CSM_SAO_DS_E_4_1
1
Current Sensor
SAO
Solid-state, Plug-in Current Sensor
Applicable to motor overcurrent protection and 3-phase AC cur-
rent detection.
Inverse-type, start-up lock type, and instantaneous type over-
current sensors available.
Instantaneous type under current sensor available.
Plug-in design simplifies installation, removal, and wiring.
DIN sized (48 mm x 96 mm)
The SAO cannot be used in circuits with
waveform distortion, inverter circuits, or
with capacitor loads.
Model Number Structure
Model Number Legend
1. Basic model name
SAO: Current Sensor
2. Operating time characteristics
R: Inverse type: inverse time both at starting and during oper-
ation
Q: Instantaneous type with start-up lock
S: Regular instantaneous type
3. Detection function
U: Undercurrent detection
None: Overcurrent detection
4. Control voltage
1: 100/110/120 VAC
2: 200/220/240 VAC
5: 24 VDC
6: 48 VDC
7: 100/110 VDC
5. Product history
N: New version
Ordering Information
* Fixed time-limit at start-up, instantaneous thereafter.
Accessories (Order Separately)
Current Converters
Socket
123 4 5
SAO-@@@@
Terminal/
mounting
Control voltage Overcurrent detection Under current
detection
Inverse type Instantaneous type Instantaneous type
W/start-up lock* W/o start-up lock
Plug-in/DIN
rail via socket
100/110/120 VAC SAO-R1N SAO-Q1N SAO-S1N SAO-SU1N
200/220/240 VAC SAO-R2N SAO-Q2N SAO-S2N SAO-SU2N
24 VDC SAO-R5N SAO-Q5N SAO-S5N SAO-SU5N
48 VDC SAO-R6N SAO-Q6N SAO-S6N SAO-SU6N
100/110 VDC SAO-R7N SAO-Q7N SAO-S7N SAO-SU7N
Model Current range
SET-3A 1 to 80 A
SET-3B 64 to 160 A
DIN rail socket
8PFA1
Type Model
Front connecting socket 8PFA1
SAO
2
Specifications
Ratings
Characteristics
Motor circuit Voltage:500 VAC max. 3-phase (primary voltage at SET Current Converter)
Current:1 to 80 A or 64 to 160 A 3-phase (primary current at SET Current Converter)
Power supply circuit Voltage: 100/110/120 VAC, 200/220/240 VAC, 24, 48 VDC, or 100/110 VDC (leveled DC)
Voltage fluctuation: +10/–15% max. of the rated voltage
Frequency: 50/60 Hz ±5%
Current SV range See table of Current Converter.
Output contact Configuration: SPDT
Capacity: 3 A (cosφ = 1.0)/2 A (cosφ = 0.4) at 240 VAC; 3 A (resistive load)/2 A (L/R = 7 ms) at 24 VDC;
0.2 A (resistive load)/0.1 A (L/R = 7 ms) at 110 VDC
Power consumption 100/110/120 VAC: approx. 3.5 VA; 200/220/240 VAC: approx. 7 VA;
24 VDC: approx. 0.3 W; 48 VDC: approx. 0.5 W; 100/110 VDC: approx. 1.2 W
Case color Munsell 5Y7/1
Item SAO-R@NSAO-Q@NSAO-S@NSAO-SU@N
Operating current 100% of the current SV (current when the relay is OFF for the SAO-SU@N)
Operating time charac-
teristics
Inverse type Fixed time at start-up and in-
stantaneous thereafter
Instantaneous type
Operating time For a 600% overcurrent:
Time scale x 1: 1 to 10 s
Time scale x 4: 4 to 40 s
For a 200% overcurrent:
2.8 x t ±30%, where t is
the operating time at
600% overcurrent.
(time SV at max.)
In start-up lock mode with a
600% overcurrent:
Time scale x 1: 1 to 10 s
Time scale x 4: 4 to 40 s
In instantaneous mode:
0.3 s max. at 120%
overcurrent
0.3 s max. with an overcur-
rent of 120% the current SV
0.3 s max. when 120% the
current SV drops below
80%
Initial current in start-
up mode
--- Approx. 30% of the current
SV
--- ---
Inertial characteristics Will not operate for 80% of op-
erating time for a 600% over-
current. (at min. current and
max. time SV)
---
Reset value More than 95% of the operating current Less than 105% of the op-
erating current
Operating current
accuracy
±10% of the current SV
Operating time
accuracy
+10/–5% of maximum time SV (at a time SV: 1)
±10% of maximum time SV (at a time SV: 2 to 10)
0.3 s max.
Influence of tempera-
ture on operating
current
±5% for 0 to 40°C; ±10% for –10 to 50°C
Influence of tempera-
ture on operating time
±10% for 0 to 40°C; ±20% for –10 to 50°C
(start-up mode)
0.3 s max. for –10 to 50°C
Influence of frequency
on operating current
±3% for a frequency fluctuation of ±5%
Influence of frequency
on operating time
±5% for a frequency fluctuation of ±5%
(start-up mode)
0.3 s max. for a frequency fluctuation of ±5%
Influence of voltage on
operating current
±3% for a voltage fluctuation of +10/–15%
Influence of voltage on
operating time
±5% for a voltage fluctuation of +10/–15% (start-up mode) 0.3 s max. for a voltage fluctuation of +10/–15%
(start-up mode)
SAO
3
Characteristics (continued)
Engineering Data
Operating Time Characteristics
Insulation resistance 10 M min. between electric circuits and the mounting panel
5 M min. between contact circuits, or between contacts of same pole
Withstand voltage 2,000 VAC for 1 min between electric circuits and the mounting panel
2,000 VAC for 1 min between contact circuits and other circuits
1,000 VAC for 1 min between contacts of same pole
Lighting impulse withstand voltage 6,000 V max. between electric circuits and the mounting panel
4,500 V max. between contact circuits and other circuits
4,500 V max. between each control power circuits
Waveform: 1.2 x 50 µs 3 times for each poles
Overload capacity Motor circuit: 20 times the current SV for 2 s, applied twice with a 1 min interval
Continuous current: 125% of the maximum current SV for each current range.
Power supply: AC: 1.15 times the rated power supply voltage for 3 hrs, once
DC: 1.3 times the rated power supply voltage for 3 hrs, once
Vibration resistance Malfunction: 10 to 55 Hz, 0.3-mm double amplitude each in 3 directions for 10 min
Destruction: 10 to 25 Hz, 2-mm double amplitude each in 3 directions for 2 hrs
Shock resistance Malfunction: 98 m/s2 (approx. 10G) each in 3 directions
Destruction: 294 m/s2 (approx. 30G) each in 3 directions
Test button operation Operated quickly (without lighting the LED)
Ambient temperature Operating: –10 to 60°C (with no icing)
Storage: –25 to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Altitude 2,000 m max.
Weight Approx. 170 g
Time Changeover Setting: 1 Time Changeover Setting: 4
SAO-QSAO-R
Current (% of current SV)
Operating time (s)
Reset Time Characteristics
SAO-SU
Operating Time Characteristics
Current (% of operating current)
SAO-S
80
70
60
50
40
30
20
10
0100 200 300 400 500 600
10
8
6
4
2
1
Time scale value
320
280
240
200
160
120
80
40
0100 200 300 400 500 600
10
8
6
4
2
1
Operating time (s)
Time scale value
Current (% of current SV)
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0100 200 300 400 500 600
Operating time (s)
Current (% of current SV)
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0100 200 300 400 500 600
Current (% of current SV)
Operating time (s)
0.4
0.3
0.2
0.1
020 40 60 80 100
Operating time (s)
0.4
0.3
0.2
0.1
100 120 140 160 180 200
0
Current (% of operating current)
Operating time (s)
SAO
4
Installation
Connection
Internal Circuit
SAO-R
3-phase 50/60 Hz
SET-3
Current Converter
SAO-R Current Sensor
Rectifying
circuit
Tap setting
circuit
OC: overcurrent LED
To all circuits
Output
relay
Test
SAO-Q Current Sensor SAO-S Current Sensor
Motor
SAO-SU Current Sensor
NORMAL: LED indicates operation.
(ON for a steady current,
OFF for an under current.)
RST
M
X
+
71
2
6
5
4
8
X/C
OC
Current SV
circuit
Overcurrent
detecting circuit
Time SV circuit
RY drive
circuit
Power supply
circuit
Control voltage
7
8OC
7
8OC
RST
M
X
71
2
6
5
4
8
X/C
NORMAL
Current SV
circuit
Overcurrent
detecting circuit
AND circuit Start-up mode
time SV circuit
Start-up
detecting circuit
Current SV
circuit
Overcurrent
detecting circuit
Current SV
circuit
Overcurrent
detecting circuit
3-phase 50/60 Hz
SET-3
Current Converter
Rectifying
circuit
Tap setting
circuit
To all circuits
Output
relay
Test
Motor
Control voltage
SAO-SU
+
RY drive
circuit
Power supply
circuit
Note: There is no polarity specification when using a DC power supply.
OC: Ovecurrent LED OC: Ovecurrent LED
ON
Output relay
operation
Motor
startup
Operating
value
Reset current
(A) Explanation of SAO-SU Contacts
1. The contact is NC (between terminals 4 and 5) when the motor is not started.
2. The contact is NO (between terminals 5 and 6) when the startup pushbutton is
pressed and a current larger than the reset current flows.
3. The contact is NC (between terminals 4 and 5) when the motor current is less than
the operating value (i.e., undercurrent).
SAO
5
Connection Examples
Note: Provide the control power supply for the SAO Current Sensor
from the contactor’s power supply side. If the control power
supply is turned ON and the motor is started at the same time,
operation inconsistent with the time SV may occur.
Note: To prevent the buzzer sounding when power is turned ON, in-
stall a timer so that the buzzer sounds only when the timer’s
contacts are closed.
Overcurrent Detection Circuit
SAO-R/SAO-Q/SAO-S
Undercurrent Detection Circuit
SAO-SU
Electro-
magnetic
contactor
Phase
advancing
capacitor
SET-3
Current
Converter
Motor
Start
Alarm
buzzer
6543
7812
RST
M
BZ
Stop
SAO
current
sensor
6543
7812
RST
M
BZ
Electro-
magnetic
contactor
Phase
advancing
capacitor
SET-3
Current
Converter
SAO
current
sensor
Start
Alarm
buzzer
Stop
Motor
SAO
6
Operation
Settings
Current Sensor Switch Settings
Current Scale Multiplying Factor Decal
Setting Operating Current
Setting Operating Time
Decal Current scale value (A)
no. 4 5 6 7 8 9 10
0.25 1 1.25 1.5 1.75 2 2.25 2.5
0.5 2 2.5 3 3.5 4 4.5 5
1 4 5 6 7 8 9 10
2 8 10 12 14 16 18 20
4 16 20 24 28 32 36 40
8 32 40 48 56 64 72 80
LED Indicator
The LED indicates that an overcurrent
has occurred and the relay is operating.
Test Button
SAO-R/Q
SAO-S
LED Indicator
The NORMAL indicator
is lit for normal current;
not lit for undercurrent.
SAO-SU
SAO-R2N
CURRENT SENSOR
sec
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
2
1
TIME
TEST
×4
sec
×1
sec
×A
0.5
CURRENT
oc
SAO-S2N
CURRENT SENSOR
10
9
8
7
6
5
4
TEST
×A
0.5
CURRENT
oc
SAO-SU2N
CURRENT SENSOR
10
9
8
7
6
5
4
TEST
×A
0.5
CURRENT
NORMAL
Set the current setting knob to the required current
value. The setting value is indicated by the product
of the scale value and the multiplying factor as
shown in the following table. The required trip current
can be obtained directly by means of the current-
setting knob.
Determine the current scale multiplying factor corresponding to the
current SV range obtained from Table 1 and paste the current scale
multiplying decal to the current sensor. For example, when the current
setting range is 2 to 5 A, the decal no. is 0.5.
Set the time setting knob to the required
time. The operating time is equal to the
time scale value times the setting on the
time changeover switch. For example, if
the time scale value is 6, and the time
changeover switch is set to 4, the
operating time is 24 s. For the SAO-R,
this is the operating time in the event of a
600% overcurrent. For the SAO-Q, this is
the operating time in start-up mode.
There is no operating time SV for the
SAO-S.
Time Setting Knob
16 64 80 96 112 128 144 160
Pressing the test button momen-
tarily operates the output relay. The
LED indicator, however, does not
light during this operation.
SAO
7
Operating and Setting Procedures
Make the settings for the SAO Current Sensor and the SET-3@ Current Converter according to the current of the load to be used.
Steady Current
Note: The current setting range is determined by the number of times the conductors to the SET-3@ are passed through and by the setting tap of
the SET-3@. The current scale values are always 4 to 10 A. Therefore, attach the included current scale multiplying factor label to the SAO
that matches the current range.
Determining Current Sensor Settings
1. Determining the Current Scale Multiplying
Factor
Determine a current scale multiplying factor that matches the steady
current obtained from the table, and attach that decal to the Current
Sensor. For example, when the current setting range is 2 to 5 A, the
label number is 0.5.
2. Setting the Operating Current
Determine the operating current setting from the required steady
current and the label number (i.e., multiplying factor) and make the
setting using the current setting knob. The following table shows the
relation between scale values and actual operating current values.
The figures are steady current values. (Unit: A)
3. LED Operation Indicator
The indicator is continuously lit when the Sensor operates due to
overload.
4. Setting the Operating Time
Set the time setting knob to
the required time. The
operating time is equal to
the scale value times scale
multiplying factor.
The scale value can be
selected using the
changeover switch. For the
SAO-R, this is the operating
time in the event of a 600%
overcurrent. For the SAO-Q,
this is the operating time in
startup mode. There is no
operating time SV for the
SAO-S.
5. Test Button
Pressing the button momentarily operates the output relay. The LED
indicator, however, does not light during this operation.
Determining Current Converter
Settings
1. Determining the Number of Passes for
Primary Conductors
Determine the number of primary conductor passes and the setting
tap according to the table. For example, for a current setting range
of 2 to 5 A, the number of passes is four and the setting tap is 20.
Pass the three wires through the holes from the same direction. It
doesn’t matter which wires go through which holes.
2. Setting the Tap
Use a screwdriver to screw the included setting screw into the
required tap hole. After the setting has been made, be sure to mount
the cover as it was before.
The SET-3B does not have tap settings.
SAO-R, -Q, -S
Rated current
(current setting
range) (A)
Current scale
multiplying factor
label number
Current converter
Number of
conductor passings
Setting tap Model
1 to 2.5
2 to 5
4 to 10
8 to 20
16 to 40
32 to 80
0.25
0.5
1
2
4
8
8
4
2
1
1
1
20
20
20
20
40
80
SET-3A
64 to 160 16 1 Fixed SET-3B
Setting
Factor
45678910
× 0.25
× 0.5
× 1
× 2
× 4
× 8
× 16
1
2
4
8
16
32
64
1.25
2.5
5
10
20
40
80
1.5
3
6
12
24
48
96
1.75
3.5
7
14
28
56
112
2
4
8
16
32
64
128
2.25
4.5
9
18
36
72
144
2.5
5
10
20
40
80
160.5
Note
After detection, the operation indicator automatically turns OFF
when there is no longer an overload.
Scale multiplying
factor
Time scale value
× 1 × 4
1
2
3
4
5
6
7
8
9
10
1 s
2 s
3 s
4 s
5 s
6 s
7 s
8 s
9 s
10 s
4 s
8 s
12 s
16 s
20 s
24 s
28 s
32 s
36 s
40 s
One conductor pass Four conductor passes
(The conductors pass
through the holes once.)
(The conductors pass
through the holes four times.)
20
40
60
MADE IN JAPAN
OMRON Corporation
CURRENT
CONVERTER
No.
DATE
25053
1983
SET-3A
(1)
(2)
SAO
8
Make the settings for the SAO-SU Current Sensor and the SET-3@ Current Converter according to the current of the load to be used.
Steady Current
Note: The current setting range is determined by the number of times the conductors to the SET-3@ are passed through and by the setting tap of
the SET-3@. The current scale values are always 4 to 10 A. Therefore, attach the included current scale multiplying factor decal to the SAO
that matches the current range.
Determining Current Sensor Settings
1. Determining the Current Scale Multiplying
Factor
Determine a current scale multiplying factor that matches the steady
current obtained from the table, and attach that decal to the Current
Sensor. For example, when the current setting range is 2 to 5 A, the
label number is 0.5.
2. Setting the Operating Current
Determine the operating current setting from the required steady
current and the label number (i.e., multiplying factor), and make the
setting using the current setting knob. The following table shows the
relation between scale values and actual operating current values.
These figures indicate steady current values. (Unit: A)
3. LED Operation Indicator
The indicator is continuously lit for normal current and not lit when
undercurrent is detected.
4. Test Button
Pressing the test button momentarily operates the output relay.
Determining Current Converter
Settings
1. Determining the Number of Passes for
Primary Conductors
Determine the number of primary conductor passes and the setting
tap according to the table. For example, for a current setting range
of 2 to 5 A, the number of passes is four and the setting tap is 20.
Pass the wires through the holes from the same direction. It doesn’t
matter which wires go through which holes.
2. Setting the Tap
Use a screwdriver to screw the included setting screw into the
required tap hole. After the setting has been made, be sure to mount
the cover as it was before.
The SET-3B does not have tap settings.
SAO-SU
Rated current
(current setting
range) (A)
Current scale
multiplying factor
label number
Current converter
Number of
conductor passes
Setting tap Model
1 to 2.5
2 to 5
4 to 10
8 to 20
16 to 40
32 to 80
0.25
0.5
1
2
4
8
8
4
2
1
1
1
20
20
20
20
40
80
SET-3A
64 to 160 16 1 Fixed SET-3B
Setting
Factor
45678910
× 0.25
× 0.5
× 1
× 2
× 4
× 8
× 16
1
2
4
8
16
32
64
1.25
2.5
5
10
20
40
80
1.5
3
6
12
24
48
96
1.75
3.5
7
14
28
56
112
2
4
8
16
32
64
128
2.25
4.5
9
18
36
72
144
2.5
5
10
20
40
80
160
One conductor pass Four conductor passes
(The conductors pass
through the holes once.)
(The conductors pass
though the holes four times.)
20
40
60
MADE IN JAPAN
OMRON Corporation
CURRENT
CONVERTER
No.
DATE
25053
1983
SET-3A
(1)
(2)
SAO
9
Checking Operation
The following circuit can be used to check SAO-@ and SET-3@ characteristics.
200 VAC, 3-phase,
50/60 Hz
SET-3
Current
Converter
SAO
Current
Sensor
Control voltage
AAA
3
2
45
6
7
81
RST
X/a
CC
100 V
C
±
RRR
Pushbutton
switch
X
3φSD: Three-phase voltage regulator
A: AC ammeter
CC: Cycle counter
X: Auxiliary relay (15 A)
R: Resistor
100 VAC
SAO
10
Dimensions
Note: All units are in millimeters unless otherwise indicated.
SAO-R/SAO-Q
Four, 6-dia. mounting holes or
four, M5 mounting screw holes
Three, 20-dia.
through holes
Mounting Holes
Two, M3.5
terminal screws
The Height of DIN
Rail Mounting
SAO-S/SAO-SU
Current Converter
SET-3A, SET-3B
44
9.5
91
78.5
100
12
96
48
44
9.5
91
78.5
100
12
96
48
SAO
8PFA1 (order separately)
111
33.5
33.5
20.5
4
28
73
6
26
40
52
60
112 80
80±0.5
52±0.5
SAO
11
Precautions
On Operation
Use a commercial frequency power supply only for the control power
supply.
The SET-3@ Current Converter is designed for use with a single SAO
Current Sensor; do not connect two units to a single SET-3@ as in
figure 1 below (even if a diode is included in the circuit).
If the current transformer has sufficient capacity, the circuit in figure 2
is acceptable.
Mounting
When installing with an 8PFA1 connecting socket, first fasten the
socket firmly to the panel with screws, then plug in the relay and
secure it with a hook. Leave at least 30 mm of space between the
relays for the hooks.
Back-connecting sockets can not be used.
Connections
Make sure that the polarity is correct when connecting the Current
Converter and Current Sensor. It is not necessary to consider polar-
ity when using a DC control power supply.
Determine the necessary number of conductor runs from the table
Selecting the Current Converter in the Operation section. Pass the
wires through the holes from the same direction. It doesn’t matter
which wires go through which holes.
Testing Method
Verify operation by turning on the control voltage and pressing the
test button.
It is possible to check whether SAO-@ and SET-3@ characteristics
are correct or not with the test circuit shown on page 9.
Figure 1: Never Use this Setup
Figure 2: OK with Sufficient Capacity
SET
SAO
SAO
SAO
SET
SAO
SET
CT
CT
One conductor pass Four conductor passes
(The conductors pass
through the holes once.)
(The conductors pass
through the holes four times.)
SAO
12
What is the procedure for using the SAO with a single
phase?
The following describes the single-phase operating
procedure for the SAO. Models for single-phase circuits,
however, are also available. Refer to SAO-
@
S.
Connection Procedure
Run the primary wires through any two of the three holes on the SET-
3 the number of times specified for the SET-3@.
Setting Procedure
The operating value will change when single phase is used as in the
figure above. Therefore, the setting must be changed.
Make the setting to approximately 0.77 times the current at which
operation is desired. For example, for operation at 10 A, set the value
to the following:
10 x 0.77 = 7.7 A
In any case, the SAO is adjusted for three-phase use. As a
precautionary measure, therefore, perform confirmation testing using
the actual load.
Can two SAO Current Sensors be used connected to one
SET-3@? If not, can a diode or other device be inserted?
It is not possible to connect two SAO Current Sensors to one
SET-3@. The SET-3 output is designed so that the output
voltage will match when one SAO (SE) is used.
Operation is not possible even with a diode inserted.
Operation as shown in figure 2, however, is possible if the
capacity of the CT is sufficient.
Q&A
Q
SET-3@
SAO
M
Motor
Q
SAO
SAO
SAO
SET-3@
SAO
SET-3@
CT
CT
SET-3@
SET-3@
SAO
SAO
Figure 1
Figure 2
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2011.12
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2011 All Right Reserved.