Semiconductor fuses
Semiconductor (AC) fuses
SCAC186
Other Protistor®Fuses
Ferrule Fuses
14x51 URGB & 22x58 URGA - 600 V to 690 VAC
12/04
Main Characteristics
*Operating voltage limited to 600 V for the model with blown fuse trip-indicator / Total clearing I2t @ 600 V = 9000 A2s
Minimum operating voltage for built-in trip-indicator: 20 V
Voltage
rating
UN( VAC )
690 V
Class
Current
rating
IN(A)
8
10
12
16
20
25
32
40
50
25
32
40
50
63
80
Tested
Breaking capacity
200 kA
@ 690 V
200 kA
@ 690 V
Total clearing I2t @ A2s
660 V
20 17
37 30
75 60
95 75
175 145
300 250
550 460
1150 940
2550 2070
210
400
700
1270
2770
5500
Pre-arcing
I2t @ 1 ms
I2tp (A2s)
3.3
6.0
9.3
15.6
30.0
53.5
100
214
480
45
84
150
270
595
1165
URGB
URGA
Watts loss
0,8 ININ
1.45
1.85
2.5
3.4
4
4.7
5.7
6.2
7
4.7
5.7
7.1
8.7
9.8
12
14.2
2.7
3.4
4.6
6.2
7.4
8.6
10.6
11.5
13
8.5
10.3
12.8
15.7
17.7
21.7
25.6
EXTREMELY HIGH BREAKING CAPACITY FUSES:
PROTECTION OF POWER SEMICONDUCTORS AS PER
IEC STANDARD 60269.1 AND 4
600 V - 690 V AC VOLTAGE RATING
aR CLASS AS PER VDE 636-23 AND IEC 60269.4
WITH AND WITHOUT TRIP-INDICATOR
FOR SIZES 14 x 51 AND 22 x 58
I
p30
INI
p
> 30 IN
Size
14 x 51
22 x 58
200 kA @600 V22 x 58 URGA 100* 2150 9000* 14.2 25.6
600* - 690 V
SCAC187
Semiconductor fuses
Semiconductor (AC) fuses
Other Protistor®Fuses
Ferrule Fuses
14x51 URGB & 22x58 URGA - 600 V to 690 VAC
12/04
References
58 7 mini
Ø 22,2
Ø 5
51 7 mini
Ø 14,3
Ø 5
14x51 - Without blown fuse trip-indicator
Current
Rating Designation Catalog Number
Ref. Number
8 A 6.900 CP URGB 14.51/8 T078033
10 A 6.900 CP URGB 14.51/10 V078034
12 A 6.900 CP URGB 14.51/12 W078035
16 A 6.900 CP URGB 14.51/16 X078036
20 A 6.900 CP URGB 14.51/20 Y078037
25 A 6.900 CP URGB 14.51/25 Z078038
32 A 6.900 CP URGB 14.51/32 A078039
40 A 6.900 CP URGB 14.51/40 B078040
50 A 6.900 CP URGB 14.51/50 C078041
14x51 - With trip-indicator
22x58 - Without blown fuse trip-indicator
Weight: 18 g
Packaging: 10 pieces
Weight: 18 g
Packaging: 10 pieces
Weight: 57 g
Packaging: 10 pieces
Weight: 57 g
Packaging: 10 pieces
See Gears and Fuse gears section
Current
Rating Designation Catalog Number
Ref. Number
8 A 6.921 CP URGB 14.51/8 D078042
10 A 6.921 CP URGB 14.51/10 E078043
12 A 6.921 CP URGB 14.51/12 F078044
16 A 6.921 CP URGB 14.51/16 G078045
20 A 6.921 CP URGB 14.51/20 H078046
25 A 6.921 CP URGB 14.51/25 J078047
32 A 6.921 CP URGB 14.51/32 K078048
40 A 6.921 CP URGB 14.51/40 L078049
50 A 6.921 CP URGB 14.51/50 M078050
Current
Rating Designation Catalog Number
Ref. Number
25 A 6.900 CP URGA 22.58/25 C095245
32 A 6.900 CP URGA 22.58/32 D095246
40 A 6.900 CP URGA 22.58/40 E095247
50 A 6.900 CP URGA 22.58/50 F095248
63 A 6.900 CP URGA 22.58/63 G095249
80 A 6.900 CP URGA 22.58/80 H095250
100 A 6.900 CP URGA 22.58/100 N078051
Current
Rating Designation Catalog Number
Ref. Number
25 A 6.921 CP URGA 22.58/25 T095260
32 A 6.921 CP URGA 22.58/32 V095261
40 A 6.921 CP URGA 22.58/40 W095262
50 A 6.921 CP URGA 22.58/50 X095263
63 A 6.921 CP URGA 22.58/63 Y095264
80 A 6.921 CP URGA 22.58/80 Z095265
100 A 621 CP URGA 22.58/100 N098222
22x58 - With trip-indicator
FR14UB69V8
FR14UB69V10
FR14UB69V12
FR14UB69V16
FR14UB69V20
FR14UB69V25
FR14UB69V32
FR14UB69V40
FR14UB69V50
FR14UB69V8T
FR14UB69V10T
FR14UB69V12T
FR14UB69V16T
FR14UB69V20T
FR14UB69V25T
FR14UB69V32T
FR14UB69V40T
FR14UB69V50T
FR22UA69V25
FR22UA69V32
FR22UA69V40
FR22UA69V50
FR22UA69V63
FR22UA69V80
FR22UA69V100
FR22UA69V25T
FR22UA69V32T
FR22UA69V40T
FR22UA69V50T
FR22UA69V63T
FR22UA69V80T
FR22UA60V100T
Semiconductor fuses
Semiconductor (AC) fuses
SCAC188
Other Protistor®Fuses
Ferrule Fuses
14x51 URGB & 22x58 URGA - 600 V to 690 VAC
12/04
These curves indicate, for each rated current,
pre-arcing time vs. R.M.S.
pre-arcing current.
Time vs current characteristics
TOLERANCE OF MEAN PRE-ARCING CURRENT ± 10%
TOLERANCE FOR MEAN PRE-ARCING CURRENT ± 8%.
a = 130 B1 = 1,25
A2 = 0,6 B2 = 0,6
Cf3 = 0,8
a = 130 B1 = 1,25
A2 = 0,6 B2 = 0,6
Cf3 = 0,8
Electrical Characteristics
SCAC189
Semiconductor fuses
Semiconductor (AC) fuses
Other Protistor®Fuses
Ferrule Fuses
14x51 URGB & 22x58 URGA - 600 V to 690 VAC
12/04
Corrective factor - Peak arc voltage
These mean curves show the variation of the total
clearing time (I2tt) and the total clearing duration tt
as a function of operating voltage U.
This curve shows the peak value Um of the arc voltage
which appears across the fuse link as a function of
operating voltage U @ cos ϕ= 0.15.
Corrective factor Peak arc voltage
K
0
0,2
0,4
0,6
0,8
1,2
200 400 600 U(V)
1
Um(V)
2000
1000
200 400 600 800
U(V)
URGA URGA
URGB URGB
K
0
0,2
0,4
0,6
0,8
1,2
200 400 600 U(V)
1
Ip 50 In
Ip > 50 In
Um(V)
2000
1000
200 400 600 800
U(V)