1000V (IEC) 20-315A
Specifications
Description: Square body DIN 43
653 stud-mount high speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 1000Vac (20-250A)
— 900Vac (315A)
Amps: — 20-315A
IR: — 150kA RMS Sym.
Agency Information: CE, Designed and tested to IEC
60269: Part 4, UL Recognized.
Electrical Characteristics
Total clearing I2t
The total clearing I2t at rated
voltage and at power factor
of 15% are given in the elec-
trical characteristics. For
other voltages, the clearing
I2t is found by multi-plying by
correction factor, K, given as
a function of applied working
voltage, Eg, (rms).
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
122
Square body DIN 43 653 — 1000V (IEC): 20-315A
High Speed Fuses
1,5
1,0
0,5
0,4
0,3
0,2
K
Eg
200 400 600 800 1000
*Rated voltage 900V
*
Arc Voltage
This curve gives the peak
arc voltage, UL, which may
appear across the fuse dur-
ing its operation as a func-
tion of the applied working
voltage Eg, (rms) at a
power factor of 15%.
Power Losses
Watts loss at rated current is
given in the electrical char-
acteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The correc-
tion factor, Kp, is given as
a function of the RMS load
current, Ib, in % of the
rated current.
Features and Benefits
• Excellent dc performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
2,5
2
1,8
1,6
1,4
1,2
103
8
7
6
5
4
3
U
L
Eg
200 400 600 800 1000
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,15
0,1
K
p
Ib
30 40 50 60 70 80 90 100
%
Dimensions (mm)
Type 00TN/80 – 00/80
Size Max A B C D Max E F G H
00/80 54 98 78 51 30 28 10
00TN/80 54 98 78 51 30 28 67 10
1mm = 0.0394” / 1” = 25.4mm
Catalog Numbers
Catalog Numbers Electrical Characteristics
00/80 00TN/80 I2t (A2Sec)
Visual Type T Rated Clearing
Indicator for Indicator for Rated Current at Rated Watts
Micro Micro Size Voltage RMS Amps Pre-arc Voltage Loss
170M4802 170M4822 00 1000 20 20 140 5
170M4803 170M4823 1000 25 30 210 7
170M4804 170M4824 1000 32 55 390 9
170M4805 170M4825 1000 35 69 500 10
170M4806 170M4826 1000 40 100 690 11
170M4807 170M4827 1000 50 170 1200 13
170M4808 170M4828 1000 63 280 2000 18
170M4809 170M4829 1000 80 500 3500 22
170M4810 170M4830 1000 100 950 6850 25
170M4811 170M4831 1000 125 1500 11500 33
170M4812 170M4832 1000 160 3000 22000 37
170M4813 170M4833 1000 200 5600 40500 40
170M4814 170M4834 1000 250 10000 74000 48
170M4815 170M4835 900 315 18000 115000 58
• Watts loss provided at rated current.
• Microswitch ordered separately. See accessories on page 179-180.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 123
Square body DIN 43 653 — 1000V (IEC): 20-315A
High Speed Fuses
High Speed
Fuses
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virtual Pre-arcing Time In Seconds
Prospective Current In Ampere RMS
10 102 103 104
25A
35A
50A
80A
125A
200A
315A*
250A
63A
40A
32A
20A
100A
160A
104
103
102
2x10
Peak Let-Through Current In Amperes
Prospective Short-Circuit Current symmetrical RMS
10 102 103 104 Amp 105
315A
250A
200A
160A
125A100A
80A 63A
50A 40A
35A 32A
25A 20A
Size 00 — 20-315A: 1000V
Time-Current Curve
Peak Let-Through Curve
* 315A fuse is derated to 900V
Data Sheet: 17058504
Protect the Promise of Customer
Satisfaction
Our customer satisfaction team answers your calls
8:00 a.m. – 4:30 p.m. for all US time zones,
receiving and responding to an average of 1600
calls and 700 emails every day.
We also offer emergency after-hours service.
Phone: 636-527-3877
email: busscustsat@cooperbussmann.com
Toll-free fax: 800-544-2570
Emergency after-hour phone: 314-995-1342
Did You Know?