Standard AC Output Modules
Features
Rugged construction
4000 volts of optical isolation between the field
devices and the control logic (transient)
Zero voltage turn-on and zero current turn-off
Description
AC output modules are used for controlling or switching AC
loads. Each module providesup to 4000 volts (transient) of
optical isolation between the field devices and the control
logic.
With the exception of the OAC5A5 module, all AC output
modules are equivalent to a single pole, single throw, normally
open contact (FORM A, SPST-NO, Make). The OAC5A5 is
equivalent to a single pole, single throw, normally closed
contact (FORM B, SPST-NC, Break). All AC output modules
feature zero voltage turn-on and zero current turn-off.
Typical uses and applications for AC output modules include
switching the following loads:
Relays
Solenoids
Motor starters
Heaters
Lamps or indicators
Part Numbers
Part Description
OAC5 AC Output 12–140 VAC, 5 VDC Logic
OAC5A AC Output 24–280 VAC, 5 VDC Logic
OAC5H* AC Output 24–280 VAC, 5 VDC Logic, higher
current ratin g
OAC5A5 AC Output 24–280 VAC, 5 VDC Logic, NC
OAC15 AC Output 12–140 VAC, 15 VDC Logic
OAC15A AC Output 24–280 VAC, 15 VDC Logic
OAC24 AC Output 12–140 VAC, 24 VDC Logic
OAC24A AC Output 24–280 VAC, 24 VDC Logic
OAC24H* AC Output 24–280 VAC, 24 VDC Logic, higher
current ratin g
* Not UL approved
OAC5 Module
Standard AC Output Modules
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2006–2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Standard AC Output Modules
PAGE
2
DATA SHEET
Form 449-120920
Specifications
General
Module Specifications
One Cycle Surge 80 amps peak
Peak Repetitive V olt age 500 Volts
Operating Ambient Temperature -30 to 70 °C
Isolation, Input-to-Output (Transient) 4,000 Vrms
Minimum Load Current 20 milliamps
Operating Frequency 25–65 Hz
Turn-on Time 1/2 cycle maximum-zero voltage
Turn-off Time 1/2 cycle maximum-zero current
DV/DT - Off-S tate 200 volts/microseconds
DV/DT - Commutating Snubbed for rated 0.5 power factor load
Output V oltage Drop Maximum Peak 1.6 volts
Off-State Leakage
@ Nominal Voltage - 60 Hz 5 milliamps rms
2.5 milliamps rms for O AC5A OAC15A,
and OAC24A @120 VAC
Units OAC5 OAC5A OAC5H OAC5A5
(NC) OAC15
3
OAC15A
3
OAC24
3
OAC24A
3
OAC24H
3
Line Voltage - Nominal VAC 120 240 240 120/240 120 240 120 240 240
Operating V oltage Range VAC 12–140 24–280 24–280 24–280 12–140 24–280 12–140 24–280 24–280
Current Rating
@ 45 °C A mbient
@ 70 °C A mbient amps
amps 3
2 3
2 4
2 3
2 3
2 3
2 3
2 3
2 4
2
UL Motor Load Rating amps 1.5 1.5 -- * 1.5 1.5 1.5 1.5 1.5 --
1
Logic Voltage - Nominal VDC 5 5 5 5 15 15 24 24 24
Logic Voltage Range (Vcc)
2
VDC 2.5
82.5
82.5
82.5
89
16 9
16 18
32 18
32 18
32
Logic Pickup Voltage
1
VDC 2.5 2.5 2.5 2.5 9 9 18 18 18
Logic Dropout V oltage VDC 1 1 1 1 1 1 1 1 1
Logic Input Current-@ Normal
Logic
Voltage (I
out
in schematic dia-
gram)
mA 12 12 12 12 15 15 18 18 18
Control Resistance
(R
c
in schematic diagram) Ohms 220 220 220 220 1K 1K 2.2K 2.2K 2.2K
1 Not UL approved
2 Module only
3 Not for use with Opto 22 brains
Standard AC Output Modules
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2006–2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Standard AC Output Modules
DATA SHEET
Form 449-120920
PAGE
3
Dimensions
Standard AC Output Modules
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2006–2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Standard AC Output Modules
PAGE
4
DATA SHEET
Form 449-120920
Connections
Schematics
More About Opto 22
www.opto22.com • Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Form 1335-110907
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Products
Opto 22 develops and manufactures reliable, flexible, easy-to-
use hardware and software products for industrial automation,
energy management, remote monitoring, and data
acquisition applications.
OptoEMU Energy Management System
The easy-to-use OptoEMU Sensor monitors electrical energy
use in your facility and delivers detailed, real-time data you
can see and analyze. The Sensor can monitor energy data from
pulsing meters, electrical panels or subpanels, and equipment.
View energy data online using a software service or
incorporate the data into your control system for complete
energy management.
SNAP PAC System
Designed to simplify the typically
complex process of selecting and
applying an automation system, the
SNAP PAC System consists of four
integrated components:
SNAP PAC controllers
PAC Project Software Suite
SNAP PAC brains
SNAP I/O
SNAP PAC Controllers
Programmable automation controllers (PACs) are
multifunctional, modular controllers based on open standards.
Opto 22 has been manufacturing PACs for over two decades.
The standalone SNAP PAC S-series and the rack-mounted
SNAP PAC R-series both handle a wide range of digital, analog,
and serial functions for data collection, remote monitoring,
process control, and discrete and hybrid manufacturing.
SNAP PACs are based on open Ethernet and Internet Protocol
(IP) standards, so you can build or extend a system easily,
without the expense and limitations of proprietary networks
and protocols.
PAC Project Software Suite
Opto 22’s PAC Project Software Suite provides full-featured,
cost-effective control programming, HMI (human machine
interface) development and runtime, OPC server, and
database connectivity software for your SNAP PAC System.
Control programming includes both easy-to-learn flowcharts
and optional scripting. Commands are in plain English;
variables and I/O point names are fully descriptive.
PAC Project Basic offers control and HMI tools and is free for
download on our website, www.opto22.com. PAC Project
Professional, available for separate purchase, adds
OptoOPCServer, OptoDataLink, options for controller
redundancy or segmented networking, and support for legacy
Opto 22 serial mistic I/O units.
SNAP PAC Brains
While SNAP PAC controllers provide central control and data
distribution, SNAP PAC brains provide distributed intelligence
for I/O processing and communications. Brains offer analog,
digital, and serial functions, including thermocouple
linearization; PID loop control; and optional high-speed digital
counting (up to 20 kHz), quadrature counting, TPO, and pulse
generation and measurement.
SNAP I/O
I/O provides the local connection to sensors and equipment.
Opto 22 SNAP I/O offers 1 to 32 points of reliable I/O per
module, depending on the type of module and your needs.
Analog, digital, and serial modules are all mixed on the
same mounting rack and controlled by the same processor
(SNAP PAC brain or rack-mounted controller).
Quality
Founded in 1974, Opto 22 has established a
worldwide reputation for high-quality products. All
are made in the U.S.A. at our manufacturing
facility in Temecula, California. Because we do
no statistical testing and each part is tested
twice before leaving our factory, we can
guarantee most solid-state relays and optically
isolated I/O modules for life.
Free Product Support
Opto 22’s California-based Product Support Group offers free,
comprehensive technical support for Opto 22 products. Our
staff of support engineers represents decades of training and
experience. Support is available in English and Spanish by
phone or email, Monday–Friday, 7 a.m. to 5 p.m. PST.
Additional support is always available on our website: how-to
videos, OptoKnowledgeBase, self-training guide,
troubleshooting and users guides, and OptoForums.
In addition, hands-on training is available for free at our
Temecula, California headquarters, and you can register online.
Purchasing Opto 22 Products
Opto 22 products are sold directly and through a worldwide
network of distributors, partners, and system integrators. For
more information, contact Opto 22 headquarters at 800-321-
6786 or 951-695-3000, or visit our website at
www.opto22.com.
www.opto22.com