https://www.phoenixcontact.com/us/products/2902993
03/22/2021Page4/9
Power supply unit-UNO-PS/1AC/24DC/100W-2902993
Technical data
Connection data, output
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3
Standards
EMC requirements for noise immunity EN61000-6-1
EN61000-6-2
EMC requirements for noise emission EN61000-6-3
EN61000-6-4
Standard - Safety of transformers EN61558-2-16
Standard - Electrical safety IEC62368-1/VDE0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN50178/VDE0160 (PELV)
Standard – Safety extra-low voltage IEC62368-1 (SELV) und EN60204-1 (PELV)
Standard - Safe isolation DINVDE0100-410
Standard – Limitation of mains harmonic currents EN61000-3-2
Mains variation/undervoltage EN61000-4-11
Conformance/approvals
UL approvals UL/C-UL listed UL 508
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
T4 (Hazardous Location)
UL/C-UL Recognized UL 60950-1
CSA CAN/CSA-C22.2 No.60950-1-07
CSA-C22.2 No.107.1-01
CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4
(Hazardous Location)
EMC data
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Electromagnetic HF field EN61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m