https://www.phoenixcontact.com/us/produkte/0915069
11.06.2012Page2/7
Thermomagnetic device circuit breaker-TMC 2 M1 120
10,0A-0915069
Technical data
Technical data
Nominal current IN 10 A
Nominal voltage UN 250 V AC
Nominal voltage UN 65 V DC
Ambient temperature (operation) -30 °C ... 60 °C
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 10
Conductor cross section stranded, with ferrule without plastic
sleeve min. 0.25 mm²
Conductor cross section stranded, with ferrule without plastic
sleeve max. 4 mm²
Conductor cross section stranded, with ferrule with plastic sleeve
min. 0.25 mm²
Conductor cross section stranded, with ferrule with plastic sleeve
max. 2.5 mm²
2 conductors with same cross section, solid min. 0.2 mm²
2 conductors with same cross section, solid max. 0.75 mm²
2 conductors with same cross section, stranded min. 0.2 mm²
2 conductors with same cross section, stranded max. 0.75 mm²
2 conductors with same cross section, stranded, ferrules without
plastic sleeve, min. 0.25 mm²
2 conductors with same cross section, stranded, ferrules without
plastic sleeve, max. 1 mm²
2 conductors with same cross section, stranded, TWIN ferrules
with plastic sleeve, min. 0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules
with plastic sleeve, max. 2.5 mm²
Connection method Screw connection
Stripping length 12 mm
Internal cylindrical gage A3
Screw thread M3
Tightening torque, min 0.6 Nm
Tightening torque max 0.8 Nm
Classifications
eclass
eCl@ss 4.0 27141116
eCl@ss 4.1 27141116