Single Phase External Power Line Filter for Frequency Converters
The FC filters provide filtering for frequency inverters and
variable speed motor drives. Designed for very noisy
applications, they attenuate conducted interference at low
and high frequency ranges and protect programmable
logic controllers from RF noise on the AC power line. These
filters perform best when installed on the line side of the
motor drive. The FC filters better prevent noise from
returning to the line, enabling equipment to meet strict
European regulations on RFI.
Suited for field wiring applications, these filters are ideal for
EMC troubleshooting and field refurbishing. The FC filters
feature side flanges for easy mounting and DIN type
terminals which eliminate live metal parts, allowing safer
and easier connection. The filters could also be sold as an
accessory to motor drives marketed into Europe.
Specifications
Maximum leakage current,each line-to-ground
@120 VAC 60 Hz: 3.8 mA
@250 VAC 50 Hz: 6.7 mA
Hipot rating (one minute):
line-to-ground 2250 VDC
line-to-line 1450 VDC
Operating frequency: 50/60 Hz
Rated voltage (max.): 250 VAC
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current Frequency–MHz
Rating .01 .03 .05 .1 .5 1 5 10 30
06A 9 19 26 37 65 65 50 40 35
12A 5 17 25 37 65 65 65 60 35
16A 4 15 22 36 65 65 70 70 35
25A 2 14 22 36 75 75 70 70 48
36A 0 6 14 27 68 75 70 70 50
Line-to-line in 50 ohm circuit
Current Frequency–MHz
Rating .01 .03 .05 .1 .5 1 5 10 30
06A 10 10 35 60 75 75 60 50 45
12A 14 14 30 51 75 75 75 70 45
16A 14 14 29 55 75 75 75 70 45
25A 14 14 17 42 75 75 70 70 50
36A 14 14 17 42 75 75 70 70 50
58 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
FC Series
FC Series
CORCOM Product Guide
UL Recognized
Electrical Schematics
LINE LOAD
LINE LOAD
Resistor location for reference only.
6 & 12 Amps
16, 25 & 36 Amps
FC10
Single Phase External Power Line Filter for Frequency Converters (Continued)
Case Dimensions
ABCDEF
± .020 ± .010
Part No. (max) (max) (max) (max)
± .51 ± .254
6FC10 4.60 3.10 1.78 2.677 3.70 2.00
116.8 78.7 45.21 67.8 94.0 50.8
12FC10 5.95 3.96 2.18 3.50 4.53 2.00
151.3 100.6 55.4 88.9 114.8 50.8
16FC10 5.95 3.96 2.18 3.50 4.53 2.00
151.3 100.6 55.4 88.9 114.8 50.8
25FC10 6.90 5.48 2.55 4.90 5.94 2.756
175.3 139.2 64.77 124.5 150.9 70.0
36FC10 6.90 5.48 2.55 4.90 5.94 2.756
175.3 139.2 64.77 124.5 150.9 70.0
59
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
RFI Power Line Filters
FC Series
CORCOM Product Guide
Case Styles
6, 12, 16FC10
25, 36FC10
LINE
LOAD
F
E
A
D
C
B
Hole: .203 x .156
5.16 x 3.96 (4)
8-32 Screws (2)
This hole indicates the "Line"
side and may be on either flange.
6FC10, 12FC10, 16FC10
Phoenix contact VDFK4
Accepts 10 AWG solid wire, 12 AWG stranded wire
Torque Spec: 5.5 - 7.0 in.lb
25FC10, 36FC10
Phoenix contact VDFK6
Accepts 8 AWG solid wire, 10 AWG stranded wire
Torque Spec: 13.5 - 16 in.lb
F
E
A
D
C
B
Slots: .260 x .156
6.60 x 3.96 (4)
8-32 Screws (2)
This hole indicates the "Line" side
and may be on either flange.
Part Numbers
06FC10 25FC10
12FC10 36FC10
16FC10