F-MS 12 ST Order No.: 2817990
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2817990
PHOENIX CONTACT Deutschland GmbH Page 3 / 6
http://www.phoenixcontact.de Feb 4, 2011
Lightning test current (10/350) µs, charge 6 As
Lightning test current (10/350) µs, peak value limp 12 kA
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE) ≤ 1.5 kV
Insulation resistance Riso: > 1 GΩ
Protection level Up≤ 1.5 kV
Protection level UP (N-PE) ≤ 1.5 kV
Residual voltage ≤ 150 V (at 5 kA)
Residual voltage (N-PE) ≤ 150 V (at 5 kA)
≤ 400 V
≤ 250 V (at 10 kA)
≤ 100 V (at 3 kA)
Response time ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Follow current quenching capacity If (N-PE) 100 A (260 V)
Connection, protective circuit
Connection type IN FLASHTRAB/VALVETRAB plug-in system
Connection type OUT FLASHTRAB/VALVETRAB plug-in system
Environmental conditions
Standards/regulations IEC 61643-1
EN 61643-11/A11
Certificates / Approvals
Certification CB, CCA, CUL, GL, GOST, KEMA, OEVE, UL
Accessories
Item Designation Description
Marking
1051993 B-STIFT Marker pen, for manual labeling of unprinted Zack strips, smear-
proof and waterproof, line thickness 0.5 mm