https://www.phoenixcontact.com/us/products/2801245
09/10/2014Page1/4
Surge protection device-PT-IQ-2X1-12DC-PT-2801245
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on
the module for two signal wires with common reference potential.
The figure shows the PT-
IQ-1x2-24DC-PT version
Key commercial data
Packing unit 1 pc
Custom tariff number 85363030
Country of origin Germany
Technical data
Dimensions
Height 109.3 mm
Width 17.7 mm
Depth 77.5 mm
Horizontal pitch 1 Div.
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
General
Housing material PA 6.6
Inflammability class according to UL 94 V0
Color black
Type DIN rail module, two-section, divisible
https://www.phoenixcontact.com/us/products/2801245
09/10/2014Page2/4
Surge protection device-PT-IQ-2X1-12DC-PT-2801245
Technical data
General
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN12 V DC
Maximum continuous operating voltage UC15 V DC
10 V AC
Nominal current IN1000 mA (up to 40 °C)
Operating effective current IC at UC≤ 1 mA (per path)
Residual current IPE ≤ 1 mA (per path)
Nominal discharge current In (8/20) µs (Core-Earth) 10 kA
Impulse discharge current (10/350)˽µs, peak value limp 2.5 kA
Voltage protection level UP (Core-Earth) ≤ 90 V (C1 - 1 kV/500 A)
≤ 135 V (C2 - 10 kV / 5 kA)
≤ 35 V (C3 - 25 A)
Voltage protection level UP static (core-ground) ≤ 45 V (C1 - 1 kV/500 A)
≤ 100 V (C2 - 10 kV / 5 kA)
Response time tA (Core-Earth) ≤ 1 ns
≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 130 kHz/150 Ω)
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system typ. 600 kHz
Capacity (Core-GND) typ. 4 nF
Resistance in series 1.2 Ω ±5 %
Surge protection fault message Optical, multi-stage
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C1 (1 kV / 500 A)
C2 - 10 kA
D1 - 2,5 kA
C3 - 25 A
Pulse reset time tr in acc. with IEC 61643-21 (Core-Earth) ≤ 15 ms
Overload failure mode as per IEC 61643-21 (plug) Mode 2
Connection data
Connection method Push-in connection
Connection type IN Push-in connection
https://www.phoenixcontact.com/us/products/2801245
09/10/2014Page3/4
Surge protection device-PT-IQ-2X1-12DC-PT-2801245
Technical data
Connection data
Connection type OUT Push-in connection
Stripping length 10 mm
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Connection, equipotential bonding
Connection method NS 35 DIN rail or connection terminal block
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130807
eCl@ss 7.0 27130807
eCl@ss 8.0 27130807
ETIM
ETIM 3.0 EC000943
ETIM 4.0 EC000943
ETIM 5.0 EC000943
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Approvals
Approvals
https://www.phoenixcontact.com/us/products/2801245
09/10/2014Page4/4
Surge protection device-PT-IQ-2X1-12DC-PT-2801245
Approvals
Approvals
UL Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
Drawings
Diagram
1000
500
0
30 35 40 45 50 55 60 65 70 75
I [mA]
T [°C]
Dimensioned drawing
7,817,7
45
109,3
51,6
77,5
Circuit diagram
7 8
11 12
910
3 4
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com