Bussmann(R) LOW-PEAK(R) LPJ_SPI Dual-Element, Time-Delay Fuses Class J - 600 Volt 70 to 600A Dimensional Data 4.63" (- 0.03) 3.63" 2.63" .75" 1.13" (- 0.03) 1" .28" .43" 70A to 100A .13" 5.75" (- 0.03) 4.38" 3.0" 110A to 200A .43" Catalog Symbol: LPJ-_SPI Dual-Element, Time-Delay - 10 seconds (minimum) at 500% rated current Current-Limiting Ampere Rating: 70 to 600A Voltage Rating: ac: 600V (or less) dc: 300V (or less) Interrupting Rating: ac: 300,000A RMS Sym. dc: 100,000A Agency Information: UL Listed - Special Purpose, Guide JFHR, File E56412 CSA Certified, Class J per CSA C22.2 No. 248.8, Class 1422-02, File 53787 1.13" .28" 1.63" (- 0.03) 1.38" .19" 225A to 400A 450A to 600A Meets all performance requirements of UL Standard 248-8 for Class J fuses. Catalog Symbol and Ampere Ratings LPJ-70SPI LPJ-125SPI LPJ-250SPI LPJ-500SPI LPJ-80SPI LPJ-150SPI LPJ-300SPI LPJ-600SPI LPJ-90SPI LPJ-175SPI LPJ-350SPI -- LPJ-100SPI LPJ-200SPI LPJ-400SPI -- LPJ-110SPI LPJ-225SPI LPJ-450SPI -- Carton Quantity and Weight Weight* Ampere Ratings Carton Qty. Lbs. Kg. 70-100 5 1.69 0.767 110-200 5 4.21 1.910 225-400 1 1.67 0.758 450-600 1 2.80 1.270 *Weight per carton. Recommended fuseblocks for Class J 600V fuses See Data Sheet: 1114 For non-indicating version, the LPJ_SP is available. See Data Sheet: 1007. 8-26-04 SB04295 General Information: * Permanent replacement fuse indication. * True dual-element fuses with a minimum 10 second timedelay at 500% overload. * Long time-delay minimizes needless fuse openings due to temporary overloads and transient surges. * Can often be sized for back-up protection against motor burnout from overload or single-phasing if other overload protective devices fail. * High interrupting rating to safely interrupt overcurrents up to 300,000A. * High degree of current-limitation due to the fast speed-ofresponse to short-circuits. * Faster response to damaging short-circuit currents than mechanical overcurrent protective devices. * Reduces let-through thermal and magnetic forces in order to protect low withstand rated components. * Proper sizing provides "no damage" Type "2" coordinated protection for NEMA and IEC motor control in accordance with IEC Standard 947-4-1. * Dual-element fuses have lower resistance than ordinary fuses, hence they run cooler. * Lower watts loss reduces power consumption. * Unique dimensions assure that another class of fuse with a lesser voltage rating, interrupting rating or current-Iimiting ability cannot be substituted. * Space-saving package for equipment down sizing. CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. Form No. LPJ 70-600 Page 1 of 3 Data Sheet: 1063 Bussmann(R) LOW-PEAK(R) LPJ_SPI Dual-Element, Time-Delay Fuses Class J - 600 Volt 70-600A 600A 400A 200A 250A 125A 80A 100A Time-Current Characteristic Curves-Average Melt AMPERE RATING 300 200 100 TIME IN SECONDS 10 1 .1 10,000 100 1,000 .01 CURRENT IN AMPERES 8-26-04 SB04295 Form No. LPJ 70-600 Page 2 of 3 Data Sheet: 1063 Bussmann(R) LOW-PEAK(R) Dual-Element, Time-Delay Fuses Class J - 600 Volt LPJ_SPI 70-600A Current-Limitation Curves The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 8-26-04 SB04295 Form No. LPJ 70-600 Page 3 of 3 Data Sheet: 1063