SPECIFICATION
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE Note.6
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
OVERTEMPERATURE
SAFETY STANDARDS
WORKINGTEMP. Note.5
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
DCOKREALY CONTACTRATINGS(max.)
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
ACCURRENT (Typ.)
800ms,150ms/400VAC 1500ms,150ms/230VACatfullload
18ms/400VAC atfullload18ms/230VAC
180~550VAC254~780VDC
47~63Hz
91%
1A/400VAC2A/230VAC
56~65V
COLDSTART 50A
<3.5mA /530VAC
29~33V
Protectiontype:Shutdowno/pvoltage, auto-recoveryafter1minuteifthefaultconditionisremoved
90 5 (TSW)detectonheatsinkofpowerswitch
¢J¡Ó ¢J
Protectiontype:Shutdowno/pvoltage,recoversautomaticallyaftertemperaturegoesdown
UL508approved,IEC60950-1CBapprovedbySIQ,designrefertoGL
CompliancetoEN55022(CISPR22),EN61204-3ClassB, EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2(EN50082-2),EN61204-3,heavyindustrylevel,criteria A approved
-30~+70
¢J
(Referto"DeratingCurve")
60Vdc/0.3A,30Vdc/1A,30Vac/0.5A resistiveload
20~95%RHnon-condensing
-40~+85 ,10~95%RH
¢J
¡Ó ¢J ¢J)
0.03%/ (0~50
Component:10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-6
141.1Khrsmin.MIL-HDBK-217F(25 )
¢J
63*125.2*113.5mm(W*H*D)
1.06Kg;12pcs/13.7Kg/1.06CUFT
WDR-240-48
48V
5A
0~5A
240W
150mVp-p
48~55V
¡Ó
1.0%
¡Ó
0.5%
¡Ó
1.0%
WDR-240-24
24V
10A
0~10A
240W
150mVp-p
24~28V
¡Ó
1.0%
¡Ó
0.5%
¡Ó
1.0%
¡½
Features :
WDR-240 series
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:2KVACO/P-FG:0.5KVAC O/P-DCOK:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:>100MOhms/500VDC/25 /70%RH
¢J
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note4)
PROTECTION
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
¢J
240WSingleOutputIndustrialDINRAIL PowerSupply
Single and two phase wide input range 180~550VAC
High efficiency 91% and low power dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
¡E
¡E
¡E
¡E
¡E
¡E
¡E
¡E
¡E
¡E
¡E
Built-in active PFC circuit compliance to EN61000-3-2
FileName:WDR-240-SPEC 2012-07-30
105~130% ratedoutputpower
Protectiontype: Constantcurrentlimiting,unitwillshutdownafter3sec.,auto-recoveryafter1minuteifthefaultconditionisremoved
EMCIMMUNITY
EMCEMISSION
POWERFACTOR (Typ.) PF 0.84/400VAC
¡Ù
PF 0.84/230VAC
¡Ù
FileName:WDR-240-SPEC 2012-07-30
MechanicalSpecification
BlockDiagram
CaseNo.979BUnit:mm
DCOKRelayContact
DETECTION
PWM&PFC CIRCUIT
O.L.P.U.V.P.
EMIFILTER
RECTIFIERS
POWER
SWITCHING FILTER
&
RECTIFIERS +V
DCOK
-V
I/P
FG
CONTROL
O.V.P.
&
O.C.P.
PFC
CIRCUIT
PFC
CONTROL
TerminalPinNo. Assignment(TB1)
TerminalPinNo. Assignment(TB2)
PinNo.
PinNo.
1
1,2
2
3,4
5,6
3
Assignment
Assignment
FG
AC/L1
AC/L2
DCOUTPUT +V
DCOUTPUT -V
ADMISSIBLEDIN-RAIL:TS35/7.5OR TS35/15
35
63
1
2
3
4
5
6
1
2
3
125.2
113.5
TB1 TB2
DCOK
DCOK
+V ADJ.
RelayContact
+
ContactClose PSUturnson/DCOK.
PSUturnsoff/DCFail.
30V/1A resistiveload.
ContactOpen
ContactRatings(max.)
WDR-240 series
240WSingleOutputIndustrialDINRAIL PowerSupply
AMBIENTTEMPERATURE( )
¢J
LOAD(%)
-30 0 10 20 30 40 50 60 70
20
40
60
80
100
(VERTICAL)
OutputderatingVSinputvoltageDeratingCurve
FileName:WDR-240-SPEC 2012-07-30
LOAD(%)
INPUTVOLTAGE(VAC)60Hz
180 190 200 250 290 310 450360 490400 500 520 550
90
100
80
70
60
50
40
WDR-240 series
240WSingleOutputIndustrialDINRAIL PowerSupply