General Purpose US Fuses
General Purpose US Fuses
GPUS11
American Power Fuses
AMP-TRAP 2000®
A2D and A6D (Class RK1 TD)
12/04
Upgrade yesterday’s circuits to today’s
Type 2 protection
Amp-trap 2000®SmartSpot®A2D, A6D fuses now
provide a visual open fuse indicator. With advanced materi-
al technology added to the existing product line the A2D,
A6D fuses provide IEC Type “2” (No Damage) protection to
main, feeder, and branch circuits, for all types of loads —
A2D, A6D’s time delay characteristics for handling harmless
in-rush currents, its current limiting ability and wide range
of ratings (from 1 to 600 Amperes) — give excellent
protection for all your applications.
Features/Benefits
• Solid State SmartSpot Indicator
• Time delay for motor starting and transformer inrush
currents without nuisance opening
• 300kA interrupting rating - self-certified,
UL witnessed tests
• Extremely Current Limiting for low peak let-thru
current
• Easy 2-to-1 selectivity for prevention of nuisance
shut downs and “black outs”
• Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
• High-visibility orange label gives instant
recognition
• Reduced inventory by taking the place of RK5,
K, and H fuses
• Metal-embossed date and catalog number for easier
traceability and lasting identification
• Fiberglass body provides dimensional stability in harsh
industrial settings
• Brass end-caps (blade-style) for cooler operation and
superior performance
Ratings
A2D AC: 1/10 to 600A 250VAC, 200kA I.R.
(self certified for250VAC, 300kA I.R.,
UL witnessed)
A6D AC: 1/10 to 600A 600VAC, 200kA I.R.
(self certified for 600VAC, 300kA I.R.)
Highlights
• SmartSpot Indicator
• Time Delay
• Current Limiting
• Plated Terminals
Applications
• Motors
• Safety Switches
• Transformers
• Branch Circuit Protection
• Disconnects
• Control Panels
• All General-purpose Circuits
Approvals
• UL Listed to Standard 248-12
• CSA Certified to Standard
C22.2 No. 248.12
General Purpose US Fuses
General Purpose US Fuses
GPUS12
American Power Fuses
AMP-TRAP 2000®
A2D and A6D (Class RK1 TD)
12/04
Ampere Cat. Number Ref. Number Amp. Cat. Number Ref. Number
Rating 250V 600V 250V 600V Rating 250V 600V 250V 600V
1/10 A2D1/10R A6D1/10R Q215248 R201932 10 A2D10R A6D10R Z216268 G211675
15/100 A2D15/100R A6D15/100R M217292 D212707 12 A2D12R A6D12R Z216774 M212186
2/10 A2D2/10R A6D2/10R J223085 C216271 15 A2D15R A6D15R R217802 N213222
3/10 A2D3/10R A6D3/10R K212184 G219357 17-1/2 A2D17-1/2R A6D17-1/2R C218318 E213720
4/10 A2D4/10R A6D4/10R N214740 E201415 20 A2D20R A6D20R P200872 C216777
1/2 A2D1/2R A6D1/2R T215757 P211153 25 A2D25R A6D25R B201412 Q217295
6/10 A2D6/10R A6D6/10R R218837 N214234 30 A2D30R A6D30R B212705 E219884
8/10 A2D8/10R A6D8/10R Q200873 D216778 35 A2D35R A6D35R L213220 W222567
1 A2D1R A6D1R Q218836 M214233 40 A2D40R A6D40R R215249 S201933
1-1/8 A2D1-1/8R A6D1-1/8R K213219 V222566 45 A2D45R A6D45R V215758 Q211154
1-1/4 A2D1-1/4R A6D1-1/4R A212704 D219883 50 A2D50R A6D50R N217293 E212708
1-4/10 A2D1-4/10R A6D1-4/10R B213717 L223087 60 A2D60R A6D60R E219355 R214743
1-6/10 A2D1-6/10R A6D1-6/10R J214230 R200874 70 A2D70R A6D70R N201929 E218320
1-8/10 A2D1-8/10R A6D1-8/10R M214739 D201414 75 A2D75R - L211150 -
2 A2D2R A6D2R P201930 V217805 80 A2D80R A6D80R D211672 S218838
2-1/4 A2D2-1/4R A6D2-1/4R C219882 T215251 90 A2D90R A6D90R J212183 F219356
2-1/2 A2D2-1/2R A6D2-1/2R D219354 Q214742 100 A2D100R A6D100R P215247 N211152
2-8/10 A2D2-8/10R A6D2-8/10R S222564 X215760 110 A2D110R A6D110R S215756 F211674
3 A2D3R A6D3R C213718 M223088 125 A2D125R A6D125R Y216267 L212185
3-2/10 A2D3-2/10R A6D3-2/10R E211673 T218839 150 A2D150R A6D150R Y216773 C212706
3-1/2 A2D3-1/2R A6D3-1/2R M211151 F218321 175 A2D175R A6D175R L217291 M213221
4 A2D4R A6D4R A216269 H211676 200 A2D200R A6D200R Q217801 D213719
4-1/2 A2D4-1/2R A6D4-1/2R K214231 S200875 225 A2D225R A6D225R B218317 L214232
5 A2D5R A6D5R S217803 P213223 250 A2D250R A6D250R P218835 P214741
5-6/10 A2D5-6/10R A6D5-6/10R A216775 N212187 300 A2D300R A6D300R C219353 S215250
6 A2D6R A6D6R T222565 V215252 350 A2D350R A6D350R B219881 W215759
6-1/4 A2D6-1/4R A6D6-1/4R D218319 F213721 400 A2D400R A6D400R R222563 B216270
7 A2D7R A6D7R K223086 Y215761 450 A2D450R A6D450R H223084 B216776
8 A2D8R A6D8R C201413 R217296 500 A2D500R A6D500R N200871 P217294
9 A2D9R A6D9R Q201931 W217806 600 A2D600R A6D600R A201411 T217804
Standard Fuse Ampere Ratings
Ampere A B C D E
Rating In. mm In. mm In. mm In. mm In. mm
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-/8 149 1-1/16 27 1/8 3 3/4 19 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
0-60A
61-600A
250V-A2D
600V-A6D
General Purpose US Fuses
General Purpose US Fuses
GPUS13
American Power Fuses
AMP-TRAP 2000®
A2D and A6D (Class RK1 TD)
12/04
A variety of pole configurations and termination provisions is available.
Recommended Fuse Blocks with Box Connectors
for Amp-trap®Class RK1 Fuses
Fuse Catalog Number Reference Number
Ampere 250V 250V
Rating 1 Pole 3 pole 1 pole 3 pole
0-30 20306R 20308R T213411 K215956
31-60 20606R 20608R B212383 E214939
61-100 21036R 21038R D201621 M212899
101-200 22001R 22003R R213915 G214941
201-400 24001R 24003R J219566 D222022
401-600 2631R 2633R H214942 P215960
Fuse Catalog Number Ref. Number
Ampere 600V 600V
Rating 1 Pole 3 pole 1 pole 3 pole
0-30 60306R 60308R H212389 K214438
31-60 60606R 60608R K212391 M214440
61-100 61036R 61038R W204788 Z211875
101-200 62001R 62003R V212906 B213924
201-400 64001R 64003R D219055 M222030
401-600 6631R 6633R J216990 E218021
TIME IN SECONDS
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
A2D 15 to 600
General Purpose US Fuses
General Purpose US Fuses
GPUS14
American Power Fuses
AMP-TRAP 2000®
A2D and A6D (Class RK1 TD)
12/04
TIME IN SECONDS
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
A2D 1/10 to 10
CURRENT IN AMPERES
TIME IN SECONDS
MELTING TIME – CURRENT DATA,600V FUSES
A6D 15 to 600
General Purpose US Fuses
General Purpose US Fuses
GPUS15
American Power Fuses
AMP-TRAP 2000®
A2D and A6D (Class RK1 TD)
12/04
CURRENT IN AMPERES
TIME IN SECONDS
MELTING TIME – CURRENT DATA, 600V FUSES
A6D 1/10 to 8
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data
A2D 30 to 600, 250 Volts AC Peak Let-Thru Current Data
A6D 30 to 600, 600 Volts AC
NOTE
: SEE APPLICATION INFORMATION SECTION OF CATALOG (LOW VOLTAGE FUSES FOR MOTOR PROTECTION) FOR GUIDE-
LINES ON THREE PHASE MOTOR FUSE SELECTION, CLASS RK1 A2D & RK1 A6D FUSES