1
Thermal (T- and TA-Line) T11-611
www.schurter.com/PG17_18_19
Circuit Breakers
Circuit Breaker for Equipment thermal, Snap-in type, Reset type, Quick connect terminals
Description
- Snap-in version
- Thermal circuit breaker
- 1-pole
- Reset type
- Quick connect terminals 6.3 x 0.8 mm
Unique Selling Proposition
- Compact design
- Positively trip-free release
- Available with cover
- Different mounting possibilities
Standards
- IEC 60934
- UL 1077
- CSA C22.2 No. 235
- GB 17701
Applications
- Power tools
- Household Equipment
- Power supplies and chargers
- Industrial appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information,
Approvals, CE declaration of conformity, RoHS, CHINA-RoHS, REACH,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product, Product News
Technical Data
Rated Voltage AC 240 V; 50/60 Hz
Rated Voltage DC 48 V
Rated current range AC 0.05 - 16 A
Conditional short circuit ca-
pacity
IEC: Inc, PC1, AC 240 V: 2 kA
Short circuit capacity Icn at In < 6.5 A/240 VAC : 8 x In
at In 6.5 A/240 VAC : 96 A
Degree of Protection from front side IP 40 acc. to IEC 60529
Dielectric Strength 50 Hz: > 1.5 kV
Impulse 1.2/50 μs: > 2.5 kV
Insulation resistance 500 VDC > 100 MΩ
Endurance typical 2 x Ir: 500 switching cycles
Endurance minimum Reset type
AC : 2 x Ir , cos φ 0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
50 switching cycles
Overload IEC: min. 40 trips
@ 6 x Ir, cos φ 0.6
UL / CSA: min. 50 trips
@ 1.5 x Ir, cos φ 0.75
Ambient temperature -5 °C to 60 °C
Vibration Resistance ± 1.5 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Fc
5 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Shock Resistance 100 G / 6 ms
acc. to IEC 60068-2-27, test Ea
Tripping Type Thermal
Actuation type Reset type
Weight ca. 10 g
2
Thermal (T- and TA-Line)
T11-611 www.schurter.com/PG17_18_19
Circuit Breakers
Dimension
21.6
34.7
15.2
2
13.5
11.0
25
12 13
14
3.6
9.2
11
48.2
6.3
42
4
Ø 4
Ø 4
3.6
T11-611N
T11-611 <7,5A T11-611 <7,5A
3
12
b
11.3
a (0,8–3,0 mm)
ab
0,
82
1,9
1,
02
2,0
1,
52
2,1
2,
02
2,3
3,
02
2,6
Diagrams
Rated current 7,5 A
1
2
Rated current >7,5 A
1
3
Shunt terminal T11-...N 6,5 A
1
32
3
Thermal (T- and TA-Line) T11-611
www.schurter.com/PG17_18_19
Circuit Breakers
Typical internal resistance
Rated Current [A] Internal Resistance []
0.05 380.000
0.50 5.200
1.00 1.350
2.00 0.300
3.00 0.130
4.00 0.080
5.00 0.040
6.00 0.040
7.00 0.020
8.00 0.012
9.00 0.012
10.00 0.011
11.00 0.0095
12.00 0.0095
13.00 0.0085
14.00 0.0085
15.00 0.0075
16.00 0.0075
Time-Current-Curves
Time in Seconds
10`000
1,05
60
1085432
1,35
2`000
1`000
500
200
100
50
20
10
5
2
1
0,5
0,3
0,2
0,1
[ sec ][ min ]
30
20
10
5
1
< 6,5 A
> 6,5 A
Multiple of Rated Current In
Reference Temperature +23°
4
Thermal (T- and TA-Line)
T11-611 www.schurter.com/PG17_18_19
Circuit Breakers
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C] Correction factor
-5 0.87
0 0.90
+10 0.95
+23 1.00
+30 1.04
+40 1.10
+50 1.15
+60 1.20
Example: Rated current = 5 A; Environmental temperature = 40 °C; --> Correction factor =
1.1; Resulting current = 5.5 A --> Fount to next higher rated current: 6 A
Config. Code
T11|-|1|2|3|A|B|-|1.23|
The characters are placeholders for the correspondingly keys of selections from the key tables.
T11|-| 1 |2|3|A|B|-|1.23| = Mounting
Mounting Configuration
key
Snap-in mounting from front side 6
T11|-|1| 2 |3|A|B|-|1.23| = Actuation type
Actuation type Configuration
key
Reset type 1
T11|-|1|2| 3 |A|B|-|1.23| = Terminal
Terminal Configuration
key
Quick connect terminal 6.3x0.8mm 1
T11|-|1|2|3| A |B|-|1.23| = Shunt terminal
Shunt terminal Configuration
key
Shunt terminal N
T11|-|1|2|3|A| B |-|1.23| = Setting indication
Setting indication Configuration
key
Setting indication R
T11|-|1|2|3|A|B|-| 1.23 | = Rated current
Rated current Configuration
key
0.05 A 0.05
0.1 A 0.1
0.15 A 0.15
0.2 A 0.2
Other rated currents on request
Rated current Configuration
key
0.3 A 0.3
0.4 A 0.4
0.5 A 0.5
0.6 A 0.6
0.7 A 0.7
0.8 A 0.8
0.9 A 0.9
1.0 1
1.1 A 1.1
1.2 A 1.2
1.3 A 1.3
1.4 A 1.4
1.5 A 1.5
1.6 A 1.6
1.7 A 1.7
1.8 A 1.8
1.9 A 1.9
2.0 A 2
2.1 A 2.1
2.3 A 2.3
2.5 A 2.5
2.8 A 2.8
3.0 A 3
3.3 A 3.3
3.5 A 3.5
4.0 A 4
4.5 A 4.5
5.0 A 5
5.5 A 5.5
6.0 6
6.5 A 6.5
7.0 A 7
7.5 A 7.5
8.0 A 8
8.5 A 8.5
Other rated currents on request
5
Thermal (T- and TA-Line) T11-611
www.schurter.com/PG17_18_19
Circuit Breakers
Rated current Configuration
key
9.0 A 9
9.5 A 9.5
10.0 A 10
11.0 A 11
12.0 A 12
Other rated currents on request
Rated current Configuration
key
13.0 A 13
14.0 A 14
15.0 A 15
16.0 A 16
Other rated currents on request
Variants
Rated current Construction variants Config. Code Order Number
Shunt terminal Setting indication
2.0 A T11-611-2 4400.0002
10.0 A T11-611-10 4400.0030
16.0 A T11-611-16 4400.0034
3.5 A T11-611-3.5 4400.0200
15.0 A l l T11-611NR-15 4400.0791
Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/Stock-Check/Stock-
Check-SCHURTER
Packaging Unit 100 Pcs
Accessories
Description
T-Linie Zubehör
Accessories to T-Line
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
31.05.2016
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Schurter:
4400.0019 4400.0021 4400.0023 4400.0024 4400.0025 4400.0028 4400.0029 4400.0031 4400.0032 4400.0165
4400.0169 4400.0291 4400.0495 4400.0505 4400.0711 4400.0714 4400.0034 4400.002 4400.003 4400.0030
4400.0020 4400.0002