https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page1/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking)
Technology, with protective coating, input: 1-phase, output: 24 V DC/10 A
Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system
protection. In addition, the high system availability is ensured by preventive function monitoring which reports critical operating states before errors can
occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 18 V
DC ... 29.5 V DC are covered. 
Product Features
For superior system availability
Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
Fast tripping of standard circuit breakers with dynamic power reserve SFB (selective fuse breaking) technology with up to 6 times the nominal
current for 12 ms
Preventive function monitoring
Optimum protection with dip coating for 100 % humidity
Key Commercial Data
Packing unit 1 pc
Weight per Piece (excluding packing) 1500.0 g
Custom tariff number 85044030
Country of origin Thailand
Technical data
Dimensions
https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page2/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Technical data
Dimensions
Width 60 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 63 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 100 % (at 25 °C, non-condensing)
Noise immunity EN 61000-6-2:2005
Maximum altitude 5000 m
Input data
Nominal input voltage range 100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range 85 V AC ... 264 V AC
90 V DC ... 410 V DC +5% (UL 508: ≤ 250 V DC)
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Discharge current to PE < 3.5 mA
Inrush surge current < 15 A (typical)
Power failure bypass > 36 ms (120 V AC)
> 36 ms (230 V AC)
Input fuse 10 A (slow-blow, internal)
Choice of suitable circuit breakers 10 A ... 16 A (AC: Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 18 V DC ... 29.5 V DC (> 24 VDC, constant capacity restricted)
Nominal output current 10 A (-25°C ... 60°C, UOUT = 24 V DC)
POWER BOOST 15 A (-25°C...40°C permanent, UOUT = 24VDC )
https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page3/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Technical data
Output data
SFB technology current reserve 60 A (12 ms)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Output power 240 W
Typical response time < 0.15 s
Maximum power dissipation in no-load condition 9.1 W
Power loss nominal load max. 22 W
General
Net weight 1.1 kg
Efficiency > 92.5 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Protection class I
> 535000 h (40°C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
vertically
Connection data, input
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Connection data, output
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page4/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Technical data
Connection data, output
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Connection data for signaling
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Screw thread M3
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Shock 30g in each direction, according to IEC 60068-2-27
Noise emission EN 55011 (EN 55022)
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CSA
Standards/regulations EN 61000-4-3
EN 61000-4-4
EN61000-4-6
Standard – Electrical equipment of machines EN 60204-1
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment EN 50178
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Equipment safety BG (design tested)
Shipbuilding approval Germanischer Lloyd (EMC 1), ABS, LR, RINA, NK, DNV, BV
UL approvals UL/C-UL listed UL 508
https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page5/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Technical data
Standards and Regulations
UL/C-UL Recognized UL 60950
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
DeviceNet approval DeviceNet™ Power Supply Conformance Tested
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Low Voltage Directive Conformance with LV directive 2006/95/EC
Approval - requirement of the semiconductor industry with regard to mains
voltage dips SEMI F47-0706 Compliance Certificate
Information technology equipment - safety (CBscheme) CB Scheme
Rail applications EN 50121-4
ATEX  II 3 G Ex nA nC IIC T4 Gc
TÜV 11 ATEX 079480 X
IECEx Ex nA nC IIC T4 Gc
IECEx TUN 11.0007X
Classifications
eCl@ss
eCl@ss 4.0 27040702
eCl@ss 4.1 27040702
eCl@ss 5.0 27049002
eCl@ss 5.1 27049002
eCl@ss 6.0 27049002
eCl@ss 7.0 27049002
eCl@ss 8.0 27049002
eCl@ss 9.0 27040701
ETIM
ETIM 4.0 EC000599
ETIM 5.0 EC002540
UNSPSC
UNSPSC 6.01 30211502
UNSPSC 7.0901 39121004
UNSPSC 11 39121004
UNSPSC 12.01 39121004
UNSPSC 13.2 39121004
https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page6/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Approvals
Approvals
Approvals
CSA / UL Recognized / UL Listed / cUL Recognized / IECEE CB Scheme / GL / BV / ABS / RINA / NK / DNV / cUL Recognized / BV / DNV / ABS /
RINA / LR / Bauartgeprüft / Bauartgeprüft / CSA / UL Recognized / UL Listed / LR / GL / NK / IECEE CB Scheme / EAC / EAC / cULus Recognized
Ex Approvals
IECEx / ATEX / IECEx / ATEX / UL Listed / cUL Listed / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
CSA
UL Recognized
UL Listed
cUL Recognized
IECEE CB Scheme
GL
https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page7/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Approvals
BV
ABS
RINA
NK
DNV
cUL Recognized
BV
DNV
ABS
RINA
LR
Bauartgeprüft
Bauartgeprüft
CSA
UL Recognized
https://www.phoenixcontact.com/us/products/2320911
12/15/2015Page8/8
Power supply, with protective coating-QUINT-PS/1AC/24DC/10/
CO-2320911
Approvals
UL Listed
LR
GL
NK
IECEE CB Scheme
EAC
EAC
cULus Recognized
Drawings
Block diagram
13
I < IN
DC OK
14
L (+)
N (-)
active
PFC
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com