OUTPUT SPECIFICATIONS
Voltage set point -48V ±0.1V @ 10A
Total regulation Main output ±5.0%
(Full load to no load) Auxiliary output, 5V, 0.5A max. ±5.0%
Rise time At turn-on 1.0s, max.
Transient response Main output 5.0% max. dev.,
75% to 100% 1ms recovery
step at 0.1A/µs
Ripple and noise Main output 1.0V pk-pk,
(20MHz)
Overvoltage protection latching -57V to -60V min.
Output power limit 1200W
Short circuit protection Yes
Current sharing ±10% sharing 0.1V/A droop
1/3L to FL
INPUT SPECIFICATIONS
Input voltage range 1000W 90 to 264VAC
1200W 108 to 264VAC
Input frequency range 47Hz to 63Hz
Input surge current 25°C cold start 36A typ.
Input surge 300VAC 20ms
Safety ground 254.4VAC, 50Hz 2.5mA
leakage current
Input current 90VAC, 1000W 14A rms max.
Input fuse Replaceable 20A
Power factor 110VAC 0.99
220VAC 0.98
DPF1000 SERIES
Dual output
[ 2 YEAR WARRANTY ]
• 1000W front end
• EN61000-3-2 compliant
• 11 x 6.0 x 5.0 inch size
• Hot pluggable
• N+1 redundancy
• Full set of status signals
• EN55022, EN55011 conducted emissions level A
• UL, VDE and CSA safety approvals
The DPF1000 is a 1000W universal input AC/DC front end power supply in a fully
enclosed hot pluggable case with built-in fan, handle, IEC input connector, on/off
switch and DIN output signal connector. Providing dual 48V and 5V outputs with a full
set of status signals. The DPF1000 is designed for use as a front end in medium
power communication applications adopting distributed power architecture. The
DPF1000 is fully compliant with EN61000-3-2. Standard features include current
sharing and full protection against overvoltage, overload and short circuit. Remote or
local system monitoring is possible via a full set of status signals that include fan fail,
DC good, power fail, remote inhibit and current monitoring. The DPF1000, with full
international safety approval and the CE mark, meets conducted emissions EN55022
level A. The DPF1000 can be used in conjunction with our complete range of 3 to
200W DC/DC converters to fully configure a distributed power system.
SPECIFICATION
All specifications are typical at nominal input, full load at 25°C unless otherwise stated
PAGE 1
Notes
1 3 orthogonal axes, random vibration, 10 minute test per axis.
EMC CHARACTERISTICS
Radiated noise EN55022/11, FCC part 15 Level A
Conducted noise EN55022/11 Level A
FCC part 15 Level A
Harmonic current emm. EN61000-3-2 Compliant
Electrical fast EN61000-4-4 Level 3
transients/bursts
Surge susceptibility EN61000-4-5 Level 3
GENERAL SPECIFICATIONS
Hold-up time 110VAC, 60Hz 20ms @ 1000W
Efficiency 110VAC @ 1kW 77% min.
Isolation voltage Input/output 3000VAC
Input/chassis 1500VAC
Switching frequency 200kHz
Approvals and VDE0805, EN60950, IEC950
standards UL1950, BABT
CSA C22.2 No. 950
Weight 4.3kg (9.5Ibs)
MTBF MIL-HDBK-217F 80,000 hours
@ 25°C full load
ENVIRONMENTAL SPECIFICATIONS
Thermal performance Operating ambient, FL 0°C to +50°C
Non-operating -40°C to +70°C
50°C to 70°C Derate linearly
ambient to 50% at +70°C
Cooling Built-in fan
Relative humidity Operating 5% to 85% RH
Altitude Operating 10,000 feet max.
Non-operating 30,000 feet max.
Vibration (See Note 1) 5Hz to 500Hz 2.4G rms peak
Shock MIL-STD-810E 516.4 Part IV