
8.6 SCALANCE X116
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 57
Technical specifications
Installation options Installation on a DIN rail
Installation on an S7-300 standard rail
Wall mounting
Switching properties
Aging time 30 seconds
Max. number of learnable MAC ad‐
dresses
2048
Response to LLDP frames Blocking
Response to spanning tree BPDU
frames
Forwarding
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
Maximum frame size 1536 bytes
Forwarding of PRP frames (Parallel
Redundancy Protocol)
Yes
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
This means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.
8.7 SCALANCE X124
Table 8-7 Technical specifications of the SCALANCE X124
Technical specifications
Order number
SCALANCE X124 6GK5124‑0BA00‑2AA3
Connection to Industrial Ethernet
Number 24
Technical specifications
8.7 SCALANCE X124
SCALANCE X-100
58 Operating Instructions, 02/2019, A2B00060666-10
Technical specifications
Design RJ-45 jacks with MDI‑X pinning
Properties Half / full duplex
Transmission speed 10/100 Mbps
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
0 to 85 m Max. 85 m IE FC TP Marine/Trailing Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing Cable + 10 m TP Cord via IE FC RJ45 Outlet
0 to 100 m Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
Electrical data
Power supply Voltage range 18 to 32 VDC Safe Extra Low Voltage
(SELV)
Rated voltage 24 VDC
Design 4-terminal plug-in block
Signaling contact Current max. 100 mA
Rated voltage 24 VDC
Design 2-pin plug-in terminal block
Current consumption Typical 200 mA
Power loss at 24 VDC Typical 4.80 W
Permitted ambient conditions
Ambient temperature During operation -20 ℃ to +70 ℃
During storage -40 ℃ to +80 ℃
During transportation -40 ℃ to +80 ℃
Relative humidity During operation ≤ 95 % no condensation
Operating altitude During operation ≤ 2,000 m above sea level at max. 56 ℃
ambient temperature
≤ 3,000 m above sea level at max. 50 ℃
ambient temperature
Design, dimensions and weight
Immunity to interference EN 61000-6-2
Emission EN 61000-6-3
Degree of protection IP 30
MTBF (EN/IEC 61709, 40 °C) 49.3 years
Housing material Basic housing Die cast aluminum, powder coated
Front cover Polyphenylene ether + polystyrene (PPE
+PS plastic)
Weight 1500 g
Dimensions (W x H x D) 180 x 125 x 124 mm
Technical specifications
8.7 SCALANCE X124
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 59
Technical specifications
Installation options Installation on a DIN rail
Installation on an S7-300 standard rail
Wall mounting
Switching properties
Aging time 30 seconds
Max. number of learnable MAC ad‐
dresses
2048
Response to LLDP frames Blocking
Response to spanning tree BPDU
frames
Forwarding
CoS acc. to IEEE 802.1Q Yes
QoS priority queues 4
Maximum frame size 1536 bytes
Forwarding of PRP frames (Parallel
Redundancy Protocol)
Yes
Note
The number of SCALANCE X Industrial Ethernet switches connected in a line influences the
frame delay time.
When a frame passes through devices of the SCALANCE X-100 product line, it is delayed by
the store and forward function of the switch
with a 64 byte frame length by approx. 10 microseconds (at 100 Mbps)
with a 1500 byte frame length by approx. 130 microseconds (at 100 Mbps)
This means that the more devices of the SCALANCE X-100 product line, the frame passes
through, the longer the frame delay.
Note
Temperature code for c-UL-us for hazardous locations, FM and ATEX Zone 2
You will find the temperature code "T.." or the maximum ambient temperature "Ta: .." on the
type plate.
Technical specifications
8.7 SCALANCE X124
SCALANCE X-100
60 Operating Instructions, 02/2019, A2B00060666-10
8.8 Mechanical stability (in operation)
Mechanical stability (in operation)
Device DIN EN 60068-2-6 os‐
cillation
DIN EN 60068-2-6 os‐
cillation
DIN EN 60068-2-6 os‐
cillation
DIN EN 60068-2-29
permanent shock
DIN EN 60068-2-29
permanent shock
10 - 58 Hz: 0.075 mm
58 - 500 Hz: 10 m/s2
10 cycles
10 - 58 Hz: 0.15 mm
58 - 500 Hz: 20 m/s2
10 cycles
5 - 8.51 Hz: 3.5 mm
8.51 - 500 Hz: 10 m/s2
10 cycles
100 m/s2, 16 ms dura‐
tion
100 shocks per axis
250 m/s2, 6 ms duration
1000 shocks per axis
X104-2
X106-1
X108
Device DIN EN
60068-2-6 vi‐
bration
DIN EN
60068-2-6 vi‐
bration
DIN EN
60068-2-6 vi‐
bration
DIN EN
60068-2-6 vi‐
bration ship
building
DIN EN
60068-2-27
shock
DIN EN
60068-2-29 per‐
manent shock
DIN EN
60068-2-29 per‐
manent shock
2 - 13.2 Hz: 2.0
mmPP
13.2 - 100 Hz: 7
m/s2
1 sweep
5 - 8.51 Hz: 7.0
mmPP
8.51 - 500 Hz:
10 m/s2
1 oct/min, 20
sweeps
5 - 8.51 Hz: 7.0
mmPP
8.51 - 150 Hz:
10 m/s2
1 oct/min, 10 cy‐
cles
2 - 25 Hz: 3.2
mmPP
25 - 100 Hz: 40
m/s2
1 sweep
150 m/s2, 11 ms
duration
6 shocks per ax‐
is
250 m/s2, 6 ms
duration
1000 shocks
per axis
100 m/s2, 16 ms
duration
100 shocks per
axis
X108PoE
Device DIN EN 60068-2-6 oscillation DIN EN 60068-2-27 shock
5 - 8.51 Hz: 3.5 mm
8.51 - 500 Hz: 10 m/s2
1 oct/min, 10 cycles
150 m/s2, 16 ms duration
6 shocks per axis
X112-2
X116
X124
Technical specifications
8.8 Mechanical stability (in operation)
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 61
Technical specifications
8.8 Mechanical stability (in operation)
SCALANCE X-100
62 Operating Instructions, 02/2019, A2B00060666-10
Dimension drawings 9


Figure 9-1 Dimension drawing, rear of the SCALANCE X104-2, X106-1, X108, X108PoE
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 63
Figure 9-2 Dimension drawing, rear of the SCALANCE X116, X112-2
Dimension drawings
SCALANCE X-100
64 Operating Instructions, 02/2019, A2B00060666-10



Figure 9-3 Dimension drawing, rear of the SCALANCE X124
Dimension drawings
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 65




Figure 9-4 Dimension drawing, side view
150
76
Dimension drawings
SCALANCE X-100
66 Operating Instructions, 02/2019, A2B00060666-10
Figure 9-5 Dimension drawing, bending radii
Dimension drawings
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 67
Dimension drawings
SCALANCE X-100
68 Operating Instructions, 02/2019, A2B00060666-10
Certifications and approvals 10
The SIMATIC NET products described in these Operating Instructions have the approvals
listed below.
Note
Issued approvals on the type plate of the device
The specified approvals apply only when the corresponding mark is printed on the product. You
can check which of the following approvals have been granted for your product by the markings
on the type plate.
Current approvals on the Internet
You will find the current approvals for the product on the Internet pages of Siemens Industry
Online Support (https://support.industry.siemens.com/cs/ww/en/ps/15273/cert).
Notes for the manufacturers of machines
The devices are not machines in the sense of the EC Machinery Directive. There is therefore
no declaration of conformity relating to the EC Machinery Directive 2006/42/EC for these
devices.
If the devices are part of the equipment of a machine, they must be included into the EU
declaration of conformity procedure by the manufacturer of the machine.
See also
SIMATIC NET Industrial Ethernet TP and Fiber Optic Networks (http://
support.automation.siemens.com/WW/view/en/8763736)
EC declaration of conformity
The SIMATIC NET products described in these operating instructions meet the requirements
and safety objectives of the following EC directives and comply with the harmonized European
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 69
standards (EN) which are published in the official documentation of the European Union and
here.
2014/34/EU (ATEX explosion protection directive)
Directive of the European Parliament and the Council of 26 February 2014 on the
approximation of the laws of the member states concerning equipment and protective
systems intended for use in potentially explosive atmospheres, official journal of the EU L96,
29/03/2014, pages. 309-356
2014/30/EU (EMC)
EMC directive of the European Parliament and of the Council of February 26, 2014 on the
approximation of the laws of the member states relating to electromagnetic compatibility;
official journal of the EU L96, 29/03/2014, pages. 79-106
2011/65/EU (RoHS)
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of
the use of certain hazardous substances in electrical and electronic equipment, official
journal of the EC L174, 01/07/2011, pages 88-110
You will find the EC declaration of conformity for these products on the Internet pages of
Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/15273/
cert).
The EC Declaration of Conformity is available for all responsible authorities at:
Siemens Aktiengesellschaft
Division Process Industries and Drives
Process Automation
DE-76181 Karlsruhe
Germany
ATEX (explosion protection directive)
WARNING
Risk of explosion in hazardous areas
When using SIMATIC NET products in hazardous area zone 2, make absolutely sure that the
associated conditions in the following document are adhered to:
"SIMATIC NET Product Information Use of subassemblies/modules in a Zone 2 Hazardous
Area".
You will find this document here:
On the data medium that ships with some products:
Product CD / product DVD
SIMATIC NET Manual Collection
On the Internet pages of Siemens Industry Online Support (https://
support.industry.siemens.com/cs/ww/en/view/78381013)
Certifications and approvals
SCALANCE X-100
70 Operating Instructions, 02/2019, A2B00060666-10
The SIMATIC NET products described in these operating instructions meet the requirements
of the EU directive 2014/34/EU "Equipment and Protective Devices for Use in Potentially
Explosive Atmospheres".
Note
Type of protection of the device
The devices are approved for various types of protection. You can find the type of protection of
your device and the ATEX certificate number on the nameplate.
Permitted types of protection
The following types of protection are possible:
nA
ATEX classification: II 3G Ex nA IIC T4 Gc
Certificate no.: KEMA 07ATEX0145 X
The products meet the requirements of the following standards:
EN 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
nA [op is]
ATEX classification: II 3 (2) G Ex nA [op is Gb] IIC T4 Gc
Certificate no.: DEKRA 11ATEX0060 X
The products meet the requirements of the following standards:
EN 60079-28 (Explosive atmospheres - Part 28: Protection of equipment and
transmission systems using with optical radiation)
EN 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
ec
ATEX classification: II 3 G Ex ec IIC T4 Gc
Certificate no.: DEKRA 18ATEX0025 X
The products meet the requirements of the following standards:
EN 60079-7 (Explosive atmospheres - Part 7: Equipment protection through increased
safety "e")
EN 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
You will find the current versions of the standards in the currently valid ATEX certificates.
Certifications and approvals
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 71
IECEx
The SIMATIC NET products described in these operating instructions meet the requirements
of explosion protection according to IECEx.
Note
Type of protection of the device
The devices are approved for various types of protection. You can find the type of protection of
your device and the IECEx certificate number on the nameplate.
Permitted types of protection
The following types of protection are possible:
nA
IECEx classification: Ex nA IIC T4 Gc
Certificate no.: DEK 14.0025X
The products meet the requirements of the following standards:
IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
nA [op is]
IECEx classification: Ex nA [op is Gb] IIC T4 Gc
Certificate no.: DEK 14.0026X
The products meet the requirements of the following standards:
IEC 60079-28 (Explosive atmospheres - Part 28: Protection of equipment and
transmission systems using with optical radiation)
IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
ec
IECEx classification: Ex ec IIC T4 Gc
Certificate no.: DEK 18.0017X
The products meet the requirements of the following standards:
IEC 60079-7 (Explosive atmospheres - Part 7: Equipment protection through increased
safety "e")
IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
You will find the current versions of the standards in the currently valid IECEx certificates.
Certifications and approvals
SCALANCE X-100
72 Operating Instructions, 02/2019, A2B00060666-10
Note for devices with CLASS 1 LASER
Important note on products certified according to Type Examination Certificate KEMA
07ATEX0145 X as of Issue 95 / DEKRA 18ATEX0025X and IECEx Certificate of Conformity
DEK 14.0025X as of Issue 43 / DEK 18.0017X and containing Class 1 optical radiation sources.
Note
CLASS 1 LASER
The device contains optical radiation sources which comply with the limits of Class 1 according
to IEC 60825-1. Fiber-optic cables connected to these optical radiation sources may therefore
be routed either to or through hazardous areas requiring Category 2G, 3G, 2D or 3D
equipment.
EMC directive (electromagnetic compatibility)
The SIMATIC NET products described in these operating instructions meet the requirements
of EU directive 2014/30/EU "Electromagnetic Compatibility" (EMC Directive).
Applied standards:
EN 61000‑6‑2 Electromagnetic compatibility (EMC) - Part 6-2: Generic standards -
Immunity for industrial environments
EN 61000‑6‑4 Electromagnetic compatibility (EMC) - Part 6-4: Generic standards -
Emission standard for industrial environments
You will find the current versions of the standards in the currently valid EC declaration of
conformity.
RoHS
The SIMATIC NET products described in these operating instructions meet the requirements
of the EC directive 2011/65/EC for the restriction of the use of certain hazardous substances in
electrical and electronic equipment:
Applied standard:
EN 50581
FM
The product meets the requirements of the standards:
Factory Mutual Approval Standard Class Number 3611
FM Hazardous (Classified) Location Electrical Equipment:
Non Incendive / Class I / Division 2 / Groups A,B,C,D / T4 and
Non Incendive / Class I / Zone 2 / Group IIC / T4
cULus Approval for Information Technology Equipment
cULus Listed I. T. E.
Certifications and approvals
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 73
Underwriters Laboratories Inc. complying with
UL 60950-1 (Information Technology Equipment)
CSA C22.2 No. 60950-1-03
Report no. E115352
cULus Approval Hazardous Location
cULus Listed I. T. E. FOR HAZ. LOC.
Underwriters Laboratories Inc. complying with
UL 60950-1 (Information Technology Equipment)
ANSI/ISA 12.12.01-2007
CSA C22.2 No. 213-M1987
Approved for use in
Cl. 1, Div. 2, GP A, B, C, D T4
Cl. 1, Zone 2, GP IIC T4
Report no. E240480
E1
The SCALANCE X108 switch meets the requirements of the directive ECE-G 95/54/EC.
Test number 10 R - 034734
e1
The SCALANCE X108 IE switch meets the requirements of the Directive 72/245/EEC in the
form 2006/96/EC "Electromagnetic Compatibility".
Test number 03 4734
Note for Australia - RCM
The product meets the requirements of the RCM standard.
Applied standards:
AS/NZS CISPR11 (Industrial, scientific and medical equipment - Radio-frequency
disturbance characteristics - Limits and methods of measurement).
EN 61000-6-4 Electromagnetic compatibility (EMC) - Part 6-4: Generic standards -
Emission standard for industrial environments
You will find the current versions of the standards in the currently valid RCM SDoCs (Self-
Declaration of Conformity).
MSIP 요구사항 ‑ For Korea only
A 기기(업무용 방송통신기자재)
Certifications and approvals
SCALANCE X-100
74 Operating Instructions, 02/2019, A2B00060666-10
기기는 업무용(A) 전자파 적합기기로서 판매자 또는 사용자는 점을 주의하시기 바라며,
가정 외의 지역에서 사용하는것을 목적으로 합니다.
Marking for the customs union
EAC (Eurasian Conformity)
Eurasian Economic Union of Russia, Belarus, Armenia, Kazakhstan and Kyrgyzstan
Declaration of conformity according to the technical regulations of the customs union (TR ZU)
FDA and IEC marking
The following devices meet the FDA and IEC requirements listed below:
Device CLASS 1 LASER Product
SCALANCE X104‑2
SCALANCE X106‑1
SCALANCE X108 -
SCALANCE X108PoE -
SCALANCE X112-2
SCALANCE X116 -
SCALANCE X124 -
&RPSOLHVZLWK&)5DQG&/$66/$6(5352'8&7)'$,(&
Figure 10-1 FDA and IEC marking
CAUTION
Use of controls or adjustments or performance of procedures other than those specified
herein may result in hazardous radiation exposure.
Certifications and approvals
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 75
Installation guidelines
The devices meet the requirements if you adhere to the installation and safety instructions
contained in this documentation and in the following documentation when installing and
operating the devices.
"Industrial Ethernet / PROFINET Industrial Ethernet" System Manual (https://
support.industry.siemens.com/cs/ww/en/view/27069465)
"Industrial Ethernet / PROFINET - Passive Network Components" System Manual (https://
support.industry.siemens.com/cs/ww/en/view/84922825)
"EMC Installation Guidelines" configuration manual (https://support.industry.siemens.com/
cs/ww/en/view/60612658)
WARNING
Personal injury and property damage can occur
The installation of expansions that are not approved for SIMATIC NET products or their target
systems may violate the requirements and regulations for safety and electromagnetic
compatibility.
Only use expansions that are approved for the system.
Note
The test was performed with a device and a connected communications partner that also meets
the requirements of the standards listed above.
When operating the device with a communications partner that does not comply with these
standards, adherence to the corresponding values cannot be guaranteed.
Certifications and approvals
SCALANCE X-100
76 Operating Instructions, 02/2019, A2B00060666-10
Index
A
Accessories, 14
Approvals, 69
Article numbers, 13
Auto polarity exchange, 24
Autonegotiation, 24
B
Bending radii, 67
BFOC socket
ST socket, 17
C
CE mark, 69
Components of the product, 14
Connection to Industrial Ethernet, 43, 46, 49, 51, 53,
56, 58
Connector pinout, 23
SCALANCE X108 PoE, 23
D
Design, dimensions and weight, 44, 47, 50, 52, 54,
57, 59
Dimension drawing, 63
Display, 41
Drilled holes, 66
E
E1, 74
Electrical data, 44, 47, 49, 52, 54, 57, 59
Error
Far-end fault, 41
LED display when voltage drops, 41
Link display, 41
ESD directives, 8
F
Fault mask
Changing the setting, 27
Error/fault, 27
Factory setting, 27
FO port, 25
G
Glossary, 6
Grounding, 38
Installation on a DIN rail, 38
S7 standard rail, 38
Wall mounting, 38
I
IE FC RJ-45 Plug 180, 39
Installation, 39
Plugging in, 40
Pulling, 40
Installation
Installation on a DIN rail, 31
Installation on a standard rail, 33
Types of installation, 31
L
LEDs, 26
Fault LED (red LED), 26
Port LEDs (green/yellow LEDs), 26
Power LED (green LED), 26
M
MDI / MDI-X autocrossover function, 24
N
Network topology, 11
Electrical star topology, 12
Electrical/optical star topology, 12
O
Optical connectors, 43, 46, 54
Optical parameters, 43, 47, 54
Order numbers, 43, 46, 49, 51, 53, 56, 58
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 77
P
Permitted ambient conditions, 44, 47, 50, 52, 54, 57,
59
Permitted cable lengths, 24, 43, 46, 49, 51, 54, 57,
59
Possible attachments
SCALANCE X108, 17
Possible connections
SCALANCE X104-2, 16
SCALANCE X108PoE, 19
SCALANCE X112-2, 20
SCALANCE X116, 21
SCALANCE X106-1, 17
SCALANCE X124, 22
Power over Ethernet (PoE) function, 19
Power supply, 36
Product properties, 15
R
Reduced voltage, 41
RJ-45, 23
S
Safety notices
for installation, 29
general, 9
Use in hazardous areas, 9, 29, 35
when connecting up, 35
SCALANCE X104-2
Connection to Industrial Ethernet, 43
Design, dimensions and weight, 44
Electrical data, 44
Optical connectors, 43
Optical parameters, 43
Order numbers, 43
Permitted ambient conditions, 44
Permitted cable lengths, 43
Switching properties, 44
SCALANCE X108PoE
Connection to Industrial Ethernet, 51
Design, dimensions and weight, 52
Electrical data, 52
Order numbers, 51
Permitted ambient conditions, 52
Permitted cable lengths, 51
PoE properties, 53
Switching properties, 52
SCALANCE X112-2
Connection to Industrial Ethernet, 53
Design, dimensions and weight, 54
Electrical data, 54
Optical connectors, 54
Optical parameters, 54
Order numbers, 53
Permitted ambient conditions, 54
Permitted cable lengths, 54
Switching properties, 55
SCALANCE X116
Connection to Industrial Ethernet, 56
Design, dimensions and weight, 57
Electrical data, 57
Order numbers, 56
Permitted ambient conditions, 57
Permitted cable lengths, 57
Switching properties, 58
SCALANCE X106-1
Connection to Industrial Ethernet, 46
Design, dimensions and weight, 47
Electrical data, 47
Optical connectors, 46
Optical parameters, 47
Order numbers, 46
Permitted ambient conditions, 47
Permitted cable lengths, 46
Switching properties, 47
SCALANCE X108
Connection to Industrial Ethernet, 49
Design, dimensions and weight, 50
Electrical data, 49
Order numbers, 49
Permitted ambient conditions, 50
Permitted cable lengths, 49
Switching properties, 50
SCALANCE X124
Connection to Industrial Ethernet, 58
Design, dimensions and weight, 59
Electrical data, 59
Order numbers, 58
Permitted ambient conditions, 59
Permitted cable lengths, 59
Switching properties, 60
SET button, 26
Function, 26
Side view, 66
Signaling contact, 37
SIMATIC NET glossary, 6
SIMATIC NET manual, 6
ST socket
BFOC socket, 16
Index
SCALANCE X-100
78 Operating Instructions, 02/2019, A2B00060666-10
Switching properties, 44, 47, 50, 52, 53, 55, 58, 60
System manual, 6, 30, 76
T
Technical specifications, 43, 46, 49, 51, 53, 56, 58
SCALANCE X104-2, 43
SCALANCE X108PoE, 51
SCALANCE X112-2, 53
SCALANCE X116, 56
SCALANCE X106-1, 46
SCALANCE X108, 49
SCALANCE X124, 58
TP ports, 23
Index
SCALANCE X-100
Operating Instructions, 02/2019, A2B00060666-10 79
Index
SCALANCE X-100
80 Operating Instructions, 02/2019, A2B00060666-10