https://www.phoenixcontact.com/us/products/2910333
05/19/2021Page1/5
Type 2 surge protection plug-VAL-US-48/40-P-2910333
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
UL Recognized type 2 SPD and IEC type 2 surge protection plug with a varistor and thermal disconnect for use
with VAL-US base elements, mechanical and visual fault warning
Product Description
Surge protective device replacement plug
Your advantages
Plugs can be checked with CHECKMASTER
Thermal disconnect device for each individual plug
Pluggable
Mechanical coding of all slots
Consists of base element and plug
Optical, mechanical status indication for the individual arresters
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4055626444468
Weight per Piece (excluding packing) 40.000 g
Custom tariff number 85363030
Country of origin Germany
Technical data
Dimensions
Height 52.4 mm
Width 17.5 mm
https://www.phoenixcontact.com/us/products/2910333
05/19/2021Page2/5
Type 2 surge protection plug-VAL-US-48/40-P-2910333
Technical data
Dimensions
Depth 55.3 mm
Horizontal pitch 1 Div.
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification II
T2
EN type T2
IEC power supply system DC
Mode of protection L-N
L-PEN
N-PE
Mounting type on base element
Color jet black RAL 9005
Housing material PA 6.6
PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type Male
Number of positions 1
Surge protection fault message optical
Protective circuit
Nominal voltage UN60 VDC ±10%
-48 VDC ±10% (RRH)
Nominal frequency fN50 Hz (60Hz)
Maximum continuous voltage UC100 VDC
Residual current IPE ≤ 450 µA
Standby power consumption PC≤ 35 mVA
Nominal discharge current In (8/20) µs 15 kA
Maximum discharge current Imax (8/20) µs 40 kA
https://www.phoenixcontact.com/us/products/2910333
05/19/2021Page3/5
Type 2 surge protection plug-VAL-US-48/40-P-2910333
Technical data
Protective circuit
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up≤ 0.55 kV
Residual voltage Ures ≤ 0.55 kV (at In)
≤ 0.425 kV (at 10 kA)
≤ 0.325 kV (at 5 kA)
≤ 0.275 kV (at 3kA)
TOV behavior at UT100 VAC (5s / withstand mode)
Max. backup fuse with branch wiring 100 A (gG)
Connection data
Connection method VALVETRAB plug-in system
UL specifications
SPD Type 4CA
Maximum continuous operating voltage MCOV 100 VDC
Nominal voltage 60 VDC
Mode of protection L-N
L-G
N-G
Power distribution system Single phase
Measured limiting voltage MLV 720 V
Nominal discharge current In20 kA
Maximum Surge Current per Phase 40 kA
Standards and Regulations
Standards/regulations IEC61643-11 2011
EN61643-11 2012
Drawings
https://www.phoenixcontact.com/us/products/2910333
05/19/2021Page4/5
Type 2 surge protection plug-VAL-US-48/40-P-2910333
Dimensional drawing
17,544,8
43,3
55,3
52,4
Circuit diagram
Classifications
eCl@ss
eCl@ss 10.0.1 27130890
eCl@ss 11.0 27130890
eCl@ss 6.0 27130800
eCl@ss 7.0 27130890
eCl@ss 9.0 27130890
ETIM
ETIM 6.0 EC002497
ETIM 7.0 EC002497
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
Approval details
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
https://www.phoenixcontact.com/us/products/2910333
05/19/2021Page5/5
Type 2 surge protection plug-VAL-US-48/40-P-2910333
Approvals
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
cULus Recognized
Accessories
Accessories
Surge arrester
Type 2 surge protection device-VAL-US-48/40/1+0-FM-2910343
Surge protective device, single channel with remote indicator contact for 48VDC.
Type 2 surge protection device-VAL-US-48/40/1+1V-FM-2910344
Surge protective device, two channels with remote indicator contact for 48VDC, 2-wire plus ground
Phoenix Contact 2021 © - all rights reserved