SPH-1200, Power Factor Corrected Single Output, Hot Swap FEATURES: * * * * * * * * * Diode isolated output for hot swap "Zero wire" slope program current sharing for redundancy High power density: 5 W/cu. in. Industry standard DIN connector Universal ac input 0.99 typical power factor Dc power good and ac power fail signals True remote inhibit Monotonic turn-on and turn-off The SPH-1200 series provides low cost, highly reliable, N+1 redundant hot swap power for critical applications. SPECIFICATIONS: INPUT Ac Input: 105-264 Vac continuous range, 47 to 63 Hz. Internally fused for 20 A. Power Factor: 0.99 typical at full load. Meets EN61000-3-2 Class A. Inrush: Cold start ac current is less than 75 A at 115 Vac and 150 A at 230 Vac for 8 ms typical. Limited by thermistor. Holdup Time: 16 ms minimum after removal of power at full load. Efficiency: 80% minimum Ac Power Fail: Provides TTL "0" 5 ms before output voltage goes out of regulation band upon loss of ac power. Brownout Protection: Holds regulation to 85 Vac for 30 seconds maximum. OUTPUT Adjustability: User adjustable 5% minimum. Line Regulation: 0.2% Load Regulation: 2% (Slope Program) from 0 to 100% load change. Turn On Delay: 1 second typical Output Rise Time: (from 10% to 90%) 20 ms typical. Ripple & Noise: Less than 1% p-p, measured at 20 MHz bandwidth. Temperature Coefficient: 0.02% per degree C. Stability: 0.1% over 8 hours after 30 minutes warm-up. Transient Response: Output voltage returns to within 1% in less than 500 s for a 50% load change. Peak transient does not exceed 3%. Overload Protection: Electronic current limit, 120% maximum. Overvoltage Protection: Protects load against power supply induced overvoltage. Trip point is factory set so that output voltage cannot exceed 136% of nominal. Requires ac input to be cycled to reset. Remote Inhibit: Contact closure or a TTL level "0" turns off dc output. Dc Power Good: Provides a TTL "0" open collector when output is above 90% of nominal. Maximum pull-up voltage 30 Vdc; maximum sink current, 10 mA. Redundancy: Built-in OR-ing diode, slope program current sharing, and DIN blade connector provide "hot swap" and "N+1" capabilities. Current sharing remains within 10% of the unit's full output rating given 0.2% initial accuracy in the output voltage setting. 96 Status Indicators: Green LED on the front panel indicates normal operation (ACPF high and DCPG low) ENVIRONMENTAL Thermal Protection: Shuts down power supply if overheated. Automatic recovery. Temperature Range: 0 to 50C at full ratings. Safety Agencies: Approved to UL1950; CSA 22.2 #950; IEC 950 and TUV EN60950, Class 1 SELV, CE 73/23/EEC//93/68/EEC (low voltage directive). Conducted RFI: Meets FCC Part 15, Class A; EN55022 Class B. Cooling: Self-cooled by internal ball-bearing fan. OPTIONS Option "R", Rack Mount Panel: Special panel is required for rack mounting. AC INPUT (105-264 VAC Continuous Range) LOCATION 115 VAC 230 VAC Z32 Line Line 1 D30 Neutral Line 2 Z28 Safety Ground Safety Ground CONNECTOR See Below DC OUTPUT FUNCTION Output Voltage LOCATION NOTES CONNECTOR Z12 D14 Z16 D18 (+) to Polarity Eurocard connector-male Z4 D6 Z8 D10 (-) to Polarity DIN 41 612 Level 1-type H STATUS AND CONTROL FUNCTION LOCATION NOTES Dc Power Good Z20 Reference to Ac Power Fail D22 common Inhibit Z24 Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033 800-235-5929 * 805-486-4565 * FAX 805-487-8911 * www.condorpower.com CONNECTOR See Above SPH-1200, Power Factor Corrected Single Output, Hot Swap Commercial Model Power Out Output No. Output Current Total Regulation SPH-1200-24 1200 1 24 V 50 A 2% SPH-1200-28 1200 1 28 V 42 A 2% SPH-1200-48 1200 1 48 V 25 A 2% SPH-1200 MECHANICAL SPECIFICATIONS: Dimensions: Inches Millimeters Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033 800-235-5929 * 805-486-4565 * FAX 805-487-8911 * www.condorpower.com 97