0713 BU-SB13725 Page 1 of 3 Data Sheet # 1013
LIMITRON™ Class L
KLU — 600Vac, 601-4000A, Time-Delay Fuses
Description: Advanced protection Class L time-delay, current-
limiting fuses. Time-delay – 5 seconds (minimum) at 500% of
rated current.
Catalog Symbol: KLU-(amp)
Ratings:
Volts — 600Vac
Amps — 601-4000A*
IR — 200kA Vac RMS Sym.
* Use KRP-CL for current ratings from 225 to 600 amps.
Agency Infortmation:
CE, UL Listed, Std. 248-10, Class L, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.10, Class 1422-02, File 53787
RoHS Compliant
Catalog Numbers (amps)
KLU–601 KLU–1200 KLU–2500
KLU–650 KLU–1500 KLU–3000
KLU–700 KLU–1600 KLU–4000
KLU–800 KLU–1800
KLU–1000 KLU–2000
Carton Quantity and Weight
Amp Rating Carton Qty.
601-800 1
1000-1200 1
1500-1600 1
1800-2000 1
2500 1
3000 1
4000 1
Dimensions – in
Features:
• KLU Limitron general purpose copper link fuses
• Copper links result in a minimum 5 second time-delay at
500% ampere rating
• Current-limiting – provides component short-circuit
protection
• 200kA interrupting rating complies with NEC®Sections
110.9 and 230.65 in today’s large capacity systems
• Selective coordination (blackout prevention)
Recommended Fuse Blocks — 601 to 1200 Amps†
Catalog Numbers Poles
51215 1
51235 3
† No Agency listings available.
No reducers available.
1.75" 1.38"
0.81"
0.88"
1.75" 1.38"
0.88"
1.63"
0.75"
0.75"
0.75"
0.5"
2.75"
0.44"
2.38"
0.38"0.38"
2"
2.5"
2"
2.5" 3" 3.5"
3.5"
5"
4"
5"
4.75"
5.75"
10.75"
(± 0.09)
8.63"
(± 0.09)
6.75" 5.75"
All Slots and Holes
0.63" (± 0.03)
Terminals: Width (± 0.06), Thickness (± 0.03)
All other tolerances (± 0.02)
1000
to
1200A
601
to
800A
1500
to
1600A
1800
to
2000A
2500A 3000A
3500
to
4000A
6.75"