3_41
33
Resistance to Internal Arcs
The testing of low-voltage switchboards under internal arc
conditions is considered a special test in accordance with
IEC 61641 and VDE 0660 Part 500, Supplement 2.
With this test, the danger to which persons may be sub-
jected in cases of internal arcs are assessed.
Thanks to its testing under internal arc conditions,
SIVACON offers the proof of operator safety with the be-
low-stated assessment criteria as a standard.
Assessment criteria
1. Properly secured doors, covers, etc., must not open.
2. Parts which may pose risks must not fly off.
3. No holes must form in the freely accessible outer parts
of the enclosure (casing).
4. No vertically attached indicators must inflame.
5. The protective conductor circuit for touchable parts of
the enclosure must remain functioning.
Grading for fault limitation
The top priority is the attempt to prevent the formation of
internal arcs completely. All quality assurance measures
serve this attempt. These measures start with the develop-
ment of the system components, which is accompanied by
numerous type tests, and furthermore comprise the switch-
boards’ correct configuration following order placement as
well as routine tests in our production units. A clearly de-
fined module structure and DP-supported configuration, or-
dering and handling procedures form the basis for configu-
ration.
For SIVACON, a graded concept was developed by
Siemens. Step 1 starts with a very high degree of operator
safety without an extensive limitation of the internal arc
effects within the system. Step 2 furthermore limits the
damage to the system’s cubicle. In the third and fourth
step, the effects on the function compartment or the in-
ternal arc's point of origin are limited, for example, to the
busbar compartment, device compartment, withdrawable
unit or connection compartment.
This facilitates the system's flexible and cost-effective ad-
justment to the actual requirements of the operator.
Load profile of SIVACON
Rated operational voltage Up to 690 V + 5%
Impulse current 110 kA/143 kA
Symmetrical short-circuit current 50 kA/ 65 kA
Permissible arcing time bis 300 ms
SIVACON internal arc concept
Step 1 (standard)
Operator safety without an extensive limitation of the in-
ternal arc's effects within the system
Molded-plastic covers in the termination walls
Pressure-relief flaps in the roof sheeting with non-venti-
lated systems
Spring-loaded locking device
50 kA/300 ms; 65 kA/300 ms with additional measures
Step 2
Operator safety with limitation of the internal arc’s effects
on a cubicle
Molded-plastic covers in the termination walls
Pressure-relief flaps in the roof sheeting with non-venti-
lated systems
Spring-loaded locking device
Light barriers (2 items/cubicle)
50 kA / 300 ms; 65 kA/300 ms with additional measures
Step 3 (fixed-mounted and withdrawable design)
Operator safety with limitation of the internal arc’s effects
on the function compartment
Molded-plastic covers in the termination walls
Pressure-relief flaps in the roof sheeting with non-venti-
lated systems
Spring-loaded locking device
Light barriers (2 items/cubicle)
Light barriers between the device compartment and the
busbar compartment
50 kA/300 ms; 65 kA/300 ms with additional measures
Step 4 (withdrawable design)
Operator safety with limitation of the internal arc’s effects
on the point of origin
Molded-plastic covers in the termination walls
Pressure-relief flaps in the roof sheeting with non-venti-
lated systems
Spring-loaded locking device
Light barriers (2 items / cubicle)
Light barriers between the device compartment and the
busbar compartment
Plug-in busbar covers
Withdrawable contact covers (only NFM withdrawable
unit)
With the additional measures, an inflammation of the inter-
nal arc upstream the protective organ is practically excluded.
Insulated main busbar
Busbars wrapped with protective tape, additionally ap-
plicable with all above-stated steps